Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.6 LAccepted-Finance | L1 | Accepted-Finance Lowest Bidder | |
| 2 | L2₹15.2 L+₹68,141.50 (4.68%)Rejected-Finance RUDRANAGAR P S SAGAR 24 PARGANAS SOUTH | L2 | Rejected-Finance Higher Bid | |
| 3 | L3₹26.7 L+₹12.2 L (83.5%)Rejected-Finance | L3 | Rejected-Finance Higher Bid |
Tender Value
Refer Docs
EMD Value
₹42,169
Closing Date
15 Feb 2024, 3:00 pmClosed
EE, South 24 Pgs. Elect. Divn.
57/2 Diamond Harbour Road Kolkata -700 023
Special Repair and allied Electrical rennovation work of Sagar Primary Health center including staff Quarter, Sagar under Kakdwip Electrical Sub-Division, PWD.
2024_WBPWD_655497_1
WBPWD/EE/S24PED/eNIT54_2nd Call/2023-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Sagar PHC, Sagar
Please refer Tender documents.
4 documents required · 4 mandatory
₹42,169
South 24 Parganas Electrical Division
20 Jun 2024
29 Jan 2024
17 Feb 2024
29 Jan 2024
15 Feb 2024
2 Feb 2024
2 Feb 2024
Amount
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] [Avg. Run 9 Mtr.]
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) --- Do--- Do--- Do--- [ On Board 5A]
Distribution wiring in 1.1 KV single core stranded 'ZHFR / LS0H' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC [Computer Board & seperate power plug]
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC HTPN to SPNDB
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC [Computer Board & seperate power plug]
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC HTPN to SPNDB
Supplying and fixing 415V, 160A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (Make - Hevells / Simense / L&T/ABB)
Supplying and fixing 415V, 160A TPN on load front operated changeover switch with sheet steel enclosure on angle iron frame on wall with nuts,bolts etc as per direction of EIC. (Make - Hevells / Simense / L&T/ABB)
Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl. 01 No. bus bar section: 500V , 200A capacity electrolity grade tinned Copper busbar with horizontal section of size 75x6mm for R,Y,B & 50x5mm for neutral bar & 50x5 mm tinned copper bar for earth & dimension of 500x150mm for sheet metal box. A bus bar shall be fixed with FRP chair & the entire bars are insulated with PVC heat shrinkble sleeves of suitable size & colour as per direction of E.I.C – ( As per Drawing no. 470 of PWD Specification Book – May 1991)
Supply of 1.1 KV Gr. XLPE/ PVC Armoured Al Cable with 2x10 SWG GI wire laying (Make:Gloster / Havells /RR Kabel/ Polycab) 4 core 50 sq. mm. Cable
Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed as per direction of EIC.
S & F compression type brass cable gland complete with brass gland, brass ring & rubber ring for dust & moisture proof entry of XLPE/PVC armoured cable. 4 core 50 sq. mm.
Finishing the end of the XLPE/PVC armoured cableas by crimping method incl. S&F solderless socket (Dowels make), tapes, anticorrosive paste & joiting materials. 4 core 50 sq. mm.
Supplying and fixing 4-way double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, with cable-end box at both ends, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of, spiral link, copper wire & neutral link & provision for earthing attachment, as per GS. Incoming 125 A Four pole MCCB-1no, Outgoing 63A TPMCB-2 no. (Make:Legrand/ L&T/ Simens/ABB) .
S&F 415 V, Horizontal type, TPN MCB DB (6-way) with SS enclosure double-door with IP-42/43 protection, with cable-end box at both ends & Four Pole Isolators as incomer and SPMCBs ('C' Curve, 10 KA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Interconnection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS. Incoming 63 A TPNMCB -1 No, Outgoing 6-32A SPMCB-18 no. (Make:Legrand/ L&T/Simens/ABB) .
S&F 2+8 way double-door SPN MCB DB (IP-42/43 Protection)with 240V 32A DPMCB isolator as incomer and 8 Nos. 6-16A SPMCB as outgoing, on flat iron frame on wall and mending good the damages to original finish, incl. Inter connection with suitable size of copper wire and neutral link and provision for earthing attachment as per GS. (Make:Legrand/ L&T/Simens) .
Supply & Fixing 240 V, 16A, plug socket with separate 16 A Piano key type switch (Brand approved by EIC) on sheet metal switchboard embedded in wall incl. S & F 150x100x65mm MS (16SWG) switchboard and akelite/perspex top cover of 3mm thick by Brass screws after making housing for the switch by cutting bakelite/perspex cover and making necessary connections as required. (Power Plug)
Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch with indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. (Piano type Computer Board)
Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required as per direction of EIC.
Supply and delivery of Single LED Fitting (18Watt, 230VAC, 50hZ, 4000K NW, THD<10%, bult in 2.5KV SPD) with all accessories incl. 1 nos 20W LED Tube, as directed by EIC. (Luminous Efficiency >=105 and <120 lumen/watt with BEE Certification) [Make: Philips, Havells, Bajaj, CG, Wipro or as per EIC]
Fixing only single light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length
Supply & delivery of 1200 mm sweep 230 volt AC Ceiling fan incl. Blades, canopy etc. With 18" down rod(14SWG), Fork(10SWG), Heavy type insulator, 3/8th inch bolt with nut, heavy type split pin etc., as directed by EIC. (with Safety Wire & S3/P2 Capacitor) [Make-Orient - Summer cool (1200 mm Metalic Bronze Copper) or similar spec of Crompton/Usha - Striker 1 Star ]
Supply and delivery of 230V 230mm (9") Exhaust fan with all necessary accessories, as directed by EIC. [Make: EPC Heavy Duty, Usha, CG, Bajaj or equiv Make]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
Engraving the deptt. number with 10 mm lettering on the body as per GS.
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and aking connection for exhaust of following diameter: a) 23cm (9")
Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) a) 23cm (9")
Supplying & Fixing CRC sheet metal (16 SWG) JB-cum- Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on Bakelite/Hard Rubber insulator over the MS welded chairs incl. bakelite/Perspex/coloured Perspex (wall matching colour) top cover 3 mm thick flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works -- 150 mm x 100 mm x 65 mm
Dismantling the existing old & damaged electrical wiring, switch board(approx-325 sets), power plugs(approx-100 sets ),computer board(approx-373 sets), fixtures (approx-635),Ceiling fans(approx-195pcs),Wall bracket fans(approx-33 pcs),exhaust fans(approx-21 pcs),SPNDBs(approx-49 sets),PDBs(approx-14 sets), VTPNs (approx-3 sets),LT panels(approx-3sets),LT cables(approx-1500mtr) all the entire building(approxArea--41350sqft) etc. from its own position with own tools & tackles, manpower and mending good the damages as per G.S.(Salvage value of less cost materials)
Supplying and fixing sheet metal inspection boxes (16 SWG) of The following sizes flushed in wall by housing the same after cutting brick walls incl. making earthing attachments, painting and mending good damages to building works a) 100 mm x 100 mm x 65 mm
Supply & delivery of 250V, 72W (Maximum) LED street light with IP-66, individual Secondary Optics Peanut Lens and Separate Toughned Glass Diffuser, Potted Driver to be used, 7000 lumen (minimum) output fittings, as directed by EIC. [Make: Havells or equivalent spec of K-Lite/ Philips/ Crompton]
Fixing only outdoor / street light type LED light fitting complete with all accessories on existing 1.5 mtr single arm bracket.
Supply & delivery of swaged type MS tubular pole conforming to IS:2713/1980 (9 mtr long, 410-SP-32), as directed by EIC. [Make - Bajaj / Utkarsh / Jindal / Subham]
Painting of Steel Tubular Pole of 9 mtr. lengths and no. of coats of paint, as given below with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint (a) 1st coat of aluminium paint over 1 coat of RO priming
(b) 2nd coat of aluminium paint over 1st coat
S&f 50 mm 1.5 mtr long detachable type G.I single arm bracket, suitable for polehead . The arm bracket shall be p[roperly weded with 15 mm . Stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the poleby bolts, nuts andwasher as per directionof EIC ( Make - Bansal/ Utkarsh/ subham/Jindal) as per GS
S&Delivery of 1.1 kv grade 2Cx16 sq mm XLPE-armoured AL. cable, as directed by EIC.(for Compound Light Connection) [Make - Polycab/Havells/RR Kabel/Gloster]
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint.
S&F of 250V double door Compound light Timer DB [equivalent of 2+10 way SPNDB] with sheet steel enclosure, pnosphitised powder coated neutral bar, DIN rail with IP-43 potection comprising with 1 no. 40A DPMCB ('C' curve 10KA), 2 no. 16A SPMCB ('C' curve 10KA), 1no. Programmable time switch-24 hrs with minimum switching of 15 minutes and 1 no. 18A/25A 2-Pole power contractor with inner-outer plate & internal wiring by suitable size of cu. wire incl. 1 no. Auto-Manual bypass toggle switch and provision for earthing attachment, incl. LED indication light for running condition with mechanical locking arrangement, as directed by EIC. [Make-ABB/L&T/Crabtree]
Erection of Single Steel tubular pole of length as given below with/without sole plate & Cap etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly, as per GS. (a) Upto 9.0 mtr. Size 0.6x0.6x1.70 mts
Extra on above item, for providing CC (6:3:1) base block (around the pole) dimension 0.45x0.45x0.60 mt. above ground level, neatly cemented finish (3 mm thick), at the base pole (in lieu of CC muffing) suitable for alkathene/ polythene pipe entry as directed for street light wiring, incl. S & F 20cmx15cmx10cm GI Loop box, 16SWG & incl. drilled hole in pole, as per GS.
Laying of 1.1 kv grade 2Cx16 sq mm XLPE-armoured AL. cable, in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick and cable and also the trench with shifted soil, leveling up and restoring the surface duly rammed as per direction of EIC
Supplying and fixing compression type gland complete with brass gland, brass ring and rubber ring for dust and moisture-proof entry of XLPE/PVC armoured cables as below : a) 2 core 16 sq mm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : a) 2 core 16sq mm
Supply & Fixing 240V, fan regulator (Step type) (Brand approved by EIC) on existing GI switch board with top cover plate incl. Making necy. connections etc.
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: a) By TATA Medium GI Pipe
Excavation of soil for installation of Earth Electrode and filling & ramming. (For Soft Soil)
Connecting the equipments to earth busbar including S & F Solid GI (Hot Dip) wire of size as below as per GS -- No.-4 SWG
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
STAFF QUARTER
Dismantling the all fittings, Switch Board, SPNDB, PBDBD, Existing wiring with skilled man power maintaining electrical power temporarily.
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed] [Avg. Run 6 Mtr.]
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) --- Do--- Do--- Do--- [ On Board 5A]
Distribution wiring in 1.1 KV single core stranded 'ZHFR / LS0H' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC [Computer Board & seperate power plug]
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC [Computer Board & seperate power plug]
Supplying and fixing 415V, 63A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (Make - Hevells / Simense / L&T)
S&Delivery of 1.1 kv grade 2Cx10 sq mm XLPE-armoured AL. cable, as directed by EIC.(For Indivisual Meter Connection to SPNDB) [Make - Polycab/Havells/RR Kabel/Gloster]
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting as per direction of EIC.
S & F compression type brass cable gland complete with brass gland, brass ring & rubber ring for dust & moisture proof entry of XLPE/PVC armoured cable. 2 core 10 sq. mm.
Finishing the end of the XLPE/PVC armoured cableas by crimping method incl. S&F solderless socket (Dowels make), tapes, anticorrosive paste & joiting materials. 2 core 10 sq. mm.
S&F 2+8 way double-door SPN MCB DB (IP-42/43 Protection)with 240V 32A DPMCB isolator as incomer and 8 Nos. 6-16A SPMCB as outgoing, on flat iron frame on wall and mending good the damages to original finish, incl. Inter connection with suitable size of copper wire and neutral link and provision for earthing attachment as per GS. (Make:Legrand/ L&T/Simens) .
S&F 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, two nos. 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with two nos. 6A Modular type switch, without plug top on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
S&F 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & delivery of 250V, 72W (Maximum) LED street light with IP-66, individual Secondary Optics Peanut Lens and Separate Toughned Glass Diffuser, Potted Driver to be used, 7000 lumen (minimum) output fittings, as directed by EIC. [Make: Havells or equivalent spec of K-Lite/ Philips/ Crompton]
Fixing only outdoor / street light type LED light fitting complete with all accessories on existing 1.5 mtr single arm bracket.
Supply & delivery of swaged type MS tubular pole conforming to IS:2713/1980 (9 mtr long, 410-SP-32), as directed by EIC. [Make - Bajaj / Utkarsh / Jindal / Subham]
Painting of Steel Tubular Pole of 9 mtr. lengths and no. of coats of paint, as given below with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint (a) 1st coat of aluminium paint over 1 coat of RO priming
(b) 2nd coat of aluminium paint over 1st coat
S&f 50 mm 1.5 mtr long detachable type G.I single arm bracket, suitable for polehead . The arm bracket shall be p[roperly weded with 15 mm . Stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the poleby bolts, nuts andwasher as per directionof EIC ( Make - Bansal/ Utkarsh/ subham/Jindal) as per GS
S&Delivery of 1.1 kv grade 2Cx16 sq mm XLPE-armoured AL. cable, as directed by EIC.(for Compound Light Connection) [Make - Polycab/Havells/RR Kabel/Gloster]
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint.
S&F of 250V double door Compound light Timer DB [equivalent of 2+10 way SPNDB] with sheet steel enclosure, pnosphitised powder coated neutral bar, DIN rail with IP-43 potection comprising with 1 no. 40A DPMCB ('C' curve 10KA), 2 no. 16A SPMCB ('C' curve 10KA), 1no. Programmable time switch-24 hrs with minimum switching of 15 minutes and 1 no. 18A/25A 2-Pole power contractor with inner-outer plate & internal wiring by suitable size of cu. wire incl. 1 no. Auto-Manual bypass toggle switch and provision for earthing attachment, incl. LED indication light for running condition with mechanical locking arrangement, as directed by EIC. [Make-ABB/L&T/Crabtree]
Erection of Single Steel tubular pole of length as given below with/without sole plate & Cap etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly, as per GS. (a) Upto 9.0 mtr. Size 0.6x0.6x1.70 mts
Extra on above item, for providing CC (6:3:1) base block (around the pole) dimension 0.45x0.45x0.60 mt. above ground level, neatly cemented finish (3 mm thick), at the base pole (in lieu of CC muffing) suitable for alkathene/ polythene pipe entry as directed for street light wiring, incl. S & F 20cmx15cmx10cm GI Loop box, 16SWG & incl. drilled hole in pole, as per GS.
Laying of 1.1 kv grade 2Cx16 sq mm XLPE-armoured AL. cable, in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick and cable and also the trench with shifted soil, leveling up and restoring the surface duly rammed as per direction of EIC
Supplying and fixing compression type gland complete with brass gland, brass ring and rubber ring for dust and moisture-proof entry of XLPE/PVC armoured cables as below : a) 2 core 16 sq mm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : a) 2 core 16sq mm
Supply and delivery of Single LED Fitting (18Watt, 230VAC, 50hZ, 4000K NW, THD<10%, bult in 2.5KV SPD) with all accessories incl. 1 nos 20W LED Tube, as directed by EIC. (Luminous Efficiency >=105 and <120 lumen/watt with BEE Certification) [Make: Philips TMC 502 P 1xT-LED & Mas LEDTube 1200mm 18W865 T8 I – 2100lm , Havells, Bajaj, CG, Wipro or as per EIC]
Supply & Delivery of 220-240 V B22 09 Watt CDL/ 6500K LED Lamp (Make-Havells, Philips/Crmpton or as per EIC)
Fixing only single light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length as per direction of EIC.
Supply & delivery of 1200 mm sweep 230 volt AC Ceiling fan incl. Blades, canopy etc. With 18" down rod(14SWG), Fork(10SWG), Heavy type insulator, 3/8th inch bolt with nut, heavy type split pin etc., as directed by EIC [Make-Orient - New Breeze/Summercool or similar spec of Crompton/Usha]
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc. As per direction of EIC.
Supply & fixing two pieces type fabricated beam to beam clamp (approx. length 2mtr.) made with 50X6mm MS strip suitable for fixing of special type of Fan Clamp and also tube light fitting to maintain uniform spacing, including S&F 4nos. Nut-bolts for fixing of clamp on Iron 'I' -section. as per direction of EIC
Supply and delivery of 230V 230mm (9") Exhaust fan with all necessary accessories, as directed by EIC. [Make: EPC Heavy Duty, Usha, CG, Bajaj or equiv Make]
S&F LED bulk head light fitting (Approved make) with die cast aluminium housing & frosted glass on wall/ceiling incl. S&F 8watt CFLcomplete set. (Make - Havells / Crompton/ Bajaj)
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
Engraving the deptt. number with 10 mm lettering on the body as per GS.
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and aking connection for exhaust of following diameter: a) 23cm (9")
Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) a) 23cm (9")
Supplying & Fixing CRC sheet metal (16 SWG) JB-cum- Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on Bakelite/Hard Rubber insulator over the MS welded chairs incl. bakelite/Perspex/coloured Perspex (wall matching colour) top cover 3 mm thick flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works -- 150 mm x 100 mm x 65 mm
Supplying and fixing sheet metal inspection boxes (16 SWG) of The following sizes flushed in wall by housing the same after cutting brick walls incl. making earthing attachments, painting and mending good damages to building works a) 100 mm x 100 mm x 65 mm
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: a) By TATA Medium GI Pipe
Excavation of soil for installation of Earth Electrode and filling & ramming. (For Soft Soil)
Connecting the equipments to earth busbar including S & F Solid GI (Hot Dip) wire of size as below as per GS -- No.-4 SWG
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
S & F Lightning Conductor Air Terminal made of 20 mm dia 1000 mm long GI pipe (ISI Medium) having five discharge prongs of 4 SWG GI (Hot Dip) wire at top duly soldered with 7/16 stranded GI (Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. complete duly grouted on the parapet etc. in CC mortar ( 4:2:1), including thimble joints of 7/16 SWG wire and GI strip with SS nuts, bolts & washers.
Supply & fixing GI (Hot Dip) strips 25 mm x 6 mm thick for horizontal & Vertical run on the Parapet/Roof/ Wall with GI Saddles 1100 mm apart incl. mending good the damages to building works, including welded lap joints, 'T' joints, etc. and painting the joints with 2 (two) coats of bituminous paint.
Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works: i) Length upto 0.5 Mtr
ii) Length above 0.5 Mtr
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run.
Supply & Fixing of Testing Joints by 25 mm x 6 mm thick GI (Hot Dip) strip 125 mm long on wall after making suitable arrangement to establish a clearance of 50mm from wall for making junction connection with vertical conductor and conductor from earth electrode complete with S & F GI bolts, nuts, check-nuts, spring washers etc. and provide a protective arrangement for that junction point by keeping it in a GI housing / enclosure (openable for maintenance procedure) , as required.
Supply, Laying & Fixing of 50mm x 6mm galvanized (Hot Dip) steel strip in underground trench for interconnection between the Earth Points by proper welding and painting the lap & 'T' joints with 2 (two) coats of bituminous paint for making a Earth Grid.
Excavation of soil for installation of Earth Electrode and filling & ramming. (for Soft Soil)(P-G1/Item-1a)
Earthing with 65 mm dia GI pipe (TATA-Medium) with welded half circle bracket of GI strip (65 x 8) mm. with two holes on extended portion of the strip of length min. 200 mm and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts. --- For LC.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required as to GS.
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe as to GS.
Extra for treatment of soil by using salt & charcoal or coke for plate electrode as to GS.
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required ISI 32 mm dia.
Testing the entire E.I. system of the whole as mentioned above after installation & making necessary connection of all the Main Switches of Panels, DBs (VTPN, PDB, SPNDBs) / cables / wires / fan / fittings all electrical parameters, protective system by Megger/ Testing equipment by certified Engineer(s) / Approved Supervisor of DOE and providing the test report with Test Report in proper format & submit as built up drawing by AUTOCAD by softcopy as well as hard printed copy (Single Line Diagram) (4 Copies - A1 Sheet) as per direction of EIC.
Note: 1) All the above rates should be quoted inclusive of all taxes & duties, District charges and LWC as applicable, with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees.
NITESH MANAGEMENT
SHATABDI ENGINEERING AND CONSULTANCY
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .