| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.4 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹32.3 L+₹7.9 L (32.3%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹33.5 L+₹9.0 L (37.0%)Rejected-Finance | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹33.5 L+₹9.1 L (37.1%)Rejected-Finance | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹40.7 L+₹16.3 L (66.6%)Rejected-Finance DOOR NO 43 2 BESIDES VIZAG DEFENCE ACADEMY 104 AREA KAPPARADA VISAKHAPATNAM 530013 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530013 | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
17 Nov 2020, 6:00 pmClosed
GE I DM
Naval Dockyard Visakhapatnam 530014
REPAIR, MAINTENANCE, REPLACEMENT OF 11 KV UG CABLE, JOINTING KITS UNDER CDS I AND CERTAIN NEAR BY MAINTENANCE SUBSTATIONS AND OTHER MISC WORKS AT ND (V)
2020_MES_390237_1
SSGE/8338/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Naval Dockyard Visakhapatnam
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE I DM
₹78,000
Yes
4 May 2021
27 Oct 2020
23 Nov 2020
27 Oct 2020
17 Nov 2020
10 Nov 2020
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft loose soil for cable work or from above cable duct complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft disintegrated rock (considered for road cutting) complete all as specified and as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed.
Removing of excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
Material & labour for dry sand cushioning for under ground cable provided with layer and sand 8 cm deep before laying the cable and 15cm after laying the cable complete all as specified and as directed.
Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mm x 180mm x 40mm complete all as specified and as directed.
Material & labour for PCC 1:3:6, type-C 2, using 40mm graded aggregrate for repair to path / drain / road against damege due to excavation / laying of cable complete all as specified and as directed.
Supplying & laying in trenches or in duct or passing through pipe XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, overall PVC sheathed electric power cables (heavy duty) with aluminium conductor, 11000 volts grade (Earthed) cross sectional area 185 sq. mm 3 core including dismantling / taking down unserviceable one complete all as specified and directed.
All as per item No 8.00 above but of size 240 sq.mm 3 core including dismantling / taking down unserviceable one complete all as specified and directed.
All as per item No 8.00 above but of size 300 sq.mm 3 core including dismantling / taking down unserviceable one complete all as specified and directed.
All as per item No 8.00 above but of size 400 sq. mm 3 core including dismentling / taking down unserviceable one complete all as specified and directed.
Dismantling taking out HT/LT Cable from cable duct of substations for realingnment of cable and relaying with proper alingnment for the cable of size 3 core, 185 sqmm, 11000 volts grade complete all as specified and as directed. Note:- (i) Each cable shall be measured separately. (ii) Steel cable rack shall be measured separately as supply and fix
All as per item No 12.00 above but for cable sizes 240sqmm
All as per item No 12.00 above but for cable sizes 300 sqmm
All as per item No 12.00 above but for cable sizes 400sqmm
Material & labour for finding of cable fault of UG 11000 volts grade cable inside trench (under soil / drain/ PCC/ Road/ Trench ) by disconnecting both cable ends, using insulation tester, cable path/fault finder and rectification complete by necessary excavation, cutting at fault position, fixing of straight through heat shrink joint, for cable sizes 150 sqmm to 400 sqmm, 3 core, 11000 volts grade or replacement of heat shrink indoor cable joint kit of size 150 sqmm to 400 sqmm, 3 core and reconnection of both cable end to original position after complete satisfactory insulation test, fixing with old or required new nuts-bolts-washers complete with testing all as specified and directed Note:- (a) Items required for rectification such as heat shrink indoor cable joint kit / heat shrink straight through joints / heat shrink sleeves and earth work shall be measured separately as material and labour . (b) required aluminium cable lugs and nuts-bolts-washers shall be inclusive of quoted rate. (c) Contractor shall bring necessary testing equipment and rate shall be inclusive of quoted rate.
Material & labour for cleaning of HT indoor cable kit at VCB end after opening VCB panel back side cable cover and bottom cable entry plate after disconneting all cable end from busbar/CT, taking out from VCB cable chamber, checking for serviceability, cleaning & decarbonising complete cable kit and aluminium cable lugs using CTC and refixing the same to original position, with new or old nuts, bolts & washers and making cable entry point totally sealed with putty complete all as specified and as directed.. Note:- Required CTC, new nuts, bolts, washers shall be inclusive of quoted rate. Serviceable cable ends will only be measured
Supply & Fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 150 sqmm to 185 sqmm after opening VCB panel back side cable cover and bottom cable entry plate after disconneting unsv cable kit from busbar/CT, taking out from VCB cable chamber and fixing the same to original position, with new or old nuts, bolts & washers, bottom plate, back cover and making cable entry point totally sealed with putty complete complete all as specified and as directed.
All as per item No 18.00 above (indoor termination) but for cable of size 240sqmm to 300 sqmm including dismantling / taking down unserviceable one complete all as specified and directed.
All as per item No 18.00 above (indoor termination) but for cable of size 400 sqmm including dismantling / taking down unserviceable one complete all as specified and directed.
Supply & Fix Cable jointing kit for 11 KV (Earthed) grade cable for out-door termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm after disconneting unsv cable kit from busbar at strcture, taking out carefully after openinf clamp at structure to GL and fixing the same to original position, with new or old nuts, bolts & washers, clamp at structure complete all as specified and as directed.
Supply & Fix Cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 150 sqmm to 185 sqmm including dismantling / taking down unserviceable one complete all as specified and directed.
All as per item No 22.00 above (straight through heat shrink type joint) but for cable of size 240sqmm to 400 sqmm incl dismantling / taking down unserviceable one complete all as specified and directed.
Supply & laying GI tubing 100mm bore medium grade for cable protection under road crossing including dismantling taking down unserviceable one complete all as specified and directed.
Supply & fixing tripping coil 110 V DC to Schneider make 11KV VCB including necessary connection testing complete all as specified and as directed.
Supply & fixing closing coil assembly 110 V DC to Schneider make 11KV VCB incl necessary connection testing complete incl dismantling taking down unsv one all as specified and directed.
Supply & fix space heater, 230V, 100 watt inside cable chamber including necessary connection, testing complete all as specified and as directed.
Supply & fix including dismantling taking out unserviceable thermostat for space heater For 800A to 1600A Schneider make 11 KV VCB.
Supply & fix single (Read-Blue) phase busbar spout suitable for 800 Amps to 1250 Amps VCB make Schneider only Model No MEP-39-32185 complete all as specified and as directed
Supply & fix single (Y) phase busbar suitable spout for 800 Amps to 1250 Amps VCB make Schneider only Model No MEP-39-32186 complete all as specified and as directed
Supply & fix single (Read-Blue) phase busbar spout suitable for 1600 Amps to 2000 Amps VCB make Schneider only Model No MEP-39-A0051301complete all as specified and as directed
Supply & fix single (Y) phase busbar spout suitable for 1600 Amps to 2000 Amps VCB make Schneider only Model No MEP-39-A0051401 complete all as specified and as directed
Supply & fix Schneider Micom P-127 protection relay, 110V, 5A, type-BAOZ112Ca1 to Schneider make 11KV VCB incl necessary connection testing complete including dismantling taking down unsv one complete all as specified and as directed.
Supply & fix incl dismantling taking out unserviceable vacuum interrupter of suitable for VCB of capacity 2500 Amps complete all as specified and as directed.
Supply & fix CT Spout suitable for VCB 800 to 1200 Amps 25 Ka chamber insulating bus support apoxy insulator of dia 95mm and 125mm length complete all as specified and as directed
Supply & fix CT Spout suitable for VCB 1600 to 2000 Amps 25 Ka chamber insulating bus support apoxy insulator of dia 95mm and 125mm complete all as specified and as directed
Supply & fix including dismantling taking out unserviceable Resin Cast CT dual core, CT racio- 100/50/5A-5A For 800A to 2500A Schneider make 11 KV VCB.
Supply & fix including dismantling taking out unserviceable Resin Cast CT dual core, CT racio- 800-400/5A-5A For 800A to 2500A Schneider make 11 KV VCB. Make-Kappa/Esun/Pragati
Supply & fix including dismantling taking out unserviceable Resin Cast CT dual core, CT racio- 600/300/5A-5A For 800A to 2500A Schneider make 11 KV VCB.
Supply & fix including dismantling taking out unserviceable Buffer (For Opening Spring ) For 800A to 1600A Schneider make 11 KV VCB.
Supply & fix including dismantling taking out unserviceable Buffer (For Closing Spring ) For 800A to 1600A Schneider make 11 KV VCB.
Supply & fix Dirve Beam suitablke for 11 KV VCB 800 to 2000 Amps make Scneider only Model No MSM3950118600FN
ANANDA PROFILES PVT LTD
aswitha engineering works
GVS ASSOCIATES
Mavee Syndicate
koneru enterprises
SV CONSTRUCTION
Raghavendra Constructions
SATYAMEGHA ENGINEERS
M/s SS Engineering Enterprises
S A R CONSTRUCTIONS
AYYAPPA CONSTRUCTIONS
MURALI KRISHNA ASSOCIATES
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .