| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹189.7 CrAccepted-AOC | ₹189.7 Cr | L1 | Accepted-AOC Accepted being reasonable and workable rates are quoted |
| 2 | L2₹194.2 CrRejected-Finance | ₹194.2 Cr | L2 | Rejected-Finance Being not L1 |
| 3 | L3₹196.5 CrRejected-Finance 126 A JAIPUR HOUSE AGRA 282010 PH NO 0562 2810176 9897638555 | ₹196.5 Cr | L3 | Rejected-Finance Being not L1 |
| 4 | L4₹198 CrRejected-Finance | ₹198 Cr | L4 | Rejected-Finance Being not L1 |
| 5 | L5₹202.0 CrRejected-Finance | ₹202.0 Cr | L5 | Rejected-Finance Being not L1 |
Tender Value
₹201.0 Cr
EMD Value
₹15 L
Closing Date
4 Jun 2022, 6:00 pmClosed
DDG CE
DG CE Conference Hall DGNP V Naval base post Visakhapatnam 14
PROVISION OF UG SUMP CUM PUMP HOUSES OVER HEAD TANKS DISTRIBUTION NETWORK AND OTHER ALLIED SERVICES UNDER WP 05B AT NAVAL STATION RAMBILLI NEAR VISAKHAPATNAM
2022_MES_510446_1
DDG CE V TOKEN 18 OF 2021-2022
Open Tender
Civil Works
900 days
Rambilli
AS per NIT
9 documents required · 9 mandatory
₹3,000
DGNP
₹15 L
Yes
DDG CE Conference Hall
20 Jul 2022
25 Feb 2022
6 Jun 2022
25 Feb 2022
4 Jun 2022
2 May 2022
25 Feb 2022 - 4 Mar 2022
21 Mar 2022
Amount
Lump sum amount worked out by the contractor for "Buildings & Structures" as listed in Schedule 'A' Part-I on Serial Page No.
Lump sum amount worked out by the contractor for "Site Clearance / Area Development / Earthwork excavation" as listed in Schedule 'A' Part-II on Serial Page No.
Lump sum amount worked out by the contractor for "Pile Foundation" as listed in Schedule 'A' Part-III on Serial Page No.
Lump sum amount worked out by the contractor for "RCC Pillars for Pipe Lines" as listed in Schedule 'A' Part-IV on Serial Page No.
Lump sum amount worked out by the contractor for "Path" as listed in Schedule 'A' Part-V on Serial Page No.
Lump sum amount worked out by the contractor for "Area Drainage" as listed in Schedule 'A' Part-VI on Serial Page No.
Lump sum amount worked out by the contractor for "Fencing/Gate/Retaining Wall" as listed in Schedule 'A' Part-VII on Serial Page No.
Lump sum amount worked out by the contractor for "Internal Water Supply" as listed in Schedule 'A' Part-VIII on Serial Page No.
Lump sum amount worked out by the contractor for "Internal Electrification" as listed in Schedule 'A' Part-IX on Serial Page No.
Lump sum amount worked out by the contractor for "External Water Supply" as listed in Schedule 'A' Part-X on Serial Page No.
Lump sum amount worked out by the contractor for "Lightning Protection" as listed in Schedule 'A' Part-XI on Serial Page No.
Lump sum amount worked out by the contractor for "External Fire Fighting" as listed in Schedule 'A' Part-XII on Serial Page No.
Schedule "A" Part - XIII: [Miscellaneous Items] [Pile Foundation, Internal Water Supply, Internal Electrification, External Water Supply, Lightning Protection, External Fire Fighting and Crane]: [To be quoted by the bidder.]
M&L for Point wiring with 1.5 Sq.mm FRLSH PVC insulated unsheathed copper conductor cable, single core multi stranded 1100Volt grade confirming to IS 694: 1990, drawn in and including rigid PVC conduit not less than 20/25mm bore, concealed type, medium grade as per IS 9537 (Part 1-1983) with conduit accessories, junction boxes, tees, terminal boxes with and including concealed pressed steel terminal box of suitable size fabricated out of 2mm thick MS sheet and 3mm thick lminated hylam sheet top cover for fixing switches, switch socket, including one run of 1.5 Sq.mm single core FRLSH PVC unsheathed copper conductor cable as earth continuity conductor and connected to common earth dolly, for one light point controlled by one way switch, complete all as specified and as directed.
Description all as per Serial Item No. 13 here in before but for fan point controlled by one way switches complete.
Description all as per Serial Item No. 13 here-in-before but with 1.5 Sqmm copper conductor cable and 1.5 Sqmm cable as earth continuity conductor for 3 pin 5Amp switch socket point, on independent board, complete all as specified.
Description all as per Serial Item No. 13 here-in-before but for 3 pin 5Amp switch socket point, on Same board, complete all as specified.
Description all as per Serial Item No. 13 here-in-before but with 4.0Sqmm copper conductor cable and 4.0 Sqmm cable as earth continuity conductor for 3 pin 5/15Amp switch socket point, on independent board, complete all as specified.
S&F Wall mounting fan 450mm sweep of approved colour and model, with complete accessories (Energy Efficient) including provision of suitable clamp, flexible cable suitable for 230 Volt, AC 50 Hz, complete all as specified and as directed.
S&F Energy saving, environmentally friendly & robust High bay light LED 80 Watt energy efficient, P.F>0.95, >100 lum/watt, with and including LED light driver holder connecting of with three core flexible copper conductor cable of suitable size, complete all as directed by Engr-in-charge. Make: Cat No. LHELAAU7PG7S080 of Havells or Equivalent in makes given here-in-after.
S&F Decorative luminary suspended type mounting 40/35 watt, 220Volt, P.F>0.95, >100 lum/watt, complete with 30/35 watt, lamp holder, complete made up of polycarbonate, connecting of with three core flexible copper conductor cable of suitable size, complete all as directed by Engr-in-charge. Make Cat. BLRL 35CDMT 35W of Bajaj or equivalent in makes given here-in-after.
S&F LED Building Security light fitting 40Watts, 230 volts, >100lum/W, with Suitable size GI bracket made out of 25/40mm GI pipe fixed with clamps, nuts&bolts etc., complete with IP 65/66 protection with LED lamp, driver, bracket with impact and corrosion resistant and all accessories, complete all as specified and as directed. Make Cat. CIS-300-40-57-SL-DP-NGR for batten and LT8-20-865(2) for tube of Crompton or equivalent in makes given here-in-after.
M&L for Earthing complete with galvanised steel earth plate electrode 60cm X 60cm X 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead 4mm GI wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-I, including excavation / earth work in any strata, adequate quantity of charcoal and common salt, PCC chamber with with RCC 1:2:4 type B1 40mm thick cover slab with suitable handle and angle iron frame of suitable size to fix the cover, with 20mm bore GI pipe light grade for watering with funnel, wire mesh and 15mm bore GI pipe medium grade for GI wire protection and 4mm GI earth wire, including testing after completion, complete all as specified and directed. Note: Earth wire will be measured after 7.5mtr from the earth strip or earth testing terminal block whichever is lesser under relevant item.
Supply, lay, test and commissioning of one run of minimum 6 Fibre OFC cable with and including 40mm HDPE duct pipe with and including all its connected accessories, laid in trenches or ducts or through the pipe etc., complete all as specified and as directed. Note: One run of Cable and one run of duct Pipe shall be measured as one RM.
M&L for Design, Manufacture, supply, testing and commissioning of electrically operated, double girder EOT crane as per IS -807 & IS -3177 with span 7.9mtrs (Apx) having 5Ton capacity and lifting ht 5.0mtrs from floor level, long travel of length 20mtrs with and including required crane track rail, Speed of main hoist - 3mtr/min, Main Creep Speed - 0.3m/min, Long Creep Speed - 1m/min, Speed of long travel - 10mtr/min, All micro speed will be 1/10 of main speed by all motions, DSL system with PVC sheated copper bus bar for 3 Phase & neutral with earth bus system with locking system & VVF Drive system, push button system, radio remote controlling systems, all safety provisions and audio visual alarm system to all motions, single phase preventer, over load relay, safety siren/over load alarm with and including connection upto DB with suitable cable from panel board to crane and conduit as per site requirement, additional push button system with interlocking wiring with and including all connected accessories like rope drum, steel wire rope, sheaves, pulleys, hydraulic brake, single phase preventer, overload relay, SFU, air brake contactor, main hoist motor, micro hoist motor, long & cross travel motor, lift hook, service platform, walkway with railing, safety latch, load indicator, catwalk along length of crane, ladders, buffers, hooks & clamps on wall etc., complete all as specified and as directed. Note: Span and Long travel may vary slightly as per site condition.
M&L for Supply, erection, testing and commissioning of HOT crane with span 7.9mtrs (Apx) having 5Ton capacity and lifting height 5.0mtrs from floor level, long travel of length 21.80mtrs with phosperous bronze cladding wheels, grade 80 load chain & zinc plated hand chain, non-ferrous parts like chain wheels, chain guides, ratchet wheel and stripping fork, double girder hand operated chain cross travelling trolley complete with ISMC girder rails, chain pulley block confirming to IS:807, IS: 3177 and IS: 3822 or latest IS, complete all as specified and as directed. Note: (i) Span and Long travel may vary slightly as per site condition. (ii) The double girder for the above HOT Crane has already installed at Main MRS Pump House.
S&F Voltage stabilizer 1KVA for automatic operation, suitable for deep freezers / refrigerator / water cooler / 2 Ton AC, single phase naturally air cooled indoor type and designed for input variation 170V to 250V, output voltage stabilized at 230Volt with accuracy of ± 2.50%, complete all as specified and as directed.
S&F AFFF type fire extinguishers - mechancial foam type 9 litres capacity, complete with initial charge, gun metal cap, discharge hose with nozzle, wall fixing brackets, etc., complete all as specified.
S&F CO2 fire extinguishers - 4.5 Kg capacity, complete with initial charge, gun metal cap, discharge hose with nozzle, wall fixing brackets etc confirming to IS : 15683 with ISI mark, complete all as specified.
S&F Dry chemical powder extinguishers, 9Kg capacity, complete with initial charge, gun metal cap, discharge hose with nozzle wall fixing brackets etc., confirming to IS : 15683 with ISI mark, complete all as specified and as directed.
S&F Cast Iron Air release valve with single air outlets, conforming to IS: 14845, suitable for 100mm bore, flanged of class PN 1.6, rubber lined, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
S&F Cast Iron Air release valve with single air outlets, conforming to IS: 14845, suitable for 150mm bore dia, flanged of class PN 1.6, rubber lined, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
Supply, laying, testing and commissioning of Ductile Iron pressure pipe of 100mm bore with socket and spigot ends with blast furnace sludge cement with Portland cement properties suitable for push -on-jointing with inside cement mortor lining with internal metallic zinc coating and external black bitumen coating duly ISI marked, confirming to IS-8329:2000, class K-9, PN-10 rating, laid in trenches / floor, complete all as specified and as directed. Note: 1. Necessary earth work will be measured and paid separately. 2. Necessary fittings will be measured and paid separately.
Description all as per Serial Item No.34 here in before but for 150mm bore dia pipe, complete all as specified.
Description all as per Serial Item No.34 here in before but for 200mm bore dia pipe, complete all as specified.
Description all as per Serial Item No.34 here in before but for 250mm bore dia pipe, complete all as specified.
Description all as per Serial Item No.34 here in before but for 300mm bore dia pipe, complete all as specified.
Description all as per Serial Item No.34 here in before but for 400mm bore dia pipe, complete all as specified.
Description all as per Serial Item No.34 here in before but for 600mm bore dia pipe, complete all as specified.
M&L for DI Specials such as Bends , tapers any type, Tee pieces, single branch, "Y" junction, double branch, cross, collars, caps and plugs for connecting up to 600mm bore DI Pipe all as per IS:9523, complete all as specified and as directed. Note: Fittings shall be conforming to IS 9523:2000.
M&L for Valve chamber of size 1500mm x 1500mm x 1000mm internal dimensions, with and including excavation in any type of soil, spreading, levelling and refilling etc. PCC (1:4:8) type D2 for foundation, Fly ash brick work of one brick thick wall in CM (1:4) including internal plaster 15mm thick in CM (1:4) external plaster 15mm thick(1:4) upto 150mm below GL and providing coping in PCC (1;2:4) type B1, angular iron frame of size 50x50x6mm with 6mm thick MS plate cover complete including locking arrangements and having FRP coating of 2mm thick on both inside and outside surfaces, complete all as specified and shown in TD drawing.
M&L Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine with and including RCC Hume pipe of 250mm bore dia, complete all as specified and as directed.
Supply, install, Retrofitting, test and commissioning of Motor Actuated Butterfly Valve, non rising type conforming to IS-14846, ISI marked, consisting of multiturn single phase actuator and butterfly valve of 200mm bore dia, 430Volt, AC, PN 1.6, double flanged with CI body wheel and brass spindle and nuts etc., with bracket / mounting arrangement, two limit switches for open / close, torque limit switch and splash proof enclosure, with inbuilt Serial / USB port, data logger with memory, SD card, space heater, with and including jointing materials, rubber gasket , nuts &bolts etc., complete all as specified and as directed.
Description all as per Serial Item No.44 here in before but for 150mm bore dia, complete all as specified.
Description all as per Serial Item No.44 here in before but for 100mm bore dia, complete all as specified.
Description all as per Serial Item No.44 here in before but for 80mm bore dia, complete all as specified.
Supply, laying, testing and commissioning of MS ERW pipe heavy grade with ISI mark, of 400mm bore with flanged type ends jointed with rubber or fibre board gasket and confirming to IS-3589:1991, of minimum thickness 6.35mm, laid in trenches / on floor, complete all as specified and as directed. Note: 1. Necessary earth work will be measured and paid separately. 2. Necessary fittings will be measured and paid separately.
Supply, laying, testing and commissioning of MS ERW pipe heavy grade with ISI mark of 600mm bore with flanged type ends jointed with rubber or fibre board gasket and confirming to IS-3589:1991, of minimum thickness 7.01mm, laid in trenches / floor, complete all as specified and as directed. Note: 1. Necessary earth work will be measured and paid separately. 2. Necessary fittings will be measured and paid separately.
M&L for MS ERW pipe Specials such as flanges, Bends , tapers any type, Tee pieces, single branch, "Y" junction, double branch, cross (for all flanged pipe) collars, caps and plugs for connecting up to 600mm bore, including necessary welding works, gasket/rubber sheet as required, complete all as specified and as directed. Note: Fittings shall be of same grade and class as per main pipe.
S&F Cast Iron Sluice valve conforming to IS : 14846 or latest, suitable for 250mm bore pipe, flanged of class PN 1.6, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
S&F Cast Iron Sluice valve conforming to IS : 14846 or latest, suitable for 300mm bore pipe, flanged of class PN 1.6, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
S&F Cast Iron Sluice valve conforming to IS : 14846 or latest, suitable for 600mm bore pipe, flanged of class PN 1.6, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
Supply, fix, testing CI non return valve of 250mm dia, double flanged conforming to IS 8321 Part-I, PN 1.6 complete all as specified and as directed.
Supply, fix, testing CI non return valve of 300mm dia, double flanged conforming to IS 8321 Part-I, PN 1.6 complete all as specified and as directed.
S&F Cast Iron Foot valve ball type, suitable for 100mm bore, shall conform to IS:4038-1986, fitted with and including 'Y' strainer which will have cored holes / slots with straining and including necessary fixing arrangement, complete all as specified and as directed.
S&F Cast Iron Foot valve ball type, suitable for 150mm bore, shall conform to IS:4038-1986, fitted with and including 'Y' strainer which will have cored holes / slots with straining and including necessary fixing arrangement, complete all as specified and as directed.
S&F Cast Iron Foot valve ball type, suitable for 200mm bore, shall conform to IS:4038-1986, fitted with and including 'Y' strainer which will have cored holes / slots with straining and including necessary fixing arrangement, complete all as specified and as directed.
S&F Cast Iron Foot valve ball type, suitable for 250mm bore, shall conform to IS:4038-1986, fitted with and including 'Y' strainer which will have cored holes / slots with straining and including necessary fixing arrangement, complete all as specified and as directed.
S&F Cast Iron Foot valve ball type, suitable for 80mm bore, shall conform to IS:4038-1986, fitted with and including 'Y' strainer which will have cored holes / slots with straining and including necessary fixing arrangement, complete all as specified and as directed.
Description all as per Serial Item No. 61 here-in-before but for 80metre head, 55Cum/Hr discharge capacity pump set, complete all as specified.
Description all as per Serial Item No. 61 here-in-before but for 80metre head, 306Cum/Hr discharge capacity pump set, complete all as specified.
Description all as per Serial Item No. 61 here-in-before but for 80metre head, 130Cum/Hr discharge capacity pump set, complete all as specified.
Description all as per Serial Item No. 61 here-in-before but for 40metre head, 115Cum/Hr discharge capacity pump set, complete all as specified.
Description all as per Serial Item No. 61 here-in-before but for 40metre head, 125Cum/Hr discharge capacity pump set, complete all as specified.
Description all as per Serial Item No. 61 here-in-before but for 40metre head, 16Cum/Hr discharge capacity pump set, complete all as specified.
Description all as per Serial Item No. 61 here-in-before but for 40metre head, 13Cum/Hr discharge capacity pump set, complete all as specified.
Description all as per Serial Item No. 61 here-in-before but for 40metre head, 54Cum/Hr discharge capacity pump set, complete all as specified.
Design, Supply, Installation, Commissioning and Testing of complete online UV DISNFECTION PLANT of capacity 55000LPH, SS304, 1 Pass UV system 320 watt x 3 Lamp chamber of diameter 255mm inlet/Outlet, 100NB flange, for filter fresh water 90% transmission to remove Coliform, Bacteria, CFU from the water of capacity 55 Cum/hr and lower down upto permissible limit as per IS, with and including SS-316 Reactor with suitable flow capacity, hard glass lamps not less than 3Nos and dosing not less than 30,000 uW-sec/cm2, with lamp burning hour and replacement counters with visual replacement alert, all Electrical / Mechanical / Instrumentation / Automation / Control Panel & monitoring works and accessories such as UV Monitoring System, Instrumentation, control Panel, Pressure gauge, Sensor and controller with automatic over temperature safety cut-offs, Automatic/Pre-settable/Adjustable time based switch on/off control, Display and control provisions and accessories, with Operating pressure not less than 120 psi, complete in all respect on turnkey basis, complying to relevant IS standards (in absence BS/ASTM/equivalent), all as per OEM Specifications, complete in all respect for best efficient functioning with 3years performance Guaranty after complete installation & trial run, complete all as specified and as directed. Note: (i) Contractor shall submit drawings for approval before manufacturing at factory and plant shall be confirming to GRIHA 3 rating. (ii) Contractor shall check the actual physical head requirement and impeller modification shall be carried out accordingly.
Description all as per Serial Item No. 70 here-in-before but for online UV DISNFECTION PLANT of capacity 306000LPH, SS304, 3 Pass UV system 320 watt x 10 Lamp with 3 pass inter interconnecting with header chamber of diameter 273mm inlet/Outlet, 150NB flange, UV disenfection main header 200NB, complete all as specified.
Description all as per Serial Item No. 70 here-in-before but for online UV DISNFECTION PLANT of capacity 130000LPH, SS304, 3 Pass UV system 320 watt x 5 Lamp with 3 pass inter interconnecting with header chamber of diameter 254mm inlet/Outlet, 100NB flange, UV disenfection main header 150NB, complete all as specified.
Description all as per Serial Item No. 70 here-in-before but for online UV DISNFECTION PLANT of capacity 115000LPH, SS304, 3 Pass UV system 320 watt x 4 Lamp with 3 pass inter interconnecting with header chamber of diameter 254mm inlet/Outlet, 100NB flange, UV disenfection main header 150NB, complete all as specified.
Description all as per Serial Item No. 70 here-in-before but for online UV DISNFECTION PLANT of capacity 125000LPH, SS304, 3 Pass UV system 320 watt x 5 Lamp with 3 pass inter interconnecting with header chamber of diameter 254mm inlet/Outlet, 100NB flange, UV disenfection main header 150NB, complete all as specified.
Description all as per Serial Item No. 70 here-in-before but for online UV DISNFECTION PLANT of capacity 20000LPH, SS304, 1 Pass UV system 320 watt x 2 Lamp with inter interconnecting with header chamber of diameter 152mm inlet/Outlet, 65NB flange, complete all as specified.
Description all as per Serial Item No. 70 here-in-before but for online UV DISNFECTION PLANT of capacity 15000LPH, SS304, 1 Pass UV system 320 watt x 2 Lamp with inter interconnecting with header chamber of diameter 152mm inlet/Outlet, 65NB flange, complete all as specified.
Design, Supply, Install, test and commissioning of SCADA system capable of complete data monitoring ,data logging and control function suitable for main Pump House and other remote located Pump Houses at UC1 to UC10, ( Each P/H needs separate server and monitring system for operator) with and including following minimum configuration, complete all as specified and directed by Engineer -in- charge. (a) 02x Servers for Main and Hot standby mode with 21" TFT Monitors (b) 01x ISR/NMS Server with 52" LED Screen. (c) Blank (d) Blank (e) 02x Black and white printer (f) 01 x Laptop for maintenance (g) PLC panel for controlling of pumps with all its accesories (h) 10 KVA, Stand alone online, 3 phase input, single phase output UPS including 30 min backup with SMF 26AH batteries 32nos with battery stand to regulate supply of ups model No. au 3100 of APLAB / Consul/Neil.
(j) 24 10/100/1000 Base – T ports + 4 SFP ports web smart switch DGS -1210 series Hardware Specifications Switching Capacity: DGS -1210-20: 40Gbps – DGS-1210-28:56Gbps, DGS -1210-28P: 56Gbps, DGS-1210-52: 104Gbps Max. Forwarding rate DGS-1210-20:29.8Mbps, DGS-1210-28:41.7Mbps, DGS-1210-28P:41.7Mbps, DGS-1210-52:77.4Mbps DDR II FOR CPU: 128M BYTES Flash Memory:16M Bytes AC input 100-240 VAC, 50/60 Hz, internal universal power supply, Acoustic Value: DGS-1210-20/28:0db (Fan-less), DGS-1210-28P:52.2dB (3 smart Fan), DGS-1210-52:47.1dB (2 smart fan) Operation Temperature 0-50°C Storage Temperature 20-70°C Operation Humidity: 0%-95%RH Storage Humidity: 0%-95%RH
(k) 15km single mode media converter DFE-855 Fast Ethernet to Media converter Number of ports.1 RJ-45 100BASE -TX One SC fiber optic 62.5/125 micron multi-mode Transnission speed of ports 100mb on both port Dupex support Auto-sense full duplex on half duplex cable support 100BASE-TXT connection supports UTP cat.5 UTP cabling 100BASE-TXT connection supports Fiber optic 62.5/125 micron Multi mode cabling Standards compliance IEEE 802 100 BASE-TX/FX Fast Ethernet Protocol CSMA /CD, Topology,UTP/STP/Star Fiber point to point converter Power consumption 3.5Watts LED'S Power, TX/RX,Link full or half Operating Temprature- 10 degree to 55 Degree C ( 14 degree to 131 Degree) Humidity:-5% to 90% non condensing Classification : FCC Class A, CE mark,VCCI Class A, c-Tick
(l) LIU6 PORT Rack Mounted Unloded NLUFXXUXXR-XX Alluminium Base Material for base Mounting slim on unit mounting hight frot mounted cable saddle for jurnper management 2 fiber Spools bUILT IN 100 LIGHTS Buffer Adapter Removable Front and rear covers for better access to interior of LIU. (m) 1x12 Adaptor Panel-sc (n) 1x6 Adaptor Panel (o) 6 port blank Adaptor Panel. (p) PIGITAIL SC SM SIMPLEX LENGTH-1m Adaptor Panel. (q) Adaptor SC SM Panel. (q) PATCH CORD LC-SC DUPLEX LENGTH -3m, Duplex type NCB-SF09-LCSC3. (r) CAT6 UTP 24AWG PATCH CORD:2M,Plug 30U Snagless. (s) Supply and installed hi wall split units indoor/outdoor complete with cordless remote control AC unit and within built air ioniser and plasma filter for better indoor air quailty with minimum 5 star rating & driven single Phase of capacity of 2.0 TR including MS bracket for mounting of suitable capacity incl sub main wiring with metal clad swith and sockets – 10Nos.
(t) Provision of chemical dosing system plunger type suitable to inject upto 25 LPH comprising dosing pump coupled with 3 phase electric motor of capacity 0.50HP 1440RPM, assembly with agitator in one motor, agitator with SS sweep blade duly FRP coated, FRP tank 150 Ltrs capacity, complete unit mounted on heavy duty MS fabricated frame duly painted with anticorrosive paint along with FR PVC round sheathed copper conductor flexible cable of size 4Core x 4Sqmm, 1100Volts, IS694 with chemical grade PVC NRV with all fittings at UC No. 07 & 08 PH - 02Nos (u) Provision of chemical dosing system plunger type suitable to inject upto 50 LPH comprising dosing pump coupled with 3 phase electric motor of capacity 0.50HP 1440RPM, assembly with agitator in one motor, agitator with SS sweep blade duly FRP coated, FRP tank 150 Ltrs capacity, complete unit mounted on heavy duty MS fabricated frame duly painted with anticorrosive paint along with FR PVC round sheathed copper conductor flexible cable of size 4Core x 4Sqmm, 1100Volts, IS694 with chemical grade PVC NRV with all fittings at UC No. 01 to 06, 09 & 10 PH and MRS PHs- 09Nos
S&F 15mm dia 2 in 1 Bib cock, fancy type, twin elbow valve faucet wall mounted type, with and including SS health faucet & jet spray with SS flexible tube & hook, complete all as specified and as directed. Make: Cat No. F-330004 for Bib cock and F-160023 for Health Faucet of Hindware or equivalent in makes given here-in-after.
Supply, laying, testing and commissioning of Ductile Iron pressure pipe of 150mm bore with flanged type ends jointed with rubber or fibre board gasket and confirming to IS-8329:2000, class K-9, PN-10 rating, with pipe lining inside with cement mortar (CML) outside with bituminous coating all as per Annx `C' of IS-8329, laid in trenches / floor, complete all as specified and as directed. Note: 1. Necessary earth work will be measured and paid separately. 2. Necessary fittings will be measured and paid separately
S&F Cast Iron Venture meter of 80mm dia, complete all as specified.
S&F Cast Iron Venture meter of 150mm dia, complete all as specified.
M&L for Cutting & Chipping of laitance concrete in piles above cut off level upto a maximum of 1m from cut of level and disposal to distance of exc. 50m but n. exc. 250m and depositing where directed by Engineer-in-Charge.
M&L for Drilling or boring for 500mm nominal dia. bored cast-in-situ piles through any or all types of strata i.e soft/loose soil, stiff clay, gravel, cobble stone, compact moorum, soft conglomerate or loose boulders, disintegrated rock, weathered rocks etc., (except hard rock for socketing depth) upto top of socketing depth/founding depth by adopting suitable method with perennial water and disposal of drilling/bored materials outside MD land as directed, complete all as specified and as directed.
All as per Serial Item No. 83 here in before but for 500mm nominal dia through hard rock for founding depth minimum 2D (Where D is dia of pile), complete all as specified.
M&L for Drilling or boring for 600mm nominal dia. bored cast-in-situ piles through any or all types of strata i.e soft/loose soil, stiff clay, gravel, cobble stone, compact moorum, soft conglomerate or loose boulders, disintegrated rock, weathered rocks etc., (except hard rock for socketing depth) upto top of socketing depth/founding depth by adopting suitable method with perennial water and disposal of drilling/bored materials outside MD land as directed, complete all as specified and as directed.
All as per Serial Item No. 85 here in before but for 600mm nominal dia through hard rock for founding depth minimum 2D (Where D is dia of pile), complete all as specified.
M&L for Drilling or boring for 750mm nominal dia. bored cast-in-situ piles through any or all types of strata i.e soft/loose soil, stiff clay, gravel, cobble stone, compact moorum, soft conglomerate or loose boulders, disintegrated rock, weathered rocks etc., (except hard rock for socketing depth) upto top of socketing depth/founding depth by adopting suitable method with perennial water and disposal of drilling/bored materials outside MD land as directed, complete all as specified and as directed.
All as per Serial Item No. 87 here in before but for 750mm nominal dia through hard rock for founding depth minimum 2D (Where D is dia of pile), complete all as specified.
M&L for Drilling or boring for 800mm nominal dia. bored cast-in-situ piles through any or all types of strata i.e soft/loose soil, stiff clay, gravel, cobble stone, compact moorum, soft conglomerate or loose boulders, disintegrated rock, weathered rocks etc., (except hard rock for socketing depth) upto top of socketing depth/founding depth by adopting suitable method with perennial water and disposal of drilling/bored materials outside MD land as directed, complete all as specified and as directed.
All as per Serial Item No. 89 here in before but for 800mm nominal dia through hard rock for founding depth minimum 2D (Where D is dia of pile), complete all as specified. Notes for Item Nos. 83 to 90:- (i) The depth of boring for piles shall be measured from existing ground level to the approved founding level. (ii) It shall be ensured that the waste bentonite slurry/ drilled or bored material is pumped off from the premises to locations shown by GE to contractor at his own cost. (iii) All channels/tanks made for bentonite circulations shall be filled with approved moorum obtained by contractor at his cost after clearing all bentonite cakes. (iv) The contractor may use any approved method as approved by GE for boring without any extra cost to the Govt. The rates for boring of piles shall be inclusive of any method/ casing that may be used by the contractor for bored piles. Nothing extra shall be paid. (v) For the purpose of payment of boring/drilling, description of hard rock shall be as given in SSR Part-I specification. (vi) The rate quoted by the contractor shall be inclusive of the rates for the shifting and setting up of piling rig as many times as required.
Carrying out initial load tests on test pile of 500mm dia as per standard procedure laid down in IS-2911 by static load test method with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc. as specified and as directed by GE and submission of reports for 2.5 times of the design load in non-working areas in the vicinity of site, including the cost of new piles with specification as same as working pile with minimum depth of socketing into the hard rock 2D (Where D is dia of pile) depth, complete all as specified. Note: Load rquired for testing as per IS shall be arranged by the contractor and test pile shall be abondoned after testing.
Carrying out initial load tests on test pile of 600mm dia as per standard procedure laid down in IS-2911 by static load test method with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc. as specified and as directed by GE and submission of reports for 2.5 times of the design load in non-working areas in the vicinity of site, including the cost of new piles with specification as same as working pile with minimum depth of socketing into the hard rock 2D (Where D is dia of pile) depth, complete all as specified. Note: Load rquired for testing as per IS shall be arranged by the contractor and test pile shall be abondoned after testing.
Carrying out initial load tests on test pile of 750mm dia as per standard procedure laid down in IS-2911 by static load test method with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc. as specified and as directed by GE and submission of reports for 2.5 times of the design load in non-working areas in the vicinity of site, including the cost of new piles with specification as same as working pile with minimum depth of socketing into the hard rock 2D (Where D is dia of pile) depth, complete all as specified. Note: Load rquired for testing as per IS shall be arranged by the contractor and test pile shall be abondoned after testing.
Carrying out initial load tests on test pile of 800mm dia as per standard procedure laid down in IS-2911 by static load test method with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc. as specified and as directed by GE and submission of reports for 2.5 times of the design load in non-working areas in the vicinity of site, including the cost of new piles with specification as same as working pile with minimum depth of socketing into the hard rock 2D (Where D is dia of pile) depth, complete all as specified. Note: Load rquired for testing as per IS shall be arranged by the contractor and test pile shall be abondoned after testing.
Carrying out routine load test on 500mm dia pile (working pile) as per standard procedure given in IS-2911 (Part IV) by high strain dynamic load with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc and submission of reports for 1.5 times of the design load, complete all as specified and as directed.
Carrying out routine load test on 600mm dia pile (working pile) as per standard procedure given in IS-2911 (Part IV) by high strain dynamic load with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc and submission of reports for 1.5 times of the design load, complete all as specified and as directed.
Carrying out routine load test on 750mm dia pile (working pile) as per standard procedure given in IS-2911 (Part IV) by high strain dynamic load with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc and submission of reports for 1.5 times of the design load, complete all as specified and as directed.
Carrying out routine load test on 800mm dia pile (working pile) as per standard procedure given in IS-2911 (Part IV) by high strain dynamic load with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc and submission of reports for 1.5 times of the design load, complete all as specified and as directed.