Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.5 LAccepted-AOC | L1 | Accepted-AOC lowest tenderer | |
| 2 | L2₹27.0 L+₹2.7 L (11.0%)Rejected-Finance | L2 | Rejected-Finance other than lowest tender | |
| 3 | L3₹27.7 L+₹3.4 L (14.2%)Rejected-Finance | L3 | Rejected-Finance other than lowest tender | |
| 4 | L4₹32.4 L+₹8.1 L (33.5%)Rejected-Finance | L4 | Rejected-Finance other than lowest tender |
Tender Value
₹37 L
EMD Value
₹74,000
Closing Date
23 Jun 2022, 6:00 pmClosed
GE NS KOCHI
Military Engineer Services Garrison Engineer (Naval Services) Kataribagh, Naval Base Post Kochi 682004.
REPAIR / MAINTENANCE OF UG CABLE , EARTHING, JUNCTION BOXES AND PANELS AND STREET LIGHTS SYSTEM AT KATARIBAGH AREA AND REPAIR / MAINTENANCE OF CERTAIN ELECTRICAL INSTALLATION AND OFFICES OF GE (NS) KOCHI
2022_MES_527304_1
8917/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
KOCHI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE NS KOCHI
₹74,000
Yes
8 Aug 2022
30 May 2022
25 Jun 2022
30 May 2022
23 Jun 2022
10 Jun 2022
30 May 2022 - 9 Jun 2022
Amount
Taking down existing street light/flood light/ solar light fittings carefully (any capacity, any type) from pole 9/11 metre or building carrying out necessary repairing at E/M yard and refixing into the existing location including replacement of unserviceable/defective spare parts i.e.(LED fitting/drivers) and removing existing green busses, tree small Branches complete all as specified and directed. Notes:- (i) Spare parts shall be Measured under supply only item expect minor spare parts such as screws, nuts, bolts, washers etc shall deemed to be included in unit rate quoted. (ii) Tools, ladder, vehicle required to carry out the work shall be provided by the contractor. (iii) Contractor shall ensure the safety of the workers employed at his own risk. (iv) Contractor shall provided skilled ITI Electrician and produces the ITI Certificate for verification before commencement of work.
Taking down existing garden light fittings carefully (any type) of post top lantern, carrying out necessary repairing at site and refixing into the existing location including replacement of unserviceable/defective spare parts (such as lamp holder etc) cleaning of acrylic cover with detergent and replacement of internal wiring with two runs of PVC insulated 1.5 Sqmm copper conductor cable from fittings to connector block and testing after refixing at site complete all as specified and directed. . Notes:- (i) New spare parts retrofit holder, LED bulb shall be measured under supply only item (ii) Tools, ladder, vehicle required to carry out the work shall be provided by the contractor. (iii) Contractor shall ensure the safety of the workers employed at his own risk.
Taking down in Repair to high mast light 15/12 metre height complete down the assembly and check the all light fitting and Replacement of the unserviceable parts (LED Drive) and other materials found rusted Changed with New spares and clean all the fittings make serviceable all as directed. Notes:- Spare parts shall be measured and paid separately under supply only items, expect minor spares parts such as screws, nuts ,bolts, washers, etc shall deemed to be included in unit quoted rate.
Supply and laying XLPE insulated PVC sheathed ,armoured, heavy duty aluminium conductors electric cable 1100 volts grade of size 10 Sqmm 2 Core in duct/floor/wall with provision of saddle and lugs etc including taking down of old one complete all as specified and as directed.
Ditto All as per Sl Item No 4, but cable grade of size 10 Sqmm 4 Core.
Ditto All as per Sl Item No 4, but cable grade of size 16 Sqmm 4 Core.
Ditto All as per Sl Item No 4, but cable grade of size 25 Sqmm 3.5 Core.
Ditto All as per Sl Item No 4, but cable grade of size 35 Sqmm 3.5 Core.
Ditto All as per Sl Item No 4, but cable grade of size 50 Sqmm 3.5 Core.
Ditto All as per Sl Item No 4, but cable grade of size 70 Sqmm 3.5 Core.
Ditto All as per Sl Item No 4, but cable grade of size 95 Sqmm 3.5 Core.
Ditto All as per Sl Item No 4, but cable grade of size 120 Sqmm 3.5 Core.
Ditto All as per Sl Item No 4, but cable grade of size 150 Sqmm 3.5 Core.
Ditto All as per Sl Item No 4, but cable grade of size 185 Sqmm 3.5 Core.
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth and getting out in soft/loose soil for laying of cable all as specified and directed
Material and labour for sand cushioning for underground cables complete all as specified and directed (Note: for the measurement purpose only punned thickness shall be measured and paid)
Supply and laying in replacement of un-reinforced precast concrete cable cover, class, LV, Type I as per IS -5820 with flat size 250X150X40 mm laid dry in trenches over underground cables complete all as specified and directed.
Returning and filling of soil including spreading leveling watering and well ramming in layers not exceeding 25cm in hard /loose soil complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed.
Cutting into existing bituminous carpet road/PCC hard standing up to a depth of 30cm for laying of UG cable/GI Pipe including making good the disturbed surfaces to match with the existing complete all as specified and directed.
Supply and fixing of GI bracket for street light fitting made out 40mm dia medium grade pipe bend to 120 degree angle shape ,drilled holes etc 1.5 m long with clamps, nuts, bolts etc and taking down old unserviceable complete all as specified and directed.
Supply and fix in repair LED street light fittings 1x 60 Watt pressure with die Cast aluminium housing heat resistant toughened glass with frame with IP 66 protection including taking down old unserviceable light fitting complete all as specified and directed.
Ditto All as per Sl Item No 22, but LED street light fittings 1x 90 Watt.
Supply and fix in repair LED Flood light fittings 1x 50 Watt RGB pressure with die Cast aluminium housing heat resistant toughened glass with frame with IP 66 protection including taking down old unserviceable light fitting complete all as specified and directed.
Supply and fix in repair LED Flood light fittings 1x 70 Watt pressure with die Cast aluminium housing heat resistant toughened glass with frame with IP 66 Protection including taking down old unserviceable light fitting complete all as specified and directed.
Supply, fixing and testing of LED Flood light complete with toughened glass including LED bulb and all standard accessories as per design of manufacture suitable for IP-66 degree of protection and of 100 Watt capacity including taking down old unserviceable light fitting complete all as specified and directed.
Supply fixing and testing of LED Flood light complete with toughened glass including LED bulb and all standard accessories as per design of manufacture suitable for IP-66 degree of protection and of 200 Watt capacity including taking down old unserviceable light fitting complete all as specified and directed.
Supply and fix in replacement LED post top lantern warm/cool in colour die-cast aluminium spigot for mounting LED driver and spun aluminium canopy which is painted white inside, epoxy powder coated matt black finish after phosphochromate treatment light source of high efficiency long life LED module with SMD LED package mounted on MCP CB and viewing angle of 116 degree suitable for mounting with OD of 70mm maximum with 3 Nos hexagonal screw etc of capacity 15 Watts WH/WW including taking down old unserviceable light fitting complete all as specified and directed.
Supply and fix in replacement LED post top lantern warm/cool in colour die-cast aluminium spigot for mounting LED driver and spun aluminium canopy which is painted white inside, epoxy powder coated matt black finish after phosphochromate treatment light source of high efficiency long life LED module with SMD LED package mounted on MCP CB and viewing angle of 116 degree suitable for mounting with OD of 70mm maximum with 3 Nos hexagonal screw etc of capacity 25 Watts WH/WW including taking down old unserviceable light fitting complete all as specified and directed.
Supply only 1x60 Watt LED Street light driver75 Watt complete all as specified and directed.
Supply only 1x50/45 Watt LED Street light driver 50/45 Watt complete all as specified and directed
Supply only LED 18 Watt classic/thread type bulb in WW/WH colour Complete all as specified and as directed
Supply and fix in replace white colour Doom any size for Garden light fitting complete including taking down old unserviceable light fitting complete all as specified and directed
Material and labour for painting to steel tubular pole of any height, size with two coats of aluminium paint including preparation of surface, marking pole number as existing size of 50mm height in black colour with yellow back ground in round shape of dia maximum up to 150mm all as per the direction of Engineer In Charge.
Material and labour for Cement Based painting to Concrete pole of height 7 metre marking pole number as existing size of 50mm height in black colour with yellow back ground in round shape of dia maximum up to 150mm all as per the direction by the Engineer-in-charge
Material and labour for wiring with two run of PVC (FR) insulated multistranded copper conductor cable of 1.5 sqmm drawing through PVC conduits with continuous earth wire PVC (FR) insulated cable of size 1.5 sq mm connected to earth including all conduit accessories complete all as directed. Note: Two run of sub main wire, one run of earth wire and one run of PVC conduit pipe measured as one unit.
Supply and fix in repair junction box made of thermoplastic of size 126x228x111mm with IP 67 protection including cable connector and MCB brackets with suitable size clamps fixing for pole/ in PCC foundation including take down old unserviceable fitting complete all as directed.
Taking down old rusted unserviceable Garden light fitting pipe any size, Removing existing location and refixed with 40mm GI pipe Medium grade 3 metre long repair to existing PCC foundation size 30x30x45 cm by using PCC 1:2:4 type B1 (using 20m graded stone aggregates) as in coping, connected Existing cable to the Junction Box, Garden light fitting and make serviceable complete all as directed. (Note: Earth work / PCC work shall deem to be included in unit rate quoted).
Material & Labour for GI tubing medium grade (ISI marked) with all fitting /accessories for protection of cable on pole/wall and under road crossing including clamps, nut, bolt etc of size 40 mm dia including take down old unserviceable tubing complete all as specified and as directed.
Ditto All as per Sl item No 39, but tube of size 80 mm dia.
Supply and fix post top lantern mounting pole 60mm OD made up of high grade unbreakable polycarbonate material suitable for retrofit LED lamp 14/18 Watt B22 base including taking down old unserviceable light fitting complete all as specified and directed.
Materials and labour for Earthing as in repair complete with galvanised iron earth plate electrode 600 x 600 x 6 mm thick, buried directly and preferably vertically in ground , earth pit not less than 2.25 metre deep below ground level with top edge of the plate not less than 1.5 metre below ground level connected with galavanised strip of size 32 x 6 mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (Medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade),wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6)type C-1 (with 20 mm grade aggregate), 50mm thick precast RCC (1:2:4) cover slab (reinforced with 8mm dia TMT bar @ 15 cm Centre to centre both ways and suitable handle made of 10mm dia) including necessary earth work complete all as directed.
Supply and fixing of cable jointing kit for straight through heat shrinkable type joint with jointing material and all connected accessories suitable for XLPE armoured aluminium conductor cable 1100 volts grade suitable for 3.5/4 core, 70 to 150 Sqmm including taking down of old one complete all as specified and as directed.
Ditto All as per Sl Item No 43, but cable grade of size 25 to 50 Sqmm 3.5/4 Core.
Ditto All as per Sl Item No 43, but cable grade of size 10 to 16 Sqmm 3.5/4 Core.
Supply and fix in replacement of MCCB 4Pole, 63Amps, 50KA, 415V, with adjustable thermal and adjustable magnetic setting Ics=75% Icu including take down old unserviceable one complete all as directed.
Ditto All as per Sl Item No 46, but MCCB 4Pole, 100Amps.
Ditto All as per Sl Item No 46, but MCCB 4Pole, 200Amps.
Ditto All as per Sl Item No 46, but MCCB 4Pole, 250Amps.
Ditto All as per Sl Item No 46, but MCCB 4Pole, 400Amps.
Dismantling /taking down steel tubular pole/RCC pole any size by cutting from foundation by means mechanically or manually all as specified and directed.
Supply and fixing hot dipped GI octagonal pole of 6 metre long with 01 metre arm suitable for mounting of 01 nos of LED street lights complete with base plate and GI foundations bolt and nuts, including PCC, excavation, returning and filling complete all as specified and as directed.
Supply and fix Danger notice plate of 1.6 mm thick Mild steel sheet, Vitreous enameled white, Letters, Figures and conventional Skull and Bones in single red colour and fixed with MS clamps, bolt and nuts of approved size ,for LT 20X15 cm size complete all as specified and as directed by the Engineer In-Charge.
Supply and fix in street light TIMER control panel , pole/wall mounting made out of CRCA sheet duly powder coated with locking arrangement, including internal wiring complete with bypass arrangements and comprising the following (or as manufactures recommendation and design) including taking down old unserviceable timer panel complete all as specified and directed. (a) Incomer MCB TPN 63/100 Amps ,240/410V-01 No (b) Digital timer switch - 01 No (c) Contractor AC 3 rating,3ph of capacity 65/100 - 01 No (d) ON/OFF indicating lamp -01 set (e) Auxiliary change over switch 6 A -01 No
Supply and fix in repair Digital timer switches DIN type Programmable every one minute with backup of 6 years ,28 memory locations, current capacity 16A weekly program with one changeover (1Co) total 28 programs as per existing site condition complete all as directed by Engineer InCharge.
Supply and fix in repair three pole power contactor 80 Amp, complete all as specified and as directed.
Supply and fix in repair MCB SP 6 to 32 Amp C curve 240/415 volt AC.
Supply and fix in repair MCB TPN C series 63 Amp C curve 240/415 volt AC.
Material and labour for shifting of panels of any size and type from one place to another place duly removing all connection are fully without any damages and losses any parts, dismantling PCC platform and mount on PCC at place and necessary painting of panels with two coats of aluminium paint over one coat of anti corrosive paint including preparation of surface ,by removing old paint ,proper cleaning, filling cavities with filler should applied internally and externally and reconnect the cable and all connected accessories including foundation painting of foundation of two coats of any size complete all as directed.
Supply and fix in repair solar LED post Top with built in solar panel, LED light and lithium battery with charge controller and 2 PIR sensor with 360 degree coverage light fitting 20 Watt 5700 K pressure die cast aluminum housing heat resistant toughened glass with frame with IP 66 protection complete all as specified and directed.
Supply and fix in replacement of Post Top Lamp LED with moonlight effect and efficient light distribution, having rated IP 65 protection ,suitable for 3 metre long die cast aluminum pole complete with base plate and GI foundation bolts and nuts including earth work and PCC foundation complete all as specified.
Material and labour for marking pole number as existing size of 50mm height in black colour with yellow back ground in round shape of dia maximum up to 150mm all as per the direction of the Engineer In-Charge.
Taking down Copper /aluminium point wiring (light ,fan ,socket ,bell, power point) complete fitting such as switches ,ceiling roses ,pendants, regulators, sockets ,light fitting any type, building security light removing materials to store for keeping in safe custody for taking credit to match with existing surface complete all as specified and directed.
Material & Labour for Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits) with 1.5 sqmm nominal cross sectional area, copper conductor unsheathed FRLSH cable 1100 Volts grade including PVC casing and caping and connected accessories ISI marked with concealed sunken boxes with modular cover plate , PVC boxes, hylam sheet , including 1.5 Sqmm nominal cross sectional area PVC insulated copper conductor unsheathed FRLSH cable single core multistranded cable as earth continuity wire for one light controlled by one switch complete all as specified and as directed.
All as per item No 64 here-in-before but for one fan point controlled by one push button on independent board.
All as per item No 64 here-in-before but for 5 pin 5 Amps socket outlet point on independent board.
All as per item No 64 here-in-before but for 5 pin 5 Amps socket outlet point on same board.
All as per item No 64 here-in-before but using 2.5 Sqmm copper conductor cable (multistranded) PVC insulated FRLSH and unsheathed cable and 2.5 Sqmm copper conductor cable (multistranded) PVC insulated FRLSH and unsheathed cable earth wire with terminal box of suitable size of modular switch & socket for one 6 pin 15 Amp socket outlet point on independent board complete all as specified.
Supply & Fix switch piano flush type single pole one way 5 Amp one way complete all as specified and as directed.
Supply & Fix switch piano flush type single pole one way 15 Amp complete all as specified and as directed.
Supply & Fix switch socket combination 5 Amps, 5 pin 2 in 1, complete all as specified and as directed.
Supply & Fix in socket outlet multipurpose 5 and 15 Amps, 5 pin, 2 in 1 complete all as specified and directed
Supply & Fix fan regulator electronic step type 100 W, 250 Volts complete all as specified and as directed.
Supply & Fix ceiling rose surface bakelite 65 x 50 mm, 3 terminals complete all as specified and as directed
Supply & Fix in repair, capacitor for ceiling fans,230 volts, 2.5 MFD including necessary soldering complete all as specified and as directed
Supply & Fix in repair, capacitor for any type of exhaust fan/pedestal fan/air circulator fan 230 volts AC including necessary soldering of capacity 4 MFD complete all as specified and directed.
Supply & Fix in repair ,lamp holder ,PVC /poly carbonate type with back plate suitable for batten fittings, complete all as specified and directed
Supply & Fix in repair, ceiling rose surface bakelite 65 x 50 mm, 3 terminals complete all as specified and as directed
Material & Labour in repair sub main wiring with 4 runs of 10 Sqmm PVC insulated unsheathed multistranded single core copper conductor FRLSH, ISI marked cable drawn through ISI Marked, medium grade, non metallic, PVC Casing & Capping and all accessories, with 1 run of 10 Sq mm PVC insulated unsheathed multistranded single core copper conductor FRLSH, and making good disturbed surfaces, applying distemper /Emulsions matching to the existing colour /quality of walls/floors/ceiling etc complete all as specified Note:- Five run of cable and one run of PVC casing and caping shall be measured as one unit.
Material & Labour in repair sub main wiring with 2 runs of 4 Sqmm PVC insulated unsheathed multistranded single core copper conductor FRLSH, ISI marked cable drawn through ISI Marked, medium grade, non metallic, PVC Casing & Capping and all accessories, with 1 run of 4 Sq mm PVC insulated unsheathed multistranded single core copper conductor FRLSH, and making good disturbed surfaces, applying distemper /Emulsions matching to the existing colour /quality of walls/floors/ceiling etc complete all as specified Note:- Three run of cable and one run of PVC casing and caping shall be measured as one unit.
Material & Labour in repair sub main wiring with 2 runs of 6 Sqmm PVC insulated unsheathed multistranded single core copper conductor FRLSH, ISI marked cable drawn through ISI Marked, medium grade, non metallic, PVC Casing & Capping and all accessories, with 1 run of 6 Sq mm PVC insulated unsheathed multistranded single core copper conductor FRLSH, and making good disturbed surfaces, applying distemper /Emulsions matching to the existing colour /quality of walls/floors/ceiling etc complete all as specified Note:- Three run of cable and one run of PVC casing and caping shall be measured as one unit.
Supply & Fix in repair, Sheet Metal Enclosure for MCB DB, TPN, 4 ways, double door, with 200 Amps rated bus bar, having IP-43 protection including taking down old DB complete all as specified.
Supply & Fix in repair, Sheet Metal Enclosure for MCB DB, TPN, 8 ways, double door, with 200 Amps rated bus bar, having IP-43 protection including taking down old DB complete all as specified.
Supply & Fix in repair, Sheet Metal Enclosure for MCB DB, TPN, 12 ways, double door, with 200 Amps rated bus bar, having IP-43 protection including taking down old DB complete all as specified.
Supply & Fix in repair, MCB, TPN, 63 Amps, 415 Volt, and B curve; having breaking capacity 10 kA, complete all as specified.
Supply & Fix in repair, MCB, TPN, 32 Amps, 415 Volt, and B curve; having breaking capacity 10 kA, complete all as specified.
Supply & Fix in repair, MCB, SPN, 63 Amps, 415 Volt, and B curve; having breaking capacity 10 kA, complete all as specified.
Supply & Fix in repair MCB SP 6-32 Amps, 240 Volt, B curve, having breaking capacity 10 KA, complete all as specified.
Supply & Fix in repair MCB SPN 6-32 Amps, 240 Volt, B curve, having breaking capacity 10 KA, complete all as specified.
Supply & Fix in repair LED light fitting 20 Watt, high performance batten, 220 volt, 50 Hz,6000 k surface mounted high quality extruded polycarbonate ,environmental friendly ,energy efficient , with all connecting accessories ,with suitable connection complete all as specified.
Taking down unserviceable ceiling fan of 1200mm/1400mm sweep, cutting out the existing burnt out fan motor winding, cleaning the motor slots, rewinding the motor with insulated copper winding wire of existing gauge, baking / heating up the motor to achieve the proper insulation resistance and re-hanging / refixing after repair including applying a coat of synthetic enamel paint (Glossy Finish) with spray gun, marking MES No complete all as specified.
Ditto all as per item Ser No 91 above but exhaust fan of 450/300/250 mm sweep complete all as specified.
Material & Labour for Earthing with galvanised MS earth plate of size 600 x 600 x 6 mm thick buried directly in ground not less than 2.25 metre below ground level, earth plate paced on all side with charcoal mixed with salt to a thickness of 150 mm in layers, connected by GI earth strip of size 25 x 4 mm thick, soldered and revetted to earth plate. GI earth strip will be protected by using 40mm bore GI pipe (light grade) earth plate to transformer body, LT feeder pillar box, and neutral of transformer etc complete. The earthing includes PCC pit chamber, RCC pit cover and frame, watering pipe 20 mm bore, funnel with wire mess with necessary earth work including disposal of surplus soil to a distance not less than 50 metre etc complete all as specified and shown in electrical plate No 3 of SSR Part I – 2009 complete all as specified and directed.
Supply & Fix in repair LED building security light 50 watts, 50 Hz, 220 volts having IP-65 protection, pressure die cast aluminium housing, high luminous efficiency and high power complete all as specified.
Supply & Fix in repair LED building security light 60 watts, 50 Hz, 220 volts having IP-65 protection, pressure die cast aluminium housing, high luminous efficiency and high power complete all as specified.
Supply & fix in repair Plastic body exhaust fans AC single phase 230/ 240 Volts of size 300 mm sweep, 900 RPM complete including taking down old one complete all as specified
Supply & fix in repair Plastic body exhaust fans AC single phase 230/ 240 Volts of size 200 mm sweep, 900 RPM complete including taking down old one complete all as specified
Amount of Credit Schedule shall be deducted to arrive the Contract Sum.
ST ANTONY CONSTRUCTIONS
P N Enterprises
PHEJAYS AGENCIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .