| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.4 LAccepted-AOC 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L1 | Accepted-AOC BEING LOWEST BIDDER | |
| 2 | L2₹37.1 L+₹4.6 L (14.2%)Rejected-Finance 154 GANDHI MARKET AMBALA CANTT HARYANA 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Other than lowest Bidder |
Tender Value
₹42 L
EMD Value
₹84,000
Closing Date
18 Jan 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE UTILITY AMBALA
GE UTILITY AMBALA CANTT 133001
PREVENTIVE MAINTENANCE OF LT OH UG ELECTRIC NETWORK AND ALLIED WORKS OF MANEKSHAW ENCLAVE STAFF ROAD CW LINE AND FAFA QTRS AREA UNDER GE UTILITY AMBALA CANTT
2024_MES_689585_1
CA NO GE U AMB T 70 OF 2024-25
Open Tender
Civil Works
Item Wise
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹84,000
31 Jan 2025
20 Dec 2024
20 Jan 2025
20 Dec 2024
18 Jan 2025
4 Jan 2025
20 Dec 2024 - 27 Dec 2024
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes ,for under ground cable / erection of poles, stays, locating fault of LT cable and stay assembly etc not exceeding 10 square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed.
All as per Srl item No 1.00 here in before but depth exceeding 1.5 metre and not exceeding 3.0 metre.
Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed.
Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Material and labour for sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable) complete all as specified and directed.
Supply and lay bricks, common burnt clay, sub class "B', old size, laid in perpendicular direction to cable as cable protection complete all as specified and directed.
All as per Srl Item No 6.00 here in before but except bricks, all as specified and directed. Note:- Old bricks retrieved from Ser Item No 11.00 here in after shall be re-used.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique or manual boring and necessary machine including HDPE pipe of 50mm to 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
Supply and fix in replacement of light grade galvanised mild steel pipe 80 mm bore with all fittings, laid under roads, drain, paths, fixed to poles/walls with suitable mild steel clamps, bolts, nuts and washers complete all as specified and directed. Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule.
All as per Srl Item No 9.00 here-in-before but of size 50 mm bore.
Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, wall etc and locate the fault, rectify the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminum conductor heavy duty 1100 volts including connecting and testing for any size complete all as specified and directed. Note:- Excavation/earth work & sand cushioning, bricks and joint shall be measured & paid for separately.
Supply, laying, connecting & testing in replacement of XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 10 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall incl aluminium thimbles/lugs etc complate all as specified & directed . Note: (i) Earth work, sand, bricks removing, returning filling will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per Srl item No 12.00 here in before but for 16 Sqmm 4 core complete all as specified and directed.
All as per Srl item No 12.00 here in before but for 25 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 12.00 here in before but for 35 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 12.00 here in before but for 50 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 12.00 here in before but for 70 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 12.00 here in before but for 95 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 12.00 here in before but for 120 Sqmm 3.5 core complete all as specified and directed.
All as per Srl item No 12.00 here in before but for 150 Sqmm 3.5 core complete all as specified and directed.
Supply and fix in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 35-95 Sqmm complete all as specified & directed.
Supply and fix in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 120-150 Sqmm complete all as specified & directed.
Supply and fix in replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 35-95 Sqmm complete all as specified & directed. Note: The quoted rate shall include the earth work, RF and removal of soil etc.
Supply and fix in replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 120-150 Sqmm complete all as specified & directed. Note: The quoted rate shall include the earth work, RF and removal of soil etc.
Material and labour for spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locations complete all as specified & directed.
Taking down old unsv Prestressed Concrete LT pole and supply and erection of Prestressed Concrete LT pole 9.0 mtr long in true vertical position 102x172 mm at top and 102 x 279 mm at bottom class-10 incl providing cement base paint over one coat of red oxide primer and also providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip complete all as specified & directed. Note:- (i) Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Taking down old unsv Steel tubular LT pole and supply and erection of steel tubular swaged poles 9.0 mtr long complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31, providing synthetic enamel aluminium paint over one coat of red oxide primer and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr above the coping of pole starting with black strip complete all as specified & directed. Note:- (i) Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Supply and fixing in replacement of stay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 and as directed incl taking down old unsv stay assy complete all as specified & directed. Note- The quoted rate shall include the cost of loop type insulator, stay clamps, excavation, PCC, stay wire, stay bow, turn buckle, nuts etc. complete.
Material and labour for Plain cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation complete all as specified & directed.
Material and labour for PCC 1:3:6 type C1 using 20 mm graded stone aggregate for stay and coping for poles including necessary form work to exposed surfaces finished smooth and even complete all as specified & directed.
Material and labour for PCC 1:2:4 Type B-1 using 20 mm graded stone aggregate for coping of poles including necessary form work and finishing the exposed surface even and smooth with out using extra cement complete all as specified & directed.
Material & Labour for surface cleaning of LT steel tubular poles 9 mtrs long including removing rusted particles painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paint complete all as specified & directed. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the repairing of coping with cement / PCC
Material & Labour for surface cleaning of LT Prestressed Concrete pole 9 mtr long including painting with two coat of cement base paint also marking black & white strips alternatively 30 cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and repairing of and painting on coping with cement base white paint complete all as specified & directed. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall include the repairing of coping with cement / PCC
Material and labour in replacement of Loop insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mm x 140mm, clearance of hole 25.5 mm, complete all as specified & directed
Material and lobour in replacement for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm complete all as specified & directed.
Taking down old unserviceable ACSR conductor and material and labour for aluminium conductor steel reinforced (ACSR) conductor of size 6/1 x 2.59 (Weasel) and 6/1 x 2.11 (Squirrel) or other existing type conductor ISI marked for LT over head lines on poles including stretching, tightining of poles insulator with winding wire of suitable size with insulator/streching of ACSR conductor complete all as specified and directed.
Taking down old unserviceable cross-arms and material and labour for cross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
Supply only for loose filling in substations, under poles, under transformers of hard core broken to gauge not exc 63 mm broken stone/boulders incl leveling and spreading lime stone powder under stones complete all as specified & directed.
Material & Labour in replacement of steel nuts, bolts, washers of any size required at site complete all as specified & directed.
Material & Labour for prepering old painted steel surfaces of any description not otherwise described over 10 cm width or girth and applying one coat of synthetic enamel paint complete all as specified and directed.
Dismantling and taking down old u/s earthing of any type and Material & Labour for provision of earthing complete with galvanised earth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, burried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 25x4 mm GI strip earth lead by means of bolts, nuts, checks nuts and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GI protection pipe (light grade), funnel, wire mesh, cast iron cover and frame etc including testing on completion complete all as specified and directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2Ώ the earthing will be redone at no extra cost.
All as per Srl item No 41.00 here in before but for connected to galvanised earth lead wire of 4.0 mm dia by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn through 15 mm bore GI pipe medium grade for protection of GI earth lead wire including 20mm bore GI pipe medium grade for watering GI funnel complete all as specified & directed.
All as per Srl item No 41.00 but using copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead complete all as specified & directed.
Taking down any type of earthing but Material and labour Supply, installation, testing & commissioning of maintenance free chemical earthing system comprising 17 mm dia copper bonded rod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6 mm thickness with equal space either side, with 12 mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducing liquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation all as directed.
Supply and fixing in replacement of LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 5 line as per IS complete all as specified & directed
All as per Srl Item No 45.00 here in before but 4 line complete all as specified & directed
Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400 sqmm complete all as specified and directed.
Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 150-185 sqmm complete all as specified and directed.
Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-120 sqmm complete all as specified and directed.
Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 25-50 sqmm complete all as specified and directed.
Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 10-16 sqmm complete all as specified and directed.
Material & Labour for 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 Metre apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as specified and directed.
All as per item ser No 52.00 here in before but for 6 sqmm 2 core complete all as specified and directed.
All as per item ser No 52.00 here in before but for 4 sqmm 2 core complete all as specified and directed.
Re-stretching existing/retrieved ACSR conductor on LT /HTpole and binding conductor on insulator properly using new binding wire/jumper wire complete all as specified and directed. Note : (i) Each Run of line conductor shall be measured in Running Metre from pole to pole.
Material and labour in repairs of stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire complete all as specified and directed.
Material & Labour for repairing broken Door, Locking Arrangements, Hinges, etc. of LT Panel/ Feeder Pillar/ Pole Box, Indoor/ Outdoor type of any size, necessary welding, drilling as reqiured, Replacing Door, Locking Arrangements, Hinges, etc. if ordered, complete all as specified & directed.
Material & Labour for Cleaning, Scraping of Exposed Surfaces of LT Panel/ Feeder Pillar /Pole Box, Indoor/ Outdoor Type and applying One coat of Synthetic Enamel Paint (Paint & Shade as approved) with Spray Painting Machine including Writing MES No. and Machine No. with Black Paint, Letters 50mm High and 15mm Wide, complete all as specified & directed.
Material and Labour for shifting of heavy items / excavation / cleaning areas / cleaning site by providing crane/hydra / excavators /tractors/ trolley etc as required at site complete, all as specified and directed.
Repairing of existing unserviceable PCC coping of LT/HT pole by breaking completely and material and labour for PCC 1:2:4 type B1, (using 20mm graded crushed stone aggregate) of size 600X600X300mm including form work and applying two coats of white wash complete all as specified and directed.
Material & Labour for Chemical spray (DC 2.26 contact cleaner) in container of 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc complete all as specified and directed.
Taking down old unserviciable board and supply and fixing of Retro reflective sign board of size 600 x 750 sqmm made of ACP sheet of 3mm thick fixed on MS frame with legs of MS angle section 35mm X 35mm X 4mm grouted in PCC 1:3:6 type C-1, 750mm above the ground level and 600mm below the ground level. The background of board to be provided with radium red colour, letters and border with radium white retro reflective tape. Same description shall be mentioned on both sides of ACP sheet complete all as specified and directed. NOTE:- (i) Excavation, earth work, PCC, nuts, bolts, fastners, paint on MS frame and legs shall be included in quoted rates by contractor. (ii) The size of letters and description shall be all as per sample approved by Engr-in-Charge.
Supply, installing, testing & commissioning in replacement of factory fabricated outdoor type feeder pillar board of size 700X600X500 mm, outer shell made out of 3.15 mm thick CRCA sheet inter 60-70% area made up with perspex sheet of 3 mm thickness and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on door 01 no of pad lock of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coated painting after 7-tank pre treatement control & power wiring with suitable size of copper conductor along with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011 Part-1 and part -2 type test certificate with not less than IP-56 comprising of the following :- (a) MCCB 160 Amps TPN, 25 KA -01 No (b) Aluminium busbar of capacity busbar 3 No 250 Amp & 01 No 125 Amp with colour coated heat shrinkable sleeve and suitable hole for out going connection - Set of four. (c) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply -03 Nos (d) Digital Multifuction meter suitable to monitor Voltage, Amp, Frequency, kWh with suitable size of CTs -01 Set (e) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, sleeves, glands etc complete are included in quoted rates
Supply and fix in repairs Lockable Trip Push Button (LTPB) suitable for air circuit breakers of rating 630 Amps to 800 Amps all as per existing complete all as specified & directed.
Supply and fix in repairs Locking of ACB in Isolated position (LIP) suitable for air circuit breakers of rating 630 Amps to 800 Amps all as per existing complete all as specified & directed.
Supply and fix in repairs Racking Interlock suitable for air circuit breakers of rating 630 Amps to 800 Amps all as per existing complete all as specified & directed.
Supply and fix in repairs Door Interlock suitable for air circuit breakers of rating 630 Amps to 800 Amps all as per existing complete all as specified & directed.
Supply and fix in repairs Vertical Terminal Adaptors suitable for air circuit breakers of rating 630 to 800 Amps rated all as per existing complete all as specified & directed.
Supply and fix in repairs Under Voltage Release suitable for air circuit breakers of rating 630 Amps to 800 Amps all as per existing complete all as specified & directed.
Supply and fix in repairs Earth Fault Release suitable for air circuit breakers of rating 630 Amps to 800 Amps all as per existing complete all as specified & directed.
Supply and fix in repairs Microprocessor based release suitable for air circuit breakers of rating 630 Amps to 800 Amps all as per existing complete all as specified & directed.
Supply and fix On-grid Solar inverter outdoor type, IP-65 protection, Minimum 60 KW capacity, AC nominal rating (array to inverter ratio 1:1), 3 P, 50 HZ, including making fresh connection as per existing complete all as per site requirement & as directed . Make: ABB Model : Solar inverter Trio-TM-60.0-480 / Microtek / Su-Kam / UTL Solar.
Material & Labour in replacement of MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type with thermal magnetic release complete all as specified and directed. Make - Havells/Indoasian/ C&S/ L&T
Material & Labour in replacement of MCCB TPN 250 Amps, 415 Volts, 25 KA, 4 pole, Ics=100% Icu, overload adjustable short circuit adjustable type complete all as specified and directed. Make - Havells/Indoasian/ C & S/ L & T
Material & Labour in replacement of MCCB TPN 200 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type complete all as specified and directed. Make - Havells/Indoasian/ C & S/ L & T
Supply & fix in replacement of MCCB TPN 100/125 Amps, 415 Volts, 16/18 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type complete all as specified and directed. Make-Havells/Indoasian/ C & S/ L & T
Supply and fixing in replacement of off load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed. Make-Havells/Indoasian/ C & S/ L & T
All as per item ser No 77.00 here in before but for 200 Amps capacity complete all as specified and directed. Make-Havells/Indoasian/ C&S/ L&T.
Supply & Fixing in replacement of extended spreaders link should be installed both side with exisitng/new MCCBs 4P/3P of any capacity with existing LT panels complete all as specified and directed.
Taking down old unserviciable earth indicator board of any type and size but supply and fixing of Retro reflective sign board of size 200 x 300 mm made of ACP sheet of 3 mm thick fixed on MS frame with legs of MS angle section 25mm X 25mm X 4 mm grouted in PCC 1:3:6 type C-1, 300 mm above the ground level and 100 mm below the ground level. The background of board to be provided with radium red colour, letters and border with radium white retro reflective tape. Same description shall be mentioned on both sides of ACP sheet complete all as specified and directed. NOTE:- (i) Excavation, earth work, PCC, nuts, bolts, fastners, paint on MS frame and legs shall be included in quoted rates by contractor. (ii) The size of letters and description shall be all as per sample approved by Engr-in-Charge.
Taking down unsv chamber cover of any type and size but Material and labour for earthing chamber cover of size 0.45 x 0.45x .04 m or size as per site with RCC 1:2:4 type B1 with 20 mm graded stone complete all as specified & directed.
Material and labour in replacement of broken earth pit of size 300x300x300 mm made of PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia TMT bars @ 100 mm centre to centre both ways with handle made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers as required at site with testing result complete all as specified and directed.
Supply, installing, testing & commissioning in replacement of outdoor type cubical panel board of size 1.2mX1.2mX.5m, outer shell made out of 3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able with arrangement of pad locking on both doors incl 2 no. of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, incl Copper bus bar of 400 A , tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011 Part-1 and part -2 type test certificate with not less than IP-65 and breaking capacity 65 KA (Make of MCCB- Havells/Indoasian/ C & S/ L & T) comprising of the following :- (a) MCCB 250 Amps, Amps 4 pole 415 Volts AC with adj thermal & magnetic 36 KA, Ics=100%, Icu - 01 No (Incoming) (b) MCCB 100 Amp, 415 volt, 4 pole, breaking capacity 25 KA , (Outgoing)-02 Nos. (c) MCCB 63 Amp, 415 volt, 4 pole, breaking capacity 25 KA , (Outgoing)-02 Nos (d) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply -03 Nos (e) Digital Multifuction meter suitable to monitor Voltage, Amp, Frequency, kWh with suitable size of CTs -01 Set (f) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, cable glands etc complete are included in quoted rates complete all as specified & directed.
Supply only chemical (Round up) for remove unwanted vegitation/grass at various locations complete all as specified and directed.
Taking down old/ unsv test point of any type and size but Supply and fixing in repair test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed.
Supply and recharge earthing pit common salt commercial type complete all as specified and directed.
Trimming of Tree branches around the sub station, solar plant area or falls into OH lines of HT/LT & minimum clearance of 3 Mtr from branches, proper shutdown will be taken and maintained in the register including any type of T & P required complete all as specified & directed.
Rectification of complaints under GE (U) Ambala area of security light, street light, hanger light, flood light and high mast lights and allied works by attendng daily complaints including Sunday and other holidays for round the clock and making the same serviceable in all respects alongwith replacement of any major part but including small length of cable (not more than 20 mtr), adhesive tape and other connected minor accessories shall also include to visual inspection of OH lines, Earth Resistance of street poles etc. Quoted rate also include excavation of faulty cable/all type lights are making seviceable with accessories of all nature like No light, faulty insulator, broken conductor & cable fault, burnt out MCCB`s, MCBs, isolators, switch fuses, service cables etc complete all as directed to the entire satisfacation of Engineer-in-charge.
Note for Ser item No 88.00 :- (i) Any complaint left unattended by the electrician will be communicated to the JE in-charge /AGE E/M with reason. No charge will be paid for the per complaint till the complaint is resolved. (ii) New material /stores provided for completing the job shall be measured and paid for separately under relevant items of BOQ. (iii) Contractor shall provide all type of T&P of street lights network, bamboo ladder with safety gloves to each electrician for attending the S/L complaints. (iv) Contractor shall provide the complaint register 200 pages – 3 No, complaint book with 100 slips- 5 No. Booklets serially numbered in triplicate. (v) Contractor will provide 01 No. Experienced Electrician having minimum 5 years experience ( 01x one shifts per day) and 01 No. Helper having minimum 2 years experience ( 01 x one shifts per day) including Sundays and Holidays to attend S/L Complaints. (vi) The Contractor will provide insurance cover of minimum Rs 5 lakh per head under IE Rules 2003 and Minimum wages Act. (vii) The Electrician and helper will be interviewed by JE E/M /Engr-in-charge for verification of experience, character and sound mind and body.
Material and labour for Detecting of fault in cable HT/LT with fault locator equipment which is capable to supply as per cable of HT/LT (11 KV/430 Volts) serviceable to cable including Straight through joint of size 70-300 Sqmm complete all as specified & directed. Note:- (a) The HT fault which is detected through cable fault locator will only be paid under this item including transportation charges deemed to be included in the quoted rate. (b) Charge of cable fault locator and DG set, transportation charge deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will levied Rs. 500/- per hour.
Material and labour in replacement of Insulation cover for overhead conductor a medium voltage wrap around line cover that provides retrofit insulation for overhead conductors to prevent electrical outages caused by trees or wildlife coming into the contact with distribution lines.It is manufactured from high quality non tracking polyolefin material. Insulation cover is designed to insulate existing bare lines without any extra cost. Installation is easy by using the split insulation tube tool which remains stationary at single location compete all as specified and directed. Note: (i) The quoted rate shall be included of all types accessaries which used to insulation cover for overhead conductor all as directed by Engr-in-Charge.
Supply and fixing in replacement of rolled mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment Fe-290 (Gde E- 165) for existing LT panel doors/gates complete all as specified and directed.
Supply and fix in replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled red, with letters, figures and conventional skull and bones in signal white colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed.
Supply and fix in replacement of MCB DP 16-40 Amps, 240 volt,10 KA 'B' curve including all accessories complete all as specified and directed.
Surface Dressing/Cleaning of various 11 KV sub-stations free from vegetation of any type including trimming of tree branches, bushes, creepers, etc. complete all as specified & directed. Note: The frequency of surface dressing shall not be less than 2 months
Note:- Amount of credit of Rs. 103803.00 for retrieved materials is mentioned in Schedule of Credit of tender documents in pdf form which will be deducted offline while acceptance of tender.
Esha Engineers (BID ID -3217714)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .