| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.5 LAccepted-AOC | L1 | Accepted-AOC Lowest Rates | |
| 2 | L2₹51.5 L+₹10.0 L (24.1%)Rejected-Finance | L2 | Rejected-Finance Second Lowest | |
| 3 | L3₹51.9 L+₹10.5 L (25.3%)Rejected-Finance 108 3 CHANDAR NAGAR DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | L3 | Rejected-Finance Third Lowest | |
| 4 | L4₹52.8 L+₹11.3 L (27.2%)Rejected-Finance JHAWAREDI POST KARBARI IDBI BANK COMPLEX SHIMLA ROAD DEHRADUN | L4 | Rejected-Finance Fourth Lowest | |
| 5 | L5₹54.7 L+₹13.3 L (32.0%)Rejected-Finance 1 50 MANGALAM RIICO INDUSTRIAL AREA KANAKPURA JAIPUR RAJASTHAN | JAIPUR | RAJASTHAN | L5 | Rejected-Finance Fifth Lowest |
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
10 Jul 2023, 5:00 pmClosed
Superintending Engineer
Office of The Superintending Engineer, 11th E/M Circle, P.W.D., 107-Nehru Colony (Phase-II), Dharampur, Dehradun
S.I.T.C. of 400 KVA Compact Sub-Station (CSS) at Passenger Terminal Building under R.C.S. UDAAN-2 at Sahastradhara Road, Dehradun.
2023_pwd_60096_1
1930/7CB(I)-11/2023-24 Dated 08.06.2023
Open Tender
Electrical Works
Item Rate
120 days
Sahastradhara Heliport
Please refer Tender Documents
2 documents required · 2 mandatory
₹4,720
Executive Engineer, E/M Division, PWD, Dehradun
₹1.1 L
Dehradun
3 Aug 2024
22 Jun 2023
12 Jul 2023
22 Jun 2023
10 Jul 2023
22 Jun 2023
22 Jun 2023 - 26 Jun 2023
27 Jun 2023
Amount
Supply, installation, testing and commissioning of 400KVA 11KV/433V Dyn11 Copper Wounded Cast Resin Dry Type Transformer Package sub station Outdoor Type ,Transformer enclosure type-tested for IP23 or above and enclosure temperature class as K10 or better, made of Galvanized sheet steel housing in a combination of 1.5/2mm (2mm for Load Bearing and 1.5mm for non-load bearing) , CSS shall be supplied by OEM only, system integrator / JV Partners are not acceptable. Substation can be lifted with transformer installed, Enclosure painted with powder coating/polyurethane paint, Aesthetic, glossy/matt finish, HT and LT Compartment as IP54, copper wound, Class F insulation associated with winding temperature indicator,Dry transformer suitable for CSS Enclosure including supplying and laying of copper conductor multicore control cable from transformer to HT breaker for safety tripping suitably mounted on MS channel including supplying and grouting of suitable MS channels, with all accessories and conforming to IEC 62271-202. Makes Of CSS : Siemens/Schneider/ABB/L&T The 11kV Outdoor Package Sub-Station shall be consisting of following ,
HT SWITCHGEAR 11kV, 630 Amps 21KA for 3 Sec. SF6 insulated Non-Extinsible Fixed type with Copper Busbar Compact switchgear (Type CCV) consisting of Two no load break switch and One No. Fixed Manual Vacuum Circuit Breaker having inbuilt load break switch and earth switch within SF6 insulated robotically welded non ferrite non magnetic stainless steel enclosure of thickness 2.5mm having IP 67, with series trip,self powered microprocessor based numerical 3 O/C & 1 E/F relay (IDMTL + Inst.) protection.HT switchgear & Vacuum Interrupter shall be of same make as CSS OEM, Interconnection between HT switchgear and transformer shall be using 1Cx3x95 sq.mm Al. unarmorured XLPE Cable(Make: ABB /Siemens/Schneider/ L&T) - 1 No.
Relay Shall be Self-powered with communication port (50,50N,51,51N) (Make : Ashida/C&S/Schneider ) or as per OEM - 1 No.
Protection CT: 40/1A 2.5VA 5P10 (Make: Ericon/ECS/Bharti Electricals/equiv) or as per OEM - 1 No.
Metering CT's of ratio 40/1 A, 2.5VA, Class 1.0 accuracy ( Make: Ericon/Pragati/Eq) or as per OEM - 1 No.
Metering Bus PT's of ratio 11KV/Root3/110V/Root3 50VA Class 1.0 accuracy ( Make: ECS/Pragati/Eq) or as per OEM -1 No.
Digital Multifunction meter Class 1.0 accuracy ( Make: ABB/Rishabh/Secure/Conzerv) or as per OEM - 1 No.
Voltage Presence Indications as per OEM - 2 Nos.
Mechnical indications for breaker ON/OFF/TRIP/SPRING CHARGE as per OEM - 1 No.
Manometer as per OEM - 1 No.
Operating Handle as per OEM - 1 No.
TRANSFORMER 400KVA 11KV/433V Dyn11 Copper Wounded Cast Resin Dry Type Transformer with Off load tap links of +5% to -10% @step of 2.5%. Class of Insulation: F, Temperature rise 90 deg.C. over ambient temp of 50 Deg C. Losses Standard (as per ECBC 2017 ) Max Losses at 50% Loading- 1290W and Max Losses at 100% Loading -3300W, % Impedance - 4.5% ( IS Tol) with Surge Arrester on HT side. - 1 No.
Hooter in Transformer Compartment - 1 No.
Winding Temperature Indicator with Alarm and Trip Contact - 1 No.
LV Panel 800 Amp. AL. Busbar (100% for Phase and 50% for Neutral) Current density of AL. shall be 1 Amp. / Sqmm.. LT panel made up of 1.5/2mm thick CRCA sheet.
INCOMER FROM TRANSFORMER 800 Amps 433V 4P 50Hz Fixed Manual drawout type Air Circuit Breaker with Mircoprocessor based over current, short circuit and earth fault Release Long-time + Short-time + Instantaneous + Equipment Ground-fault Protection (LSIG/LSING) - 1 No.
OUTDOOR ENCLOSURE Outdoor type enclosure having construction of Galvanised Sheet Steel of thickness 2mm for Load bearing member and 1.5mm for non load bearing member with 4mm baseframe. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 34 degree of protection for Transformer compartment. The enclosure exterior shall be powder coated ( colour Light Gray & D.A.Gray ). Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for MV & LV compartment. Seperate switch operated bulket lamp+hooter in transformer compartment. Transformer compartment door interlocked with Breaker module
INTERCONNECTION AND EARTHING Interconnection Between HT switchgear & Transformer using 1Cx3x150Sq.mm XLPE AL. Single core cable. Interconnection between Transformer & LT switchgear using Al. Busbars. Internal earthing connections by using 50x6 mm GI Strips including Transformer Neutral.
LT Panel Low Voltage Panel suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system as per standard IEC 61439- 1 &2 as DVA from OEM Authorized Partners and of suitable size fabricated in compartmentalized design with CRCA sheet steel of 1.6mm thickness for load bearing member and 1.6mm for Non load bearing member. Complete with 7 tank process (automatic PT spray) for powder coating in the approved shade, the Panel shall be suitable for Internal Arc Test 85kA for 300mS as per IEC61641 and Seismic Zone-V tested, Form of Separation Form 3b, Mechanical Impact IK10 as per IEC. The board shall be dust and vermin-proof with a degree of protection IP 54
800 Amps 433V 4P 50Hz Fixed Manual drawout type Air Circuit Breaker with Mircoprocessor based OC, EF, SC Protection Long-time + Short-time + Instantaneous + Equipment Ground-fault Protection, Pretrip alarm as main incomer -1.LV switchgear shall be of same make as per OEM - 1 No.
630 AMPS 433V 4P 36KA MCCB For Outgoing - 3 Nos.
800 AMPS 433V 4P 50KA Electrical drawout type Buscoupler with Mircoprocessor based OC, EF, SC Protection Long-time + Short-time + Instantaneous + Equipment Ground-fault Protection, Pretrip alarm as main incomer - 1 No.
LED Type Indicating Lamps- R,Y,B Phase and ON-OFF-TRIP - 1 No.
LT Current Transformer -800/5 Amps, 5 VA, Class-1.0 - 1 No.
RYB, ON-OFF-TRIP Indications - 3 Nos.
Digital Multifunction meter of Model - 1 No.
800 AMPS 433V 4P 50KA Electrical drawout type Air Circuit Breaker (ACB) with microprocessor Based over current, short circuit and earth fault Release Long-time + Short-time + Instantaneous + Equipment Ground-fault Protection (LSIG/LSING) as DG incomer - 1 No.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I.pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required
Providing and laying in position reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set/CSS etc including form work etc as required (excluding reinforcement).
Katsons Technologies Private Limited
MITTAL MACHINES PVT LTD
M/s Shashi Enterprises
Ankit Electricals
VERSATILE
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .