DSITC 11 KV 3 Phase 630A Motorised SF6
9645082
GEM/2026/B/7820537
Two Packet Bid
Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insula
Medchal Malkajgiri, Telangana
Total value wise evaluation
BOQ
7 documents required · 7 mandatory
3 yrs
₹32 L
80%
Prasar Bharati Corporation Addl Director General, OFFICE OF THE ADDITIONAL DIRECTOR GENERAL ENGG SZ SWAMY SIVANANDA SALAI CHENNAI 600005, (Prasar Bharati Corporation Addl Director General)
₹1.3 L
24 Aug 2026
29 Jul 2026
24 Aug 2026
| Item No | Item Title | Description | Qty | Unit | Consignee | Delivery (days) |
|---|---|---|---|---|---|---|
| 1 | Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU | Supply of 11kV 3 phase, 630Amps, Motorized SCADA compatible Monitoring and Controlling , SF6 Insulated Outdoor, totally enclosed, 5Way Ring Main Unit RMU Consisting of Incoming LBS 2 Nos and Outgoing CB 3 Nos. with voltage and current Metering on all incoming or Outgoing feeders including all the protective devices confirming to standard IS3427 1997 amended to date as detailed below and conforming to TGSPDCTL ,Hyderabad requirements. RMU design and CT PT ratio should be suitable for 320kVA Maximum Demand. | 1 | Set | DDE_DDKHYD | 30 |
| 2 | Insurance, transportation and unloading of RMU at site | Insurance, transportation and unloading of RMU at site | 1 | Job | DDE_DDKHYD | 30 |
| 3 | Design, fabrication and construction of RCC foundation or plinth for 5Way RMU panels | Design, fabrication and construction of RCC foundation / plinth for 5Way RMU panels including anchor bolts, cable trench interface panel to panel and civil works as recommended by OEM and as per TGSPDCL Hyderabad norms. | 1 | Job | DDE_DDKHYD | 30 |
| 4 | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 11kV Feeder structure to RMU panel | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 11kV Feeder structure to Outdoor type RMU incomer panel. Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCL ,Hyderabad norms. Payment shall be as per actuals | 20 | Mtr | DDE_DDKHYD | 30 |
| 5 | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from Outdoor type RMU to 4 panel HT Switchgear | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from Outdoor type RMU to 4 Panel HT Switchgear Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCL ,Hyderabad norms. Payment shall be as per actuals | 40 | Mtr | DDE_DDKHYD | 30 |
| 6 | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 4 panel HT Switchgear to 500 kVA Transformers 2 Nos. | Laying of 11kV, 3 core, 120 Sqmm XLPE, Aluminium Armoured HT cable from 4 Panel HT Switchgear to 500 kVA Transformers 2 Nos. Work includes excavation of cable trench, laying of HT Cable, filling with sand cushioning, bricks and closing with protective covers trench, providing cable markers and back filling as per TGSPDCLTL ,Hyderabad norms. Payment shall be as per actuals. | 20 | Mtr | DDE_DDKHYD | 30 |
| 7 | Supply and fixing of outdoor heat shrinkable end standard make termination kits for 11 kV, 120Sq mm XLPE HT Cable for RMU | Supply and fixing of outdoor heat shrinkable / end standard make termination kits for 11 kV, 120Sq mm XLPE HT Cable for RMU | 10 | Nos | DDE_DDKHYD | 30 |
| 8 | Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV, 120Sq mm XLPE HT Cable for HT Switchgear Panel and 500KVA Indoor Transformers 2 Nos. | Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV, 120Sq mm XLPE HT Cable for HT Switchgear Panel and 500KVA Indoor Transformers 2 Nos | 8 | Nos | DDE_DDKHYD | 30 |
| 9 | Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV 120Sq mm XLPE HT Cable 500KVA Indoor Transformers 2 Nos | Supply and fixing of indoor heat shrinkable or end standard make Cable termination kits for 11 kV 120Sq mm XLPE HT Cable 500KVA Indoor Transformers 2 Nos | 2 | Nos | DDE_DDKHYD | 30 |
| 10 | Supply and Providing conventional type Copper plate earthing system for RMU | Supply and Providing conventional type Copper plate earthing system for RMU including termination, interconnections, test links and all accessories as per the drawing enclosed in Annexure C Diagram 2 for completion of the earthing.Copper Strips 50 x 3 mm As per Actuals, Copper Plate, GI Pipe,and any other required materials to complete the Earthing system should be supplied by the tenderer. Copper Purity Certificate for 99.95 Percentage to be submitted for the copper materials supplied for Earthing system. | 2 | Sets | DDE_DDKHYD | 30 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
bid_9645082.pdf
GEM_BID • 0.22 MB
revised_specification_for_rmu_gddrc_hyderabad_for_e_2026-07-22-11-21-54_7916a3e76735bf88858d7c2db619233b.pdf
BOQ • 0.98 MB
boq__21_7_26_2026-07-22-11-21-54_f967275788c88892c03e3825da8a70c8.csv
BOQ • 0.01 MB
1784711932.xlsx
GEM_OTHER • 0.31 MB
gtc.pdf
GEM_OTHER • 0.71 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].