Loading…
Loading…
Tender Value
₹3.4 L
EMD Value
₹2,300
Closing Date
24 Jul 2026, 12:00 pmClosed
Deputy Executive Engineer, Electrical (R&B) Sub-Division, Vyara
Repairs to Street Light of Court Building at Vyara,Di-Tapi
324623
02 of 2026-27
Open
Electrical Works
Works
Tapi
₹600
Executive Engineer, Electrical R and B Division surat
₹2,300
16 Jul 2026
16 Jul 2026
16 Jul 2026
24 Jul 2026
16 Jul 2026
Name of work :- Repairs to Street Light of Court Building at Vyara,Di-Tapi
Memorandum showing items of work to be carried out
Item Quantities Item of work Estimated Rates Unit Total
No. estimated but Amount
may be more according to
or less In words estimated
1 35 Mtr. Replacing old & u/s by Supplying and erecting 58.58 Rupees Fifty Mtr.
Flexible PVC insulated multi strand multi core Eight And
1.1 kv grade ISI marked copper wires of Paise Fifty
following size to be erected as directed. (e) Eight Only
1.50 Sq.mm 3 core round PVC sheathed
2 12 Nos. Replacing old & u/s by Supplying and erecting 7186.15 Rupees Seven Ea.
LED street light / Flood light fittings with High Thousand One
power White LEDs wattage of 3 Watt and Hundred
above assembled on single MCPCB, efficiency Eighty Six And
more than 130 lm/w and corrosion free High Paise Fifteen
pressure die cast aluminum housing with Only
smooth finish powder coated and heat sink
extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with toughened
glass with company mark/name engraved or
embossed 160 to 270 V,Power Factor more
than 0.95, THD < 10 %, CCT 3000 K to
5700K,Uniformity ratio >0.45, Luminaire
efficacy> 100 lumens/watt . LED driver
efficiency > 85 %.( fittings required LM-79 &
LM-80 certificates)(NOTE: Below description
have shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any
wattage capacity between the ranges
shown.)(A) Street Light (IP-65), Surge
protection -4KV integral and ,Light must have
440VAC line supply with over-voltage
protection. (ii) above 48 to 60 Watts CatIII (B)
Flood Light (IP-65), Surge protection -4kV
integral and ,Light must have 440VAC line
supply with over-voltage protection. (v) 120 -
159 wattsCat-lll
3 276 Mtr. Replacing old & u/s by Providing and erecting 151.50 Rupees One Mtr.
XLPE (IS:7098)(I)-88 ISI armoured cable Hundred Fifty
multistrand / Solid Aluminium conductor for 1.1 One And Paise
KV. to be laid on wall with necessary clamps or Fifty Only
in existing trench / pipe of following size of
cables (B) 4 core 6 Sq. mm
4 260 Mtr. Supplying & erecting approved make SMC 476.72 Rupees Four Mtr.
press moulded composite FRP. loop-in, loop- Hundred
out approx. 2mm thick box complete with Seventy Six
Bakelite connector strip 5way(3P+N+E),DIN rail And Paise
for mounting mob & hinged doors as per Seventy Two
requirement having locking arrangements with Only
mounting clamp with nuts, bolts & washers
suitable for erection on pole with cable clamps&
earth bolt of following size of box.(C)150mm x
125mm x 100mm [deep]
5 260 Mtr Providing & laying approved make Double 62.62 Rupees Sixty Mtr.
walled corrugated pipes (DWC) of Two And Paise
polyethylene(conforming to IS 14930 II )with Sixty Two
necessary connecting accessories of same Only
material at required depth in existing trench for
laying of cable. below ground / road surface
for enclosing cable (A)50 mm outer dia[4-5-8]
6 2 Nos. Supplying & erecting approved make IP 55 13350.18 Rupees Ea.
grade Company fabricated Timer Panel of Thirteen
following capacity for switch On-Off street Thousand
lights on time scheduling basis made from 16G Three Hundred
CRCA sheet duly epoxy power painted inside Fifty And
and outside with hinged doors and locking Paise Eighteen
arrangement consisting of suitable size of 4 Only
Pole MCB and 4 pole contactor (cat-III)with
analog time switch, auto manual switch of
same make and suitable input and output
Bakelite terminals and with door earthing
approved by Engineer in charge.(B) 40 Amp[6-
7 50 Mtr Providing and erecting FRLS-XLPE (IS:7098)(I)- 184.83 Rupees One Mtr.
88 ISI armoured cable multistrand Aluminium Hundred
conductor for 1.1 kV. to be laid on wall with Eighty Four
necessary clamps or in existing trench / pipe of And Paise
following size of cables(A) 4 core 16 Sq. mm[4- Eighty Three
8 2 Nos. Providing and erecting Approved make Four 7469.25 Rupees Seven Ea.
pole moulded case circuit breaker having Thousand Four
breaking capacity ICU of 25 KA. at 415 Hundred Sixty
V,having normal current rating up to 25 A to Nine And
100A. with Fixed thermal & magnetic release Paise Twenty
suitable to work on A.C. supply 50 Hz. with all Five Only
internal connections, spreader tinned copper &
complete erected in new 16 G.M.S.
housingICS=100% of ICU only Cat III[3-4-
9 2 Nos. Providing & erecting 415 V MCB Four Pole for 736.29 Rupees Seven Ea.
Motor & Inductive Load (C Curve) having 10KA Hundred
breaking capacity & confirms to IS :8828 in Thirty Six And
existing box having following capacity (b)40 Paise Twenty
Amp. Cat.III [3-10-5] Nine Only
10 1 Nos. Supplying & erecting earth pit of minimum bore 4591.46 Rupees Four Ea.
dia.150mm size approved make Earthing Thousand Five
Electrode consisting Pipe-in-Pipe Technology Hundred
as per IS 3043-1987 made of corrosion free hot Ninety One
dipped G.I.Pipes having Outer pipe dia of And Paise
50mm having 80-200 Micron galvanising, Inner Forty Six Only
pipe dia of 25 mm having 200-250 Micron
galvanising, connection terminal dia of 12mm
with constant ohmic value surrounded by highly
conductive compound with high charge
dissipation suitable for following type of
applications with chamber and heavy duty
cover. (A)(approved make OEM has to submit
test certificate including value of earth
resistance of installation duly stamped and
signed by agency and officer Incharge has to
ensure the value of earthing resistane
mentioned in test Certificate) & having back
filling compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 ohm / meter
testing as per IEC 62561-2017, Voltage drop:-
< 1 volt at no load & dry form, Sulphar content:-
<2%(C) Back fill Compound :- Earthing
compound should be capable to retain moisture
for long time Necessary test report must be
submitted by Agency. (a) For Electrical
Installation up to 440V in normal soil
Length of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg.[3-
11 10 Kg Providing and erecting Annealed bare Copper 794.87 Rupees Seven Ea.
wire 4.064mm to 1.626mm.[3-14-4] Hundred
12 12 Nos. providing and erecting Miniature circuit breaker 297.95 Rupees Two Ea.
single pole 0.5A to 2A system and having Hundred
breaking capacity 10 KA to be erected in Ninety Seven
existing box. confirming to IS 8828/1996 with And Paise
ISI Mark Cat.III[3-10-1.(A)] Ninety Five
Rupees Three Lakh(s) Thirty Eight Thousand Seven Hundred Ninety Five And Paise One Only
I/We am /are willing to carry out the work at…………% above/below percent (should be written in figures and words) at
the estimated rates mentioned above amount of my/your tender works out as under.
the estimated rates mentioned above amount of my/your tender works out as under.
*Estimated Amount *Estimated Amount
put to Tender Rs. 338795.01 put to Tender Rs.
Deduction …………….. % below………………… Add ………… % above Rs. …………….
Less Dismental 5407.70 Less Dismental
Note 1:- An amount of Rs.5407.70 (Rs.Five Thousand Four Hundred Seven & seventy Paise Only) towards
estimated credit value of dismantled materials shall be recovered from the 1st R.A. Bill of this work.
Note 2:- All work shall be carried out as per public work department hand book and other specifications of Division
Note 3:- Rates quoted include clearance of site (Prior commencement of work and its close) in all respects and hold
good for work under all condition, site, moisture/ weather etc
Note 4:- The Contractor shall exhibit a board as per Government Circular No. BDG/ 3277/ 1657/ N Dated 26/1/1997
S (M.GUJ) with detailed specification and details of work and amount involved at site without any payment
as directed by the Engineer-in-charge.
Signature of Bidder Deputy Executive Engineer
Electrival (R&B) Sub-Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
dismental condition1.pdf
FINAL _ SBD (Electrical Work) bOOK LATE.pdf
List of Dismental.pdf
NIVIDA-02 OF 2026-27.pdf
schedule-B.pdf
origional sch-b.pdf
CORRIGENDUM
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .