Loading…
Loading…
Tender Value
₹9.1 L
EMD Value
₹22,839
Closing Date
16 Jun 2026, 6:00 pm6d left
Assisstant Executive Engineer
Office of the Assisstant Executive Engineer PWD Electrical Subdivision Thalassery
GENERAL-Animal Husbandry Department Regional Disease Diagnostic Lab Kannur. SITC of Generator and Airconditioners at First Floor-General Electrical Work
2026_PWD_837451_3
PWD/BLDG/TR/10520/2024_6_1_1/1
Open Tender
Electrical Works
90 days
KANNUR
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,015
₹22,839
8 Jun 2026
8 Jun 2026
19 Jun 2026
8 Jun 2026
16 Jun 2026
8 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1SITC of Air conditioner at RDDL First Floor | ||||||
| 1.001 | OD198300/2024-2025:SITC of Inverter type wall mounting split Air conditioner unit of the following ratings conforming to relevant IS suitable for operating on 230V, 50Hz single phase AC supply ,filled with R-410 A/R32 refrigerant gas, full copper condenser ,high energy efficient, RoHS complaint, capable of performing functions like cooling, dehumidifying ,air circulating ,filtering etc of following capacity including refrigerant copper piping 3m with insulation, control cable up to 5m,3m drain pipe, Condenser stant, microprocessor control with cordless remote control ,base frame etc. with comprehensive maintenance contract upto the end of 36 months from date commissioning including periodical services, gas topping etc. complete . 1.5 Tr single phase 3 Star rated inverter type Split Ac unit .Make Thosiba/Daikin/Carrier/Lloyd | - | each | - | - | BI01010001010000000000000515BI0100001114 |
| 1.002 | OD62243/2024-2025:Supply and Fixing of 4 KVA voltage stabilizer for split type A/C unit with voltage range of 175-275V and out put range of 210 - 240V (V-Guard or its equivalent) | - | each | - | - | BI01010001010000000000000515BI0100001115 |
| 1.003 | 90.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator | - | each | - | - | BI01010001010000000000000515BI0100001116 |
| 2SITC of Generator and additional electrification to Rabies Lab | ||||||
| 2.001 | OD232956/2024-2025:Supply, conveyance, Installation, testing & commissioning of 10 KVA Diesel
Generator set with integral acoustic enclosure as per CPCB IV+norms with standared
acessories as per technical details given below. 1. Engine : a) Make of Engine -
Leyland/cummins/caterpillar/volvo/kirloskar b) Type of Engine - Diesel Engine c)
No. of Cylinders - As per manufactures standards. d) Method of Cooling - Water
cooled with radiator. e) .natural aspiration f) Design - Suitable
for generating set operation 2.Standard accessories with Diesel Engine a) Fly wheel to
suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided
with fan guard. e) Fuel Pump f)) g) Fuel filter h) Lubricating oil filter i) in built
Exhaust silencer j) EGR system k) Battery Charger/Generator 3. Engine Instrument
Panel with the following items a) Starting switch with key or button 1 b) Lubricating
oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter e)
Battery charging Ammeter 4. Safety Controls for Engine a) Trip for low lubricating
oil pressure b) Trip for high water temperature. 6. Brushless Alternator a) Make -
Kirloskar/Crompton/Greaves/Stanford b) Type - Self exited and self regulated. c)
Capacity - 10KVA/7.5 KW @ 0.8PF d) System of Voltage - 3 phase, 415 V, e)
Frequency - 50 Hz f) Insulation - Class F/H The Alternator should confirm to IS
4722. Operation and service manual, spares and tools shall be provided. 7. Fuel Tank
Suitable size built in type integrated with the acoustic enclosure Fuel connection shall
be done as per standards 8. Battery Suitable size built in type integrated battery with
leads and terminals of appropriate AH capacity as per Manufactures requirement.
Automatic Battery charger Solid state phase indication lamp for supply ON/OFF with
HRC protection. standard control panel with 12V Batteries.standard control panel as
per kerala Electrical Inspectorate requirements, with suitable size MCCB and
accessories such as Multi function meter and Energy meter etc. Complete | - | each | - | - | BI01010001010000000000000515BI0100001118 |
| 2.002 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. | - | cum | - | - | BI01010001010000000000000515BI0100001119 |
| 2.003 | 14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required. | - | cum | - | - | BI01010001010000000000000515BI0100001120 |
| 2.004 | 14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels. | - | cum | - | - | BI01010001010000000000000515BI0100001121 |
| 2.005 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels | - | sqm | - | - | BI01010001010000000000000515BI0100001122 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.04 MB
specificconditionNEW.pdf
Tender Documents • 0.34 MB
BOQ_1444601.xls
BOQ • 0.33 MB
MOM.pdf
Tender Documents • 0.19 MB
viewnit.pdf
Tender Documents • 0.02 MB
viewsbd.pdf
Tender Documents • 1.63 MB
Download all tender documents and submit your bid