Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹22.6 LAccepted-AOC | 1 | Accepted-AOC L1 | |
| 2 | 2₹31.4 L+₹8.7 L (38.6%)Rejected-Finance 16 12A SWAMIJI ROAD NEAR SABUJ SANGHA KOLKATA WEST BENGAL 700060 | KOLKATA | WEST BENGAL | 700060 | 2 | Rejected-Finance L2 | |
| 3 | 3₹33.3 L+₹10.7 L (47.0%)Rejected-Finance 56 ARUNACHALAM MAIN ROAD AMBAL NAGAR PORUR CHENNAI TAMIL NADU 600116 | THIRUVALLUR | TAMIL NADU | 600116 | 3 | Rejected-Finance L3 |
Tender Value
₹45.7 L
EMD Value
₹91,400
Closing Date
5 Jul 2022, 4:00 pmClosed
The GM,STPS.
Admin Bldg., STPS,Santaldih,Purulia-723146
Maintenance work of 315 MVA Generator Transformer-6 (SL. No. 6006559), UAT-6A, UAT-6B and ST-5 during U-6 OH period under EMOPH department
2022_WBPDC_382215_1
WBPDCL/STPS/ NIT / E2779/22-23
Open Tender
Electrical Work/ Equipment
Item Rate
26 days
Admin Bldg., STPS, Santaldih, Purulia-723146
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹91,400
Yes
Admin Bldg., STPS,Santaldih,Purulia-723146
21 Aug 2022
30 May 2022
7 Jul 2022
31 May 2022
5 Jul 2022
9 Jun 2022
7 Jun 2022
Amount
Maint. work for GT#6 in OH
Job for Isolation of GT#6 from both terminal with dismantling and Removing of Twin Moose Connector & LV side Flexible Connector after clearance
Assistance for Testing work of transformer along with bushing before O/H
Disconnection of oil lines to conservator tank and oil equalizer line form top area & Blanking work prior oil draining at reasonable level
Trf conservator Tank Lifting for air cell healthiness checking with Dry air, pressure test,MOG & both side gasket replacement and placement on base.
Disconnection & refixing of Twelve (12) nos Radiator bank from header and two Bottom header valve line (250NB) for Maint. Of valve by change of O-ring & gasket due oil leakage as per instruction.
Dismantling & Lifting of LV turret from base & Assistance to OEM (BHEL) for rectification of Hotspot in LV turret area and necessary maintenance work like changes of Bolt, Stud, as per instruction and again placement upon base
Dismantling & Fitting of Twelve (12) GT Cooler Fans after OH of Motor (to be done by other agency)
Dismantling & Fixing of Buchholz Relay WTI, OTI, PRV, other flange gaskets (LV or HV side inspection door, equalizing pipe flanges, radiator flanges etc.) with change of gasket/O-ring OLTC diverter top area and any other related tit bit jobs
Oil Filtration by filter machine (To be provided by WBPDCL) till desired parameter of oil due to exposure to air after completion of jobs & oil Filling and proper Venting.
Assistance for Final Testing Reconnection of HV & LV Terminal after completion of maintenance work & Deputation of Skilled Manpower during Charging of GT#6 for 12 hours or more as per situation during unit synchronization.
Maint. work of UAT#6A
Assistance for testing of UAT before overhauling job prior LV, HV side disconnection
Disconnection of oil lines to conservator tank & 100NB equalizer line & Blanking work prior oil draining at reasonable level & Fixing of gasket & O-ring in top area inspection door, Line flanges, PRV, 4 nos CT terminal & allied parts
Job Assistance to OEM for UAT OLTC Servicing / maintenance work as per CTR necessary with oil draining & fill up and new OLTC area gasket fixing
Conservator Tank Lifting for Air Cell Healthiness checking by Dry air,pressure testing MOG & necessary gasket replacement and placement on base with oil line.
Transformer Oil Filtration after completion of jobs as required BDV value due to exposure to air during maintenance works prior Oil Filling
Transformer oil top up as necessary upto conservator level & venting as required & transformer body cleaning, final leakage checking after completion of jobs
Replacement of cable with termination for LV, HV & Neutral side current transformer with gasket replacement job and assistance for testing work
Checking & Cleaning of Neutral grounding resistance bank with cover dismantling & fixing
Assistance for Final Testing after Cooling Fan dismantling & re-fixing after checking/OH, connection of both Terminal
Maint. job for UAT#6B
Assistance for testing of UAT before overhauling job prior LV, HV side disconnection
Disconnection of oil lines to conservato tank & 100NB equalizer line & Blanking work prior oil draining at level & Fixing of gasket & O-ring in top area inspection door, Line flange, PRV, 4 nos CT terminal & allied parts
Job Assistance to OEM for UAT OLTC fixing.Servicing / maintenance work as per of OEM personal (CTR) as necessary with oil draning & fil up & new OLTC area gasket fixing.
Conservator Tank Lifting for Air Cell Healthiness checking by Dry air, pressure testing MOG & necessary gasket replacement and placement on base with oil line.
Transformer Oil Filtration after completion of jobs as required BDV value due to exposure to air during maintenance works prior Oil Filling.
Transformer oil top up as necessary upto conservator level & venting as required & transformer body cleaning, final leakage checking after completion of jobs
Checking & Cleaning of neutral grounding bank, Replacement of cable with termination for LV, HV & Neutral side CT & Assistance for Final Testing, Reconnection of HV & LV Terminal after completion
Drying Out Process of UAT#6B
Disconnection & shifting of 12 nos radiator bank from transformer body and proper preservation of each till completion of drying process.
Full Oil Down from main tank and storing in oil tanks for Transformer Dry out
Heating & Drying out of Transformer, Oil filling under vacuum as per proper procedure with Dismantling of transformer bushings if required, all radiator bank AND Alumina Chamber, of transformer pipe line, bellows between transformer & bus duct etc
N2 sealing & Vacuum process of 20MVA UAT #6B with Disconnection, Dismantle & other related jobs along with Blanking & preservation of cannibalized components with N2 gas dew point -70°C
Assemblimg of all parts after successful completion of dry out & vacuum process and Oil Filling inside tank with fixed radiator bank.
Maint. Job for ST#5
Assistance for Testing work ST#5 with bushing before O/H, LV, HV side disconnection
Disconnection of oil lines to conservator tank & 100NB equalizer line & Blanking, prior oil draining at level & Fixing of gasket & O-ring in top area inspection door, Line flanges, PRV, 9 nos CT terminal & allied parts.
Conservator Tank Air Cell Healthiness checking by Dry air, MOG checking & necessary gasket replacement after lifting from base and placement and Assistance to OEM for OLTC servicing
Dismantling of transformer pipe line from main tank, Buchholz Relay etc if required and Change of gaskets such as Man-hole gaskets, WTI & OTI Gaskets, PRV, Buch. Relay gaskets, (LV side inspection, equalizing pipe flanges,radiator flanges etc.)
Transformer Oil Filtration after completion of jobs still as required BDV value of oil due to exposure to air during maintenance works prior Oil Filling.
Transformer Surface cleaning oil settling, venting Jobs after completion of oil filtration, & Assistance for Final Testing, Reconnection of HV & LV Terminal after completion
TECHNO ENGINEERING
SHREE ABIRAMI ENGGINEERING WORKS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .