Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.4 LAccepted-Finance BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | ₹5.4 L | L1 | Accepted-Finance L1 Bidder. |
| 2 | L2₹5.5 LRejected-Finance 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | ₹5.5 L | L2 | Rejected-Finance Not L1 Bidder. |
| 3 | L3₹6.0 LRejected-Finance 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | ₹6.0 L | L3 | Rejected-Finance Not L1 Bidder. |
| Sl No | Description | Qty | Unit | Computer Gallery L1 | PERFECT IMAGE SOLUTIONS L3 | Creative Projects L2 |
|---|---|---|---|---|---|---|
| 1.00 | Checking, Rectification, Re-Installation, Testing and Re-Commissioning of Addressable fully networkable fire alarm control Panel EN Standred VDS approved 4 Loops Expendabele upto 18 loop, loop card wich will have 127 devices of both detectors and modules in a single line circuit on any combination. (Approved Make: Honeywell-Esser) | 1 | Job | 60,000 ₹60,000 | 22,000 ₹22,000 | 30,000 ₹30,000 |
| 2.00 | Checking, Re-Installation, Testing and Commissioning of VDS approved Addressable Multi Sensor - Smoke cum Heat detector with ROR features to raise an alarm when the temperature reaches 11.1°per Minute with inbuilt fault isolator with base with Binary coded address setting. Dual LED’s for 360° visibility. Polarity free, Sleek low-profile housing design. Regular 100mm base as required. (Approved Make: Honeywell-Esser) | 440 | Nos | 100 ₹44,000 | 30 ₹13,200 | 25 ₹11,000 |
| 3.00 | Checking,, Installation, Testing and Commissioning VDS approved of addressable type loop sounder wall mounted type rated at 100 ± 5 DBA @ 1m for Audible annunciation, Fire Sires Sound, Indoor type IP40, ABS plastic as required. (Approved Make: Honeywell-Esser) | 23 | Nos | 100 ₹2,300 | 30 ₹690 | 25 ₹575 |
| 4.00 | Checking, ,Installation, Testing and Commissioning of VDS approved addressable Manual Call Point -Single Action with back box and Break Glass Rod, shall be resettable by Align key to avoid unauthenticated restorations with extra acceesories as required. (Approved Make: Honeywell-Esser) | 23 | Nos | 100 ₹2,300 | 30 ₹690 | 25 ₹575 |
| 5.00 | Supply & Fixing of Manual Call Point Glass. (Approved Make: Honeywell-Esser) | 23 | Nos | 50 ₹1,150 | 22 ₹506 | 15 ₹345 |
| 6.00 | Supply & Fixing of 12 V 7 Ah SMF Battery. (Approved Make : Exide) | 4 | Nos | 1,200 ₹4,800 | 2,675 ₹10,700 | 2,851 ₹11,404 |
| 7.00 | Supply, Installation, Testing and Commissioning of VDS/UL/LPCB approved Addressable Multi Sensor - Smoke cum Heat detector with ROR features to raise an alarm when the temperature reaches 11.1°per Minute with base with Binary coded address setting. Dual LED’s for 360° visibility. Polarity free, Sleek low-profile housing design. Regular 100mm base as required. (Approved Make: Honeywell-Esser/ Honeywell-Notifire/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Bosch/ Edwards/ GST/ Jhonson Control/ Securiton/Notofire) | 60 | Nos | 1,800 ₹1.1 L | 4,200 ₹2.5 L | 3,650 ₹2.2 L |
| 8.00 | Supply ,Installation, Testing and Commissioning of VDS/UL/LPCB approved addressable Manual Call Point -Single Action with back box and Break Glass Rod, shall be resettable by Align key to avoid unauthenticated restorations with extra acceesories as required. (Approved Make: Honeywell-Esser/ Honeywell-Notifire/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Bosch/ Edwards/ GST/ Jhonson Control/ Securiton/Notofire) | 3 | Nos | 3,000 ₹9,000 | 4,600 ₹13,800 | 4,800 ₹14,400 |
| 9.00 | Supply, Installation, Testing and Commissioning VDS/UL/LPCB approved of addressable type loop sounder wall mounted type rated at 100 ± 5 DBA @ 1m for Audible annunciation, Fire Sires Sound, Indoor type IP40, ABS plastic as required. (Approved Make: Honeywell-Esser/ Honeywell-Notifire/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Bosch/ Edwards/ GST/ Jhonson Control/ Securiton/Notofire) | 3 | Nos | 4,000 ₹12,000 | 7,200 ₹21,600 | 6,300 ₹18,900 |
| 10.00 | Supply ,Installation, Testing and Commissioning of Addressable fully networkable fire alarm control Panel VDS/UL/LPCB approved 1 Loop expendable upto 4 Loop capacity with each loop card wich will have 250 devices of both detectors and modules in a single line circuit on any combination, SLC should supports both Class A and Class B wiring. Shall have an LED indication for FIRE, Normal and Redundancy conditions which consists of display board which will have 160 Character Display with Touch key pad, Mother board which will have ARM CORTEX M3 32 Bit Processor, Inbuilt RS-485 Networking Circuit for peer to peer networking, Inbuilt USB 2.0 Port for upload and download the Configuration tools, Two inbuilt programmable inputs, Two inbuilt NAC's, and Three Programmable Relays. power Supply Board, having minimum 1000 event memory, which will have SMPS fully protected board, which its operates on 120 to 220V AC ± 10% with 50/60 Hz, battery backup 24V DC with built-in charger. the panel have IP-50 rating complete as required and as per specification. (Approved Make: Honeywell-Esser/ Honeywell-Notifire/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Bosch/ Edwards/ GST/ Jhonson Control/ Securiton/Notofire) | 1 | sets | 2,00,000 ₹2 L | 2,25,050 ₹2.3 L | 2,15,000 ₹2.1 L |
Tender Value
Refer Docs
EMD Value
₹12,080
Closing Date
28 Jan 2026, 12:30 pmClosed
Executive Engineer, PWD, DDED
Purta Bhawan,4 th Floor,Kachari Road,Balurghat,Dakshin Dinajpur,Pin-733101
Repairing, Testing and Re-Commissioning of existing Fire Detection System at Balurghat DH, Dakshin Dinajpur. RN 25000328. Project ID - HF252633963S000.
2026_WBPWD_983541_1
WBPWD/EE/DDED/e-NIQ- 28 of 2025-26 (3rd Call)
Open Tender
ELECTRICAL WORKS ORG
30 days
Balurghat, Dakshin Dinajpur
Please refer Tender documents.
5 documents required · 5 mandatory
₹12,080
12 Mar 2026
5 Jan 2026
30 Jan 2026
5 Jan 2026
28 Jan 2026
5 Jan 2026
Checking, Rectification, Re-Installation, Testing and Re-Commissioning of Addressable fully networkable fire alarm control Panel EN Standred VDS approved 4 Loops Expendabele upto 18 loop, loop card wich will have 127 devices of both detectors and modules in a single line circuit on any combination. (Approved Make: Honeywell-Esser)
Checking, Re-Installation, Testing and Commissioning of VDS approved Addressable Multi Sensor - Smoke cum Heat detector with ROR features to raise an alarm when the temperature reaches 11.1°per Minute with inbuilt fault isolator with base with Binary coded address setting. Dual LED’s for 360° visibility. Polarity free, Sleek low-profile housing design. Regular 100mm base as required. (Approved Make: Honeywell-Esser)
Checking,, Installation, Testing and Commissioning VDS approved of addressable type loop sounder wall mounted type rated at 100 ± 5 DBA @ 1m for Audible annunciation, Fire Sires Sound, Indoor type IP40, ABS plastic as required. (Approved Make: Honeywell-Esser)
Checking, ,Installation, Testing and Commissioning of VDS approved addressable Manual Call Point -Single Action with back box and Break Glass Rod, shall be resettable by Align key to avoid unauthenticated restorations with extra acceesories as required. (Approved Make: Honeywell-Esser)
Supply & Fixing of Manual Call Point Glass. (Approved Make: Honeywell-Esser)
Supply & Fixing of 12 V 7 Ah SMF Battery. (Approved Make : Exide)
Supply, Installation, Testing and Commissioning of VDS/UL/LPCB approved Addressable Multi Sensor - Smoke cum Heat detector with ROR features to raise an alarm when the temperature reaches 11.1°per Minute with base with Binary coded address setting. Dual LED’s for 360° visibility. Polarity free, Sleek low-profile housing design. Regular 100mm base as required. (Approved Make: Honeywell-Esser/ Honeywell-Notifire/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Bosch/ Edwards/ GST/ Jhonson Control/ Securiton/Notofire)
Supply ,Installation, Testing and Commissioning of VDS/UL/LPCB approved addressable Manual Call Point -Single Action with back box and Break Glass Rod, shall be resettable by Align key to avoid unauthenticated restorations with extra acceesories as required. (Approved Make: Honeywell-Esser/ Honeywell-Notifire/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Bosch/ Edwards/ GST/ Jhonson Control/ Securiton/Notofire)
Supply, Installation, Testing and Commissioning VDS/UL/LPCB approved of addressable type loop sounder wall mounted type rated at 100 ± 5 DBA @ 1m for Audible annunciation, Fire Sires Sound, Indoor type IP40, ABS plastic as required. (Approved Make: Honeywell-Esser/ Honeywell-Notifire/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Bosch/ Edwards/ GST/ Jhonson Control/ Securiton/Notofire)
Supply ,Installation, Testing and Commissioning of Addressable fully networkable fire alarm control Panel VDS/UL/LPCB approved 1 Loop expendable upto 4 Loop capacity with each loop card wich will have 250 devices of both detectors and modules in a single line circuit on any combination, SLC should supports both Class A and Class B wiring. Shall have an LED indication for FIRE, Normal and Redundancy conditions which consists of display board which will have 160 Character Display with Touch key pad, Mother board which will have ARM CORTEX M3 32 Bit Processor, Inbuilt RS-485 Networking Circuit for peer to peer networking, Inbuilt USB 2.0 Port for upload and download the Configuration tools, Two inbuilt programmable inputs, Two inbuilt NAC's, and Three Programmable Relays. power Supply Board, having minimum 1000 event memory, which will have SMPS fully protected board, which its operates on 120 to 220V AC ± 10% with 50/60 Hz, battery backup 24V DC with built-in charger. the panel have IP-50 rating complete as required and as per specification. (Approved Make: Honeywell-Esser/ Honeywell-Notifire/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Bosch/ Edwards/ GST/ Jhonson Control/ Securiton/Notofire)
NOTE :- 1) The Fire Alarm system shall comply with latest requirements of -- (i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 , (iii) NFPA 70 National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code , (v) Local Statutory Regulations , (vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand.
TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done.
TERMS & CONDITIONS :-
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/Gloster/ RR Kable/Polycab/KEI ) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall.
N.B- The Rate to be quoted by all the bidders should be inclusive of all taxes, duties including GST & CESS etc.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.87 MB
Tendernotice_2.pdf
PDF • 5.39 MB
Tendernotice_3.pdf
PDF • 0.44 MB
BOQ_2399890.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid