| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 953 16TH CROSS 1ST PHASE 1ST STAGE CHANDRA LAYOUT BANGALORE KARNATAKA 560072 | BENGALURU URBAN | KARNATAKA | 560072 | Admitted-Finance |
| 2 | Not Admitted-Fee/PreQual/Technical A 42 JAI AMBEY NAGAR TONK ROAD JAIPUR RAJASTHAN 302018 | JAIPUR | RAJASTHAN | 302018 | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹22.0 L
EMD Value
₹44,042
Closing Date
3 Jun 2023, 6:00 pmClosed
EE(E),BCD,EKM
4th fllor,CTO bd,Karkkatt rd,EKM
Supply Installation Testing Commissioning of UPS system 2 Nos 40 KVA for RMC DC Data Centre at TE Panampilly Nagar Replacement Recall
2023_BSNL_154046_1
10/EE-BSNL/CD/EKM/2023-24
Open Tender
Electrical Works
Item Rate
60 days
Panampilly Nagar
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹44,042
Yes
15 Jul 2023
12 May 2023
5 Jun 2023
12 May 2023
3 Jun 2023
12 May 2023
Amount
Supply Item
Supply of 2 Nos. 40 KVA UPS's 3Ph-3Ph in (1+1) configuration for providing power supply to servers with in-built/ separate mounted isolation transformer, battery charger facility, having 415V, 3-phase pure sine wave output & having features of automatic parallel redundant configuration system between UPS's along with all electrical and programmable arrangement i/c paralleling kit and signal interconnecting cable for parallel redundancy along with suitable size SMF battery bank with stand/housing for minimum 1 hour battery backup of rated capacity seperately for both UPS, necessary copper cabling work including 24 Months comprehensive warranty for UPS and Batteries at site from the Date of commissioning etc complete as reqd. (as per specifications attached) Makes DELTA, Emerson, APC, Legrand
40 kVA UPS
12V 150AH SMF Battery (Min 72000 VAH x 2 sets )
(Buy Back) Cost of Old 2x40KVA UPS and battery bank (Deduction)
Installation, Testing & Commissioning of 40 KVA UPS's 3Ph-3Ph in (1+1) configuration for providing power supply to servers with in-built battery charger facility, having 415V, 3-phase pure sine wave output & having features of automatic parallel redundant configuration system between UPS's along with all electrical and programmable arrangement i/c paralleling kit and signal interconnecting cable for parallel redundancy along with suitable size SMF battery bank with stand/housing for minimum 1 hour battery backup of rated capacity with suitable stand/housing, necessary copper cabling work ,including 24 Months warranty complete as required. (as per specifications attached)
AMC for 3rd,4th & 5th year
Annual comprehensive Maintenance of 2 no.s of 40 KVA UPS's 3Ph-3Ph in (1+1) configuration along with its battery bank i/c periodical servicing, attending break downs, replacement of defective parts with new one(excluding the replacement of batteries) after the 24 months warranty period etc complete as required.
3'rd year (After completing the 24 months warranty) (replacement of battery not included in the scope of CMC )
4th year (replacement of battery not included in the scope of CMC )
5th year(replacement of battery not included in the scope of CMC )
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .