Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 LAccepted-Finance | L1 | Accepted-Finance L1 | |
| 2 | L2₹8.9 L+₹1.7 L (23.2%)Accepted-Finance | L2 | Accepted-Finance L2 | |
| 3 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹8.5 L
EMD Value
₹9,000
Closing Date
20 Feb 2023, 12:00 pmClosed
SE, EDC, Rampur
Office of the SE, EDC, Rampur
47/2022-23/EDCR Increasing load capacity of overloaded Transformer, replacement of VCB, Jarjar wire and construction of line under Scheme Nagar Nikay, EDD-Milak, Rampur(Semi Trunkey Basis).
2023_PVVNL_769354_2
47/2022-23(EDCR)
Open Tender
Electrical Work/ Equipment
Lump-sum
45 days
Office of the SE, EDC
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,180
SE, EDC, Rampur
₹9,000
28 Feb 2023
3 Feb 2023
20 Feb 2023
3 Feb 2023
20 Feb 2023
3 Feb 2023
Amount
Carriage of the following material from Store Centre, Rampur to work site including loading & unloading.
11 KV VCB O/G Feeder CTR 200/100/5A
LT PVC Cable 3.5*70 SQ MM
AB Cable(3*120+1*95+1*16) MM SQ
ACSR Weasal Conductor
ACSR Rabbit ConductorConductor
Old Scrap VCB(From Site to Store)
Old Scrap wire (From Site to Store)
Cartage of Healty Transformer from store to site, dismantling of HT & LT connection & replace of follwoing capacity T/F from substation double poles (including connection) and loading and unloading with associated work at both ends within 70 kms.
Increasing load capacity of overloaded TF by Separate 63 KVA trasnformer
a) Single support Excavation of foundation Pit in size of 75x45cm having depth of 1/6th of the full length of the support(pole), providing and laying of stone pad (300x300x75 mm) in the Bottom of the pit. Erection of support(pole) complete with fixing of 11 KV V-type cross-Arms and other accessories by providing clamps made of MS flat of size 65x65xc6 mm with Nuts & Bolts, as per RESPO Norms.
11 Mtr Long ST Pole.
8.5 Mtr PCC Pole Long
Grouting of support in CC 1:4:8(cement, sand & 40 mm. brick ballast) Grouting will be done in the block of size 45x45cmx1/6th of full length of the support upto ground level, 30 cm plinth above the ground level with CC 1:3:6 (cement, course sand and stone grit) with muffing. The work includes back filling and proper ramming etc. a) Single support
11 Mtr Long ST Pole.
8.5 Mtr PCC Pole Long
Grouting of Stay Rods(20x1800)mm including all work of excavation, cement concrete in size of (0.60x0.60x0.30)M in the ratio of 1:4:8(cement, sand, 40mm brick ballast) including back filling of soil and proper ramming etc.
Fixing, tightening and nozelling of stay wire with stay rod with the pole of required tension by providing stay clamps.
Earthing of support with MS Earth Rod of (20x2500)mm long including excavation of pit and driving MS Rod 3.0 M apart from support and 0.5 M below the ground level and connecting below the earth electrodes with the help of GI wire No. 8SWG and earthing lugs
Providing & fixing of 11 KV Pin Insulator with Pin
Providing & fixing of 11 KV Disc Insulator
Laying ,stringing and binding of AB Cable(3*120+1*95+1*16) MM SQ as per RESPO Norms and as per direction of Supervising Engineer.
Laying ,stringing and binding of LT PVC Cable 3.5*70 SQ MM as per RESPO Norms and as per direction of Supervising Engineer.
Laying ,stringing and binding of ACSR Weasal Conductor as per RESPO Norms and as per direction of Supervising Engineer.
Dismentaling old line and Laying ,stringing and binding of ACSR Rabbit Conductor as per RESPO Norms and as per direction of Supervising Engineer.
Dismentaling of old VCB and Installing new 11 KV VCB O/G Feeder CTR 200/100/5A with fitting by providing of bolt and nuts as per RESPO Norms and as per direction of Supervising Engineer.
Installing Distribution Box three phase with fitting by providing of bolt and nuts as per RESPO Norms and as per direction of Supervising Engineer.
Gaurding of 11 KV HT Line as per RESPO Norms and as per direction of Supervising Engineer.
Providing and fixing Danger Board with Clamps
Providing and fixing J Hook
Providing and fixing Piareing Clamp
Providing and fixing Suspention Clamp
Providing and fixing Dead end clamp
Providing and fixing Stone Pad
Providing and fixing barbed wire
Providing and fixing F Bracket with nut bolt
Providing PCC Pole 8.5 Mtr. Long.
Providing ST Pole 11 Mtr. Long.
Providing X-Arms.
Providing Distribution Box
Providing Droper Channel 100x50
Providing Top Channel 125x65
Providing MS Angle 75x75
Providing Guarding Angle
Providing GI Wire
Providing Stay Complete
Providing Earthing Complete
Providing and fixing Clamp with Nuts & bolts for Holding X-Arm
Providing and fixing Nut Bolt with clamp
S A TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .