| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.3 LAccepted-AOC | L1 | Accepted-AOC Accepted as L1 | |
| 2 | L2₹38.5 L+₹73,614 (1.95%)Rejected-Finance SADASHIV PHUGE NAGAR OPP SANDVIK FACTORY RADHIKA RESIDENCY F WING FLAT NO 7 PHUGEWADI PUNE 411 012 | PUNE | MAHARASHTRA | 411012 | L2 | Rejected-Finance Rejected | |
| 3 | L3₹46.5 L+₹8.7 L (23.1%)Rejected-Finance RH NO 06 KARMA KSHETRA HOUSING SOCIETY SECTOR 29 PRADHIKARAN RAVET POST DEHU ROAD 412 101 | NA | NA | 412101 | L3 | Rejected-Finance Rejected | |
| 4 | L4₹49.9 L+₹12.1 L (32.1%)Rejected-Finance | L4 | Rejected-Finance Rejected |
Tender Value
₹41 L
EMD Value
₹82,000
Closing Date
12 Jun 2021, 6:00 pmClosed
GE Dehu Road, Pune
GE Dehu Road, Pune
SPL REP MO TO LT PANELS AT ASHOK NAGAR AREA SPL REP FOR REPLACEMENT OF LT APFC PANEL IN LIEU OF HT CAPACITOR BANK SPL REP MO UG CABLES POLES AND PANELS AT 29 FAD SPL REP EXTERNAL ELECT SUP AT PERIMETER OF COD DEPOT UNDER GE DEHU ROAD
2021_MES_435626_2
8508
Open Tender
Civil Works
Item Rate
270 days
GE Dehu Road, Pune
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE Dehu Road, Pune
₹82,000
Yes
12 Jul 2021
22 May 2021
17 Jun 2021
22 May 2021
12 Jun 2021
29 May 2021
Amount
Taking out of LT cable of any size & Supply,laying,jointing , testing and commisioning XLPE cable 1100 volts grade PVC insulated armoured & PVC sheathed with stranded aluminium conductor heavy duty ISI marked incl cable glands lugs bolts nuts washers etc to suit the cable size to be laid in trenches fixed along pole, LT pannel floor or through GI pipe laid under floors, etc complete of following sizes (NOTE :- Excavation and earth work shall be measured at separately) :-
50 Sq mm x 3.5core
25 Sq mm x 4 core
16 Sq mm x 4 core
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depth and getting out Soft / loose soilall as specified and directed.
Returning, filling in soil, including spreading, leveling watering and well ramming in layers not exceeding 25 cm all as specified and directed.
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and directed by Engineer -in-Charge.
Supply & erect in repair in position steel tubular pole swaged type as per IS 2713 complete with MS base plate finial tapper plug cap bolt, nut, screws etc all as specified swaged pole of type 410 SP 31 , 09 mtrs long incl painting with two coats of aluminium paint over a coat of red oxide primer all as directed.
M&L for preparing old painted steel surfaces by scrubbing with wire brush and applying two coats of aluminium paint to 9 /11 mtr long LT steel tubular poles complete with connected fittings such as brackets, cross arms, metal portion etc and stick computer cut sticker radium number on the pole with of suitable high letters on 10 cm x 10 cm square block with black enamelled paint complete all as directed by Engineer-in-Charge
Only writing of pole numbers on existing pole nexe 0.1 sqm in area and applying one coat of synthetic enamel paint any tint
Restringing OH line of ACSR conductors of any description which includes replacement 22 SWG aluminium binding wire,removing jumper connections, reconnection with binding wire & jumper connections after restringing complete upto the satisfaction of Engr-in-Charge. NOTE :- Span includes 2 to 8 line of aluminium conductors of length upto 60 mtrs.
S&F in repairs ACSR conductor and strengthening on insulators including aluminium binding wire including reconnecting service connections any type which has been disconnected while dismantling old conductor complete all as specified and directed including dismantling of U/S conductor any type any size.
M & L for LT insulator, PIN type 1100 volts as per IS 1445 of size 100mm height, 65mm dia, porcelain, vitreous, white or brown including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut including taking down existing unserviceable insulator all as directed. Make;- Elpro or equivalent.
M & L for shackle type insulator as per IS 1445 working pressure in 1100 volts, 100mm height, 115mm dia porcelain, vitreous, white or brown insulator including galvanised mild steel straps of size 31x5mm, washers, insulator bolts of size 14mm dia, washers and nuts, including taking down of u/s shackle insulators complete all as directed by Engr-in-charge.
Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m (Note :- Reusable shall be kept at a suitable distance properly).
M&L cross arms, bracing supports, clamps, back plates, hooks etc fabricated from structural steel section (MS channel, angle sections, flat, round or square bars ) for reqd sizes and shape including bolts nuts & washers welding bending cutting cold or hot drilling holes for inserting in any shape or size as indicated or directed complete incl painting ( one red oxide primer coat two coats of aluminium paint ) complete.
S&F in repairs synthetic/PVC line separators of LT OH lines with nut,bolts & washers straight type horizontal configuration fixed at a point as directed and suitable for three phase 4 wire LT lines
Dismantling stay assembly complete, including demolition of concrete, etc. and excavation of earthwork measured separately)
M&L for Stay assembly with 16 mm stay rod complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately)
M&L for fixing of galvanised stay strand 7/4 mm complete with accessories all as spacified and directed by Engr in Charge.
M&L for Loop type insulator, vitreous porcelain, white, brown or green Small size, with overall dimensions 65 x 90mm, clearance of hole 16mm
M & L for plain cement concrete 1:3:6 type C1 (using 20mm graded stone aggregate) as in plinth, platforms, pole coping etc., all as specified and as directed.
M&L for provision of PCC 1:4:8, type D2 (using 40mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and as directed.
Supply & fixing in replacement of automatic street light switch using Nature Switch for automatic switching of street lights based on LUX level of natural light the sensor (nature switch) along with suitable power contactors and MCBs (Input-output) should be enclosed in pole/wall mountable enclosure made of rust proof, Electric shock proof, termite proof and FR grade SMC junction box (sintex make) conforming to IP 54.the contactor,MCBs and copper circuit wiring (min.16sqmm) should enough to take: three-phase load of 12KW;contactor Rating 80Amps; MCB(SPN) Rating 80Amps including making all connection all as specified and directed by engineer in Charge..MAKE:-Nature switch :Kakatiya energy systems pvt.ltd. hyderabad/bajaj/healer. Contactor:- BCH/L&T/Schneider or equivalent (as per IEC-60947-4-1/IS-13947-4-1), MCBs(Input-output):Hager/schneider/L&T/BCH or equivalent (as per IEC-60898/IS-8828),Circuit wiring : Finolex/polycab/RR Kable or equivalent. Model no SWADEEP-66-12KW3P.
Supply & fixing in replacement of automatic street light switch using Nature Switch for automatic switching of street lights based on LUX level of natural light the sensor (nature switch) along with suitable power contactors and MCBs (Input-output) should be enclosed in sheet steel enclosure made of rust proof, Electric shock proof, termite proof and FR grade conforming to IP 54.the contactor,MCBs and copper circuit wiring (min.10sqmm) should enough to take: Single-phase load of 5KW;contactor Rating 40Amps; MCB(sp) Rating 40Amps including making all connectiuon all as specified and directed by engineer in Charge.MAKE:-Nature switch :Kakatiya energy systems pvt.ltd. hyderabad/bajaj/healer. Contactor:- BCH/L&T/Schneider or equivalent (as per IEC-60947-4-1/IS-13947-4-1), MCBs(Input-output):Hager/schneider/L&T/BCH or equivalent (as per IEC-60898/IS-8828),Circuit wiring : Finolex/polycab/RR Kable or equivalent. Model no SWADEEP-02EC5KW1P.
M & L for earthing with galvanised steel earth plate electrode 60cmx60cmx6.3mm burried directly in ground earth pit not less than 2.25 m deep below normal ground level with top edge of the plate vertically to depth of not less than 1.5m below ground level connected to and including GI wire of size 4.0 mm dia as earthing lead welded with earth electrode (excluding GI protection pipe) and connecting to equipments by means of earthing lead connecting to equipments by means of GI bolts & nuts etc. with provision of char-coal and salt etc. all as per electrical plate No. 3 of SSR Part I, 2009 including RCC cover and MS angle iron frame watering arrangement with GI pipe 20mm dia (medium grade) & MS funnel, concrete pit including excavation and earthwork in any type of earth strata and testing on completion etc complete all as specified and directed by Engr-in-Charge
M & L for earthing with galvanised steel earth plate electrode 60cmx60cmx6.3mm burried directly in ground earth pit not less than 2.25 m deep below normal ground level with top edge of the plate vertically to depth of not less than 1.5m below ground level connected to and including GI strip of size 25 X 4 mm as earthing lead welded with earth electrode (excluding GI protection pipe) and connecting to equipments by means of GI bolts & nuts etc. with provision of char-coal and salt etc. all as per electrical plate No. 3 of SSR Part I, 2009 including RCC cover and MS angle iron frame watering arrangement with GI pipe 20mm dia (medium grade) & MS funnel, concrete pit including excavation and earthwork in any type of earth strata and testing on completion etc complete all as specified and directed by Engr-in-Charge
Material and labour in replaement for LED Street lighting 60W LED IP66 New generation energy saving & environmental friendly long life Versatile pressure die-cast aluminium with lens and toughened glass type roadway luminaire with high power LEDs as light source including electronic driver 72W LED 6000K including making connection with thre core aluminium conductor pvc cable from junction box to street light fitting all as specified. MAKE:- CAT PART NO LSTP-60-CDL-M of Crompton ,LHETBXU7PA6J060 OF HAVELLS, LR02-781-XXX-57-XX OF WIPRO,LSRT01S060XC of JAGUAR
Taking out of old panel & Supply instal testing and commissioning of CPRI approved factory make LT panel board outdoor type pedelstal mounted dust proof, weather proof, vermin proof front side double door hinge type with locking arrangement rear side single door hinge type with locking arangement, sheet steel cubical type with slanting roof made out of 3.0mm thick CRCA sheet with powder coated finished suitable length and size. High conductivity 3 phase and neutral Aluminium bus bar of 400 Amps capacity duly mounted on pre cast insulators including earth work excavation, PCC foundation necessary coping work, nuts and bolts and connecting electrically with suitable copper cable lug, cable glands etc complete all as specified and directed to accomodate the following items. Incoming:- (a) MCCB 160 amps 4 pole 16 KA - 1 Nos. (b) Advanced Multi functional meter 4420 series LCD meter C1 with RS481 MAKE :- CAT No WC442011OOOO of L&T /Seimens/schiender (d) LED type indication lamp for RYB. Outgoing: (a) MCCB 63 amps 4 pole 16 KA - 4 No
Material and labour for replacement of unserviceable street light bracket made out of GI pipe 1.2 mtr long 40mm dia medium grade bent to shape as directed including MS clamps made out of 40mmX6mm flat iron for fixing bracket suitable for PCC/ street poles including nuts and bolts of required size all as directed incl taking down of old unserviceable bracket.
Taking out of old Panel & Supply instal testing and commissioning of CPRI approved factory make LT panel board outdoor type pedelstal mounted dust proof, weather proof, vermin proof front side double door hinge type with locking arrangement rear side single door hinge type with locking arangement, sheet steel cubical type with slanting roof made out of 3.15mm thick CRCA sheet with powder coated finished suitable length and size. High conductivity 3 phase and neutral Aluminium bus bar of 400 Amps capacity duly mounted on pre cast insulators including earth work excavation, PCC foundation necessary coping work, nuts and bolts and connecting electrically with suitable copper cable lug, cable glands etc complete all as specified and directed to accomodate the following items. Incoming:- (a) MCCB 160 amps 4 pole 16 KA - 1 Nos. (b) Advanced Multi functional meter 4420 series LCD meter C1 with RS481 MAKE :- CAT No WC442011OOOO of L&/Seimens/Schiender (c) LED type indication lamp for RYB. Outgoing: (a) MCCB 63 amps 4 pole 16 KA - 03Nos. (b) MCCB 40 amps 4 pole 16 KA - 01 Nos
Taking out of old panel & Supply instal testing and commissioning of CPRI approved factory make LT panel board outdoor type pedelstal mounted dust proof, weather proof, vermin proof front side double door hinge type with locking arrangement rear side single door hinge type with locking arangement, sheet steel cubical type with slanting roof made out of 3.15mm thick CRCA sheet with powder coated finished suitable length and size. High conductivity 3 phase and neutral Aluminium bus bar of 400 Amps capacity duly mounted on pre cast insulators including earth work excavation, PCC foundation necessary coping work, nuts and bolts and connecting electrically with suitable copper cable lug, cable glands etc complete all as specified and directed to accomodate the following items. Incoming:- (a) MCCB 160 amps 4 pole 16 KA - 1 Nos. (b) Advanced Multi functional meter 4420 series LCD meter C1 with RS481 MAKE :- CAT No WC442011OOOO of L&T /Seimens/schiender (d) LED type indication lamp for RYB. Outgoing: (a) MCCB 40 amps 4 pole 16 KA - 5 No
Supply, laying HDPE DWC pipe flexible type of size 40 mm dia for protection of LT cable laid in trenches including insertion of the cable complete all as specified and directed by Engr-in -Charge
Fixing only MS cross arms, bracing supports, clamps, back plates, hooks etc fabricated from structural steel section dismantled from existing LT poles of any type or description complete all as specified and directed.
S & F Cradles hexagonal or rectangular fabricated with galvanised steel wires 4 mm or 3.15 mm dia for road crossings, HT and LT conductors etc., including dismantling existing U/S cradles all as directed.
Supply instal testing and commissioning of CPRI approved factory make LT panel board outdoor type pedelstal mounted dust proof, weather proof, vermin proof front side double door hinge type with locking arrangement rear side single door hinge type with locking arangement, sheet steel cubical type with slanting roof made out of 3.15mm thick CRCA sheet with powder coated finished suitable length and size. High conductivity 3 phase and neutral Aluminium bus bar of 400 Amps capacity duly mounted on pre cast insulators including earth work excavation, PCC foundation necessary coping work, nuts and bolts and connecting electrically with suitable copper cable lug, cable glands etc complete all as specified and directed to accomodate the following items. Incoming:- (a) On load change over switch 415V of capacity 160 amps. -01 (b) MCCB 160 amps 4 pole 16 KA - 1 Nos. (b) Advanced Multi functional meter 4420 series LCD meter C1 with RS481 MAKE :- CAT No WC442011OOOO of L&/Seimens/Schiender (d) LED type indication lamp for RYB. Outgoing: (a) MCCB 63 amps 4 pole 16 KA - 04Nos.
Supply instal testing and commissioning of CPRI approved factory make LT panel board outdoor type pedelstal mounted dust proof, weather proof, vermin proof front side double door hinge type with locking arrangement rear side single door hinge type with locking arangement, sheet steel cubical type with slanting roof made out of 3.15mm thick CRCA sheet with powder coated finished suitable length and size. High conductivity 3 phase and neutral Aluminium bus bar of 400 Amps capacity duly mounted on pre cast insulators including earth work excavation, PCC foundation necessary coping work, nuts and bolts and connecting electrically with suitable copper cable lug, cable glands etc complete all as specified and directed to accomodate the following items Incoming:- (b) MCCB 250 amps 4 pole 16 KA - 1 Nos. (b) Advanced Multi functional meter 4420 series LCD meter C1 with RS481 MAKE :- CAT No WC442011OOOO of L&/Seimens/Schiender (d) LED type indication lamp for RYB. Outgoing: (a) MCCB 100 amps 4 pole 16 KA - 03Nos. (b) MCCB 63 amps 4 pole 16 KA - 01Nos.
Supply, install, connect, test and commissioning capacitor bank of capacity 15 KVAR (1x1+2x2+10x1), 3 Phase, 4 Wire, 50Hz, 433 Volts, 50 KA fault level, outdoor LT power factor improvement panel IP-54 of size 600mm x 700mm x 400mm, fully automatic type including power factor sensors for correcting the power factor from 0.9 to 0.99 necessary contactors with electrolytic aluminium bus bar 25 x 5 x 3mm with SMC support, dust and vermin proof, cubical, free standing floor mounting type, mounted on floor/over the duct, with required mounting channel, capcitor banks installed inside the panel, and electric connection to the main distribution panel etc., panel fabricated of 2mm thick CRCA steel sheet for doors and frame, 1.62mm thick for partition compartmentalized design and suitable size MS angle iron frame duly pretreated and powder coated, factory fabricated panel suitable for and acommodating and including the components complete all as described as per the details in particular specifications. (Note:- The Panel shall be OEM made and tested at OEM factory INCOMER MCB, D curve , 63Amp,TP ,10KA - 1 nos.L&T/Schneider/ Siemens Phase Indicating Lamps 3nos-1 set,L&T/Schneider/ Siemens Current Transformer (100/5A)- 1 setL&T/Schneider /MODL Siemens/VCA APFC CONTROLLER 8 steps with Microprocessor Based,96X96mm, Should display Lead Kvar &Lag Kvar on hourly basic including Bluetooth connectivity for remote measurement and settings - 1 no.L&T/Schneider /MODL Siemens/VCA Cooling Fans 1 no -Reputed Standard 10KVAr MPP Cylindrical Capacitor Fixed type - 01 No Schneider/ VAC/L&T/Epcos OUTGOING Indicating Lamps (ON.OFF)- L&T/Schneider/Siemens FOR 1 kVAr - 1 STEPS MCB- TYPE D, 10AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 01 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 2 KVAr - 2 STEPS MCB- TYPE D, 10AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 02 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 5 KVAr - 2 STEPS MCB- TYPE D, 25AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 02 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 10 kVAr - 2 STEPS MCB- D curve, 25AMP,TP - 01 no. L&T/Schneider/Seimens. Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 01 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 01 No Schneider/VAC/L&T/Epcos/Jaivic. FOR HARDWARE Mechanical Hardware Set inclusive of Door handle,Busbar,nuts,bolts,screws,hinges, rating plate,stickers,electrical hradware setinclusive of lugs,connectors,terminal blocksferrules,sleeves etc. Reputed Standard.
Supply, install, connect, test and commissioning capacitor bank of capacity 25 KVAR (1x1+2x2+ 5x2+10x1), 3 Phase, 4 Wire, 50Hz, 433 Volts, 50 KA fault level, outdoor LT power factor improvement panel IP-54 of size 600mm x 700mm x 400mm, fully automatic type including power factor sensors for correcting the power factor from 0.9 to 0.99 necessary contactors with electrolytic aluminium bus bar 25 x 5 x 3mm with SMC support, dust and vermin proof, cubical, free standing floor mounting type, mounted on floor/over the duct, with required mounting channel, capcitor banks installed inside the panel, and electric connection to the main distribution panel etc., panel fabricated of 2mm thick CRCA steel sheet for doors and frame, 1.62mm thick for partition compartmentalized design and suitable size MS angle iron frame duly pretreated and powder coated, factory fabricated panel suitable for and acommodating and including the components complete all as described as per the details in particular specifications. (Note:- The Panel shall be OEM made and tested at OEM factory INCOMER MCB, D curve , 63Amp,TP ,10KA - 1 nos.L&T/Schneider/ Siemens Phase Indicating Lamps 3nos-1 set,L&T/Schneider/ Siemens Current Transformer (100/5A)- 1 setL&T/Schneider /MODL Siemens/VCA APFC CONTROLLER 8 steps with Microprocessor Based,96X96mm, Should display Lead Kvar &Lag Kvar on hourly basic including Bluetooth connectivity for remote measurement and settings - 1 no.L&T/Schneider /MODL Siemens/VCA Cooling Fans 1 no -Reputed Standard 10KVAr MPP Cylindrical Capacitor Fixed type - 01 No Schneider/ VAC/L&T/Epcos OUTGOING Indicating Lamps (ON.OFF)- L&T/Schneider/Siemens FOR 1 kVAr - 1 STEPS MCB- TYPE D, 10AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 01 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 2 KVAr - 2 STEPS MCB- TYPE D, 10AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 02 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 5 KVAr - 2 STEPS MCB- TYPE D, 25AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 02 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 10 kVAr - 01 STEPS MCB- D curve, 25AMP,TP - 01 no. L&T/Schneider/Seimens. Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 01 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 01 No Schneider/VAC/L&T/Epcos/Jaivic. FOR HARDWARE Mechanical Hardware Set inclusive of Door handle,Busbar,nuts,bolts,screws,hinges, rating plate,stickers,electrical hradware setinclusive of lugs,connectors,terminal blocksferrules,sleeves etc. Reputed Standard.
Supply, install, connect, test and commissioning capacitor bank of capacity 35 KVAR (1x1+2x2+5x2+10x2), 3 Phase, 4 Wire, 50Hz, 433 Volts, 50 KA fault level, outdoor LT power factor improvement panel IP-54 of size 600mm x 700mm x 400mm, fully automatic type including power factor sensors for correcting the power factor from 0.9 to 0.99 necessary contactors with electrolytic aluminium bus bar 25 x 5 x 3mm with SMC support, dust and vermin proof, cubical, free standing floor mounting type, mounted on floor/over the duct, with required mounting channel, capcitor banks installed inside the panel, and electric connection to the main distribution panel etc., panel fabricated of 2mm thick CRCA steel sheet for doors and frame, 1.62mm thick for partition compartmentalized design and suitable size MS angle iron frame duly pretreated and powder coated, factory fabricated panel suitable for and acommodating and including the components complete all as described as per the details in particular specifications. (Note:- The Panel shall be OEM made and tested at OEM factory INCOMER MCB, D curve , 63Amp,TP ,10KA - 1 nos.L&T/Schneider/ Siemens Phase Indicating Lamps 3nos-1 set,L&T/Schneider/ Siemens Current Transformer (100/5A)- 1 setL&T/Schneider /MODL Siemens/VCA APFC CONTROLLER 8 steps with Microprocessor Based,96X96mm, Should display Lead Kvar &Lag Kvar on hourly basic including Bluetooth connectivity for remote measurement and settings - 1 no.L&T/Schneider /MODL Siemens/VCA Cooling Fans 1 no -Reputed Standard 10KVAr MPP Cylindrical Capacitor Fixed type - 01 No Schneider/ VAC/L&T/Epcos OUTGOING Indicating Lamps (ON.OFF)- L&T/Schneider/Siemens FOR 1 kVAr - 1 STEPS MCB- TYPE D, 10AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 01 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 2 KVAr - 2 STEPS MCB- TYPE D, 10AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 02 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 5 KVAr - 2 STEPS MCB- TYPE D, 25AMP,TP - 02 No L&T/Schneider/Siemens Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 02 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 02 No Schneider/VAC/L&T/Epcos/Jaivic. FOR 10 kVAr - 2 STEPS MCB- D curve, 25AMP,TP - 01 no. L&T/Schneider/Seimens. Capasitor duty contactor, including current ,ON/OFF monitiring and display system - 01 No L&T/Schneider/MODL seimens/VAC Capacitor MPP CYLINDRICAL - 01 No Schneider/VAC/L&T/Epcos/Jaivic. FOR HARDWARE Mechanical Hardware Set inclusive of Door handle,Busbar,nuts,bolts,screws,hinges, rating plate,stickers,electrical hradware setinclusive of lugs,connectors,terminal blocksferrules,sleeves etc. Reputed Standard.
M/S kirpan Enterprises
Shri Sai Electricals
Mahindra Electric Stores
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .