Improvement of Emergency Lighting System as a Backup Power Supply with the Provision of Inverter System at Manned Level Crossing Gates in the Jurisdiction of DEE/G&CHG./KIR.
31_2026
31_2026
Open
6 Months
Unknown (Unspecified Location)
₹0
₹3.4 L
13 Jun 2026
13 Jun 2026
25 Jun 2026
Provision of Inverter System at Manned Level Crossing Gates in the Jurisdiction of DEE/G&CHG./KIR.
Item- 1 Please see item breakup for details.
S No. Item Description of Item Unit Qty Rate Amount
1 1 Supply, wiring, testing & commissioning of point Numbers 350.00 425.00 148750.00
complete with 6 amps flush type individual
controlling switch fitted on half flush MS board
with hylem sheet top and wiring by FR PVC
insulated and unsheathed 1.5 sq mm, single
core multi strand copper wire 1.1 kV grade and
earth continuity wire by FR PVC insulated and
unsheathed 1 sq mm , single core copper wire
drawn through double lock PVC casing caping of
not less than 19 mm width & minimum thickness
of 0.85 mm as per instruction of Engineer
Incharge at site. (a) FL Point/LED Tube Point with
KATIHAR DIVISION-ELECTRICAL/N F RLY
2 2 Supply, wiring, testing & commissioning of 2 x 6 Numbers 210.00 137.00 28770.00
amp. plug point on separate board complete
with 2 nos. 6 amps switch with 2 nos. 6 amps 5
pin socket fitted on half flash MS board with
hylem sheet top as per instruction of Engineer
Incharge at Site.
3 3 Supply, wiring, testing & commissioning of Numbers 280.00 200.00 56000.00
Power plug point on separate half flush MS
board with hylem sheet top complete with 16 A
flush type controlling switch & 6/16 amps socket
as per instruction of Engineer incharge at site.
4 4 Supply, fixing, connection & testing of indoor Numbers 250.00 987.00 246750.00
LED tube batten with 20 watt LED T8 tubular
lamp with extuded aluminium body and PC
diffuser complete with inbuilt driver (System
wattage-20 Watt, System efficacy> 120 lm/W,
Power factor 0.90) with suitable fixing
arrangement as per instruction of Engineer
incharge at site.
5 5 Supply & wiring by 2.5 sq mm, Single Core FR- Metre 2800.00 47.00 131600.00
LSH PVC Insulated Industrial Grade Copper
Conductor (Unsheathed) Flexible Cables, 1100
Volts Conforming to IS: 694 to be drawn through
double locked PVC casing capping of not less
than 19 mm wide & 0.85 mm thick along with 1
sq mm single core FR PVC insulated and
unsheathed copper wire for earth continuity as
per instruction of Engineer Incharge at Site.
6 6 Supply & wiring by 4 sq mm, Single Core FR-LSH Metre 2100.00 63.00 132300.00
PVC Insulated Industrial Grade Copper
Conductor (Unsheathed) Flexible Cables, 1100
Volts Conforming to IS: 694 to be drawn through
double locked PVC casing capping of not less
than 19 mm wide & 0.85 mm thick along with 1
sq mm single core FR PVC insulated and
unsheathed copper wire for earth continuity as
per instruction of Engineer Incharge at Site.
7 7 Supply & testing of GI octagonal pole 6 mt long Numbers 90.00 14193.00 1277370.00
with foundation bolt, loop box of bakelite sheet
with one 6A SP MCB and 16 sq mm stud type
connector etc. The octagonal pole shall be hot
dip galvanized in single dip. Technical
specification of pole as following:- Height - 6 mt
Top dia (A/F) - 70 mm Bottom dia (A/F) - 130 mm
Sheet thickness - 3 mm Base plate (L x B x T) -
(200 x 200 x 12) mm Foundation Bolt size (no.x
dia) - 4 x 20 dia mm Pitch Circle Dia (PCD) - 200
mm Bolt length - 600 mm Projected Bolt Length -
8 8 Supply & fixing of 1 mtr GI Single arm bracket Numbers 90.00 1615.00 145350.00
(header) and holder with Nut & bolt as per
instruction of Engineer incharge at site.
9 9 Erection of Rail/Tubular/Octagonal pole to 1/5 th Numbers 90.00 1712.00 154080.00
of its height with CC foundation from base block
(30 cm x 30 cm x 15 cm) including digging &
refilling of earth to a height of 30 cm above
ground level as per drawing
no.CEE/OH@47'40@FGA) in ratio 1:3:6 by
cement sand & Chips 19 mm & down including
excavation of earth.
10 10 Supply, installation, testing & commissioning of Numbers 300.00 3872.00 1161600.00
45 watt LED street light luminaire with heat
resistant glass with connecting lead (IP
protection- IP 66 class-I, System efficacy 120
lm/w, Housing- Pressure die cast aluminium
powder coated, THD<10%, p.f.>0.95, Surge
protection- 5 kV) as per instruction of Engineer
incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
11 11 Supply, installation, testing & commissioning of Set 130.00 54282.00 7056660.00
Standalone 30 W Solar Street Light alongwith
100 Wp Poly Crystalline Solar Panel, 12V 75 Ah
Lead Acid Battery, 6 M Tubular Pole, Mounting
Structure, Battery Box, and LED Street Light
Bracket (For outdoor Street light) as per
instruction of Engineer Incharge at Site.
12 12 Supply, installation, testing & commissioning of Set 90.00 37439.00 3369510.00
Sine wave Inverter 1400 VA or 1450 VA suitable
for operation on 230 volt AC, with supply of 02
nos. 12 volt @ 150 Ah SMF battery including
inverter battery trolley as per instruction of
Engineer incharge at site.
13 13 Horizontal machine boring of 300 mm dia hole Metre 200.00 2538.00 507600.00
across track/Road/High drain etc. at a depth of
1.0 mtr below of ground level with suitable
boring instruments & neessary arrangement and
as per technical procedure.
14 14 Supply, laying, commissioning & testing of CI Metre 200.00 1388.00 277600.00
Pipe 150 mm dia Class LA type (IS 1536-2001) to
be laid partly along the pole and partly through
ground under railway track/road in cable trench
for protection of cable with suitable fixing
arrangement by MS clamp, nut, bolt, washer
etc. as per instruction of Engineer incharge at
15 15 Supply, laying, commissioning & testing of HDPE Metre 200.00 70.00 14000.00
pipe 50 mm dia, PN-6 grade to be laid partly
along the p o l e / w a l l with suitable fixing
arrangement by MS clamp made of MS flat of
size 50x6 mm and suitable size nut , bolt,
washer etc as per instruction of Engineer
Incharge at site.
16 16 Supply, erection, testing & commissioning of CLS Numbers 13.00 31473.00 409149.00
PANNEL 30A, Automatic Changeover Control
Panel for Colour Light Signaling system of 5 KVA
30A capacity as per CORE approved RDSO
specification No. TI / SPC / PSI / CLS / 0023 with
A&C slip. as per instruction of Engineer Incharge
17 17 Supply, erection, testing & commissioning of CLS Numbers 8.00 69511.00 556088.00
PANNEL 60 A, Automatic Changeover Control
Panel for Colour Light Signaling system of 10
KVA 60 A capacity as per CORE approved RDSO
specification No. TI / SPC / PSI / CLS / 0023 with
A&C slip. as per instruction of Engineer Incharge
18 18 Supply, installation, testing & commissioning of Numbers 140.00 1292.00 180880.00
poly carbonate/Thermoplastic cable cable
junction box of size (155 x 210 x 92) mm with IP
67 grade protection with metric knock out with
terminals as per instruction of Engineer incharge
19 19 Supply, installation, testing & commissioning of Numbers 70.00 1331.00 93170.00
poly carbonate/SMC/Thermoplastic cable
junction box / loop box of size (200 x 160 x 98)
mm with IP 65 grade protection with metric
knock out with 04 nos terminals as per
instruction of Engineer incharge at site.
20 20 Supply & Erection of earth by 50 mm dia 3 Mtrs. Numbers 70.00 4349.00 304430.00
long (3.6 mm thickness) GI pipe, 32x6 mm GI
strip- 5 Mtrs, GI nuts, bolts including masonry
materials for earthing pit, salt, charcoal,
soldered end terminal etc. and construction of
earth pit covered with RCC cover slab12.7 mm
thickness and watering pipe as per Drg. No.-
PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as
per instruction of Engineer Incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
21 21 Supply, erection & commissioning of earth spike Numbers 75.00 366.00 27450.00
made of 16 mm dia 1.8 mt long GI rod &
connection metal body with the earth spike rod
by 6 SWG GI earth wire with nut, bolt & washer
22 22 Supply, fixing, testing & commissioning of MCB Set 70.00 1099.00 76930.00
DP 16-32 amps, 2 module, 10 kA, Conforms to
IS/IEC 60898 - 1:2002 with MCB enclosure 2 way
made of CRCA sheet powder coated as per
instruction of Engineer Incharge at site.
23 23 (a) Supply, installation, testing & commissioning Numbers 70.00 1450.00 101500.00
of MCB Two Way Centre Off Changeover Switch,
40 Amp. as per instruction of Engineer Incharge
24 24 (b) Supply & fixing of MCB enclosure 2 way, 2 Numbers 70.00 500.00 35000.00
module, made of CRCA sheet steel powder
coated, IP30, metal door alongwith supply &
fixing of following MCB as per instruction of
Engineer incharge at site.
25 25 (a) Supply, installation, testing & commissioning Numbers 30.00 1490.00 44700.00
of 4 way SPN distribution board, Flush/Surface
mounting, IP 43 grade protection with copper
bus bar, fully shrouded neutral bar, earth bar,
cable ties, Prefitted masking sheet, Reversible
metal door as per IEC 61439-3 with supply and
fixing of following MCB as per instruction of
Engineer Incharge at Site.
Conforms to IS/IEC 60898 - 1:2002
Conforms to IS/IEC 60898 - 1:2002
28 28 Laying, commissioning & testing of HT/LT Metre 2000.00 55.00 110000.00
XLPE/PVC cable of different sizes partly along
the pole and partly through ground in cable
trench by excavation of ground below 1.5 mt
from ground level with suitable fixing
arrangement by MS clamp of size 50x6 mm and
suitable size nut, bolt. Loading, Unloading &
Carrying of cable to actual work site by
contractor's own arrangement. (Aluminium
Crimping Socket should be provided for each
Cable Termination). (Cable will be supplied by
29 29 Excavation of cable trench (0.3 x 1.5) mtr below Metre 1520.00 148.00 224960.00
ground level for laying of cable & refilling the
soil after digging the earth as per instruction of
Engineer incharge at site. Cable should be laid
on bedding of height 75 mm sand at the bottom
of trench, and covering it with additional sand of
height 75 mm and thereafter protecing it by
mean of bricks before refilling the soil as per IS
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCCApril-2022PDFwithallACS_compressed.pdf
ATTACHMENT
NITEmergencyLightingSystemJurisdictionofDEEGCHGKIR.pdf Tender Paper
ATTACHMENT
NITEmergencyLightingSystemJurisdictionofDEEGCHGKIR.pdf
ATTACHMENT
Download all tender documents and submit your bid