Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.3 CrAccepted-AOC | ₹1.3 Cr | 1 | Accepted-AOC Being L1 |
| 2 | 2₹1.5 Cr+₹14.5 L (10.8%)Rejected-Finance 13 29 3RD FLOOR EAST PATEL NAGAR NEW DELHI 110 008 | WEST | DELHI | 110008 | ₹1.5 Cr+₹14.5 L (10.8%) | 2 | Rejected-Finance Since not L1 |
| 3 | 3₹1.6 Cr+₹22.5 L (16.9%)Rejected-Finance SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | ₹1.6 Cr+₹22.5 L (16.9%) | 3 | Rejected-Finance Since not L1 |
| 4 | 4₹1.7 Cr+₹32.8 L (24.6%)Rejected-Finance H NO 9 9 1 1 DOCTOR S COLONY SHIVAJIPALEM VISAKHAPATNAM 530 017 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530017 | ₹1.7 Cr+₹32.8 L (24.6%) | 4 | Rejected-Finance Since not L1 |
| 5 | 5₹1.8 Cr+₹48.3 L (36.2%)Rejected-Finance | ₹1.8 Cr+₹48.3 L (36.2%) | 5 | Rejected-Finance Since not L1 |
Tender Value
₹1.8 Cr
EMD Value
₹2.5 L
Closing Date
6 May 2022, 6:00 pmClosed
Chief Engineer R n D Secunderabad
Chief Engineer RnD Picket Secunderabad 500003
REPLACEMENT OF BER EQUIPMENTS AND ITEMS OF ELECTRICAL INSTALLATION AND VARIOUS BUILDINGS OF NSTL VISAKHAPATNAM
2022_MES_516197_1
87147
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
NSTL Visakhapatnam
Class B
Category b ii
7 documents required · 7 mandatory
₹1,000
Yes
AGE I RnD NSTL
₹2.5 L
Yes
1 Jun 2022
1 Apr 2022
13 May 2022
1 Apr 2022
6 May 2022
22 Apr 2022
Amount
Supply, install, testing and commissioning of Out door LT Panel Cubicle type, 440 volts 3 phase, vermin proof, factory made CPRI approved, at Building No. 102, Main frame 3.15 mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door sytem lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 sahde and air vent gasket for natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, ingress of protection of outer shall be IP-54, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted and locking arrangements, alluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar of 1.5 times of incomer for phase and full rated capacity for neutral. Bus bar support of 'F' calss insulators epoxy type, earthing of 32x6 mm GI Flat, control wiring with multi stranded copper conductor cable of suitable size along with fuses, MCBs etc including following accessories and switch gears complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
Supply, install, testing and commissioning of Out door LT Panel Cubicle type, 440 volts 3 phase, vermin proof, Factory made CPRI approved, at Old MRS Bldg No. 105, Main frame 3.15 mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door sytem lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 sahde and air vent gasket for natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, ingress of protection of outer shall be IP-54, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted and locking arrangements, alluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar of 1.5 times of incomer for phase and full rated capacity for neutral. Bus bar support of 'F' calss insulators epoxy type, earthing of 32x6 mm GI Flat, control wiring with multi stranded copper conductor cable of suitable size along with fuses, MCBs etc including following accessories and switch gears complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
Supply, install, testing and commissioning of Out door LT Panel Cubicle type, 440 volts 3 phase, vermin proof, factory made CPRI approved, at Bldg No. 104, Main frame 3.15 mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door sytem lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 sahde and air vent gasket for natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, ingress of protection of outer shall be IP-54, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted and locking arrangements, aluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar of 1.5 times of incomer for phase and full rated capacity for neutral. Bus bar support of 'F' calss insulators epoxy type, earthing of 32x6 mm GI Flat, control wiring with multi stranded copper conductor cable of suitable size along with fuses, MCBs etc including following accessories and switch gears complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
Supply, install, testing and commissioning of Out door LT Panel Cubicle type, 440 volts 3 phase, vermin proof, Factory made CPRI approved, at Bldg No. 108, Main frame 3.15 mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door sytem lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 sahde and air vent gasket for natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, ingress of protection of outer shall be IP-54, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted and locking arrangements, aluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar of 1.5 times of incomer for phase and full rated capacity for neutral. Bus bar support of 'F' calss insulators epoxy type, earthing of 32x6 mm GI Flat, control wiring with multi stranded copper conductor cable of suitable size along with fuses, MCBs etc including following accessories and switch gears complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
Supply, install, testing and commissioning of Out door LT Panel Cubicle type, 440 volts 3 phase, vermin proof, Factory made CPRI approved, at Bldg No. 108 PDB-2, Main frame 3.15 mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door sytem lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 sahde and air vent gasket for natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, ingress of protection of outer shall be IP-54, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted and locking arrangements, aluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar of 1.5 times of incomer for phase and full rated capacity for neutral. Bus bar support of 'F' calss insulators epoxy type, earthing of 32x6 mm GI Flat, control wiring with multi stranded copper conductor cable of suitable size along with fuses, MCBs etc including following accessories and switch gears complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
Supply, install, testing and commissioning of Out door LT Panel Cubicle type, 440 volts 3 phase, vermin proof, Factory made CPRI approved, at MRS Bldg, Main frame 3.15 mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door sytem lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 sahde and air vent gasket for natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, ingress of protection of outer shall be IP-54, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted and locking arrangements, alluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar of 1.5 times of incomer for phase and full rated capacity for neutral. Bus bar support of 'F' calss insulators epoxy type, earthing of 32x6 mm GI Flat, control wiring with multi stranded copper conductor cable of suitable size along with fuses, MCBs etc including following accessories and switch gears complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
Supply, install, testing and commissioning of Out door LT Panel Cubicle type, 440 volts 3 phase, vermin proof, Factory made CPRI approved, at Bldg No. 203 Shock Tank (old Work shop-1), Main frame 3.15 mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door sytem lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 sahde and air vent gasket for natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, ingress of protection of outer shall be IP-54, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted and locking arrangements, aluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar of 1.5 times of incomer for phase and full rated capacity for neutral. Bus bar support of 'F' class insulators epoxy type, earthing of 32x6 mm GI Flat, control wiring with multi stranded copper conductor cable of suitable size along with fuses, MCBs etc including following accessories and switch gears complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
Supply, install, testing and commissioning of Out door LT Panel Cubicle type, 440 volts 3 phase, vermin proof, Factory made CPRI approved, at Bldg No. 203 (old Work shop - 2), Main frame 3.15 mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door sytem lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 sahde and air vent gasket for natural flow of air, U gasket for making complete vermin proof, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, ingress of protection of outer shall be IP-54, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted and locking arrangements, aluminum bus bar, colour coded sleeving heat shrinkable type, with bus bar of 1.5 times of incomer for phase and full rated capacity for neutral. Bus bar support of 'F' calss insulators epoxy type, earthing of 32x6 mm GI Flat, control wiring with multi stranded copper conductor cable of suitable size along with fuses, MCBs etc including following accessories and switch gears complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
Supply, install, connect, test and commissioning of Manufacturer / OEM assembled Silent Type (DG) Diesel Engine driven Generating Set having prime power rating of 250 KVA/200 KW at a power factor of 0.8 lagging, 415 Volts, AC, 3 phase, 4 wire, 50 Hz, 1500 RPM, alternator directly coupled with diesel engine, mounted on common base frame complete with an overload capacity of 10% for one hour in every 12 hours operation and Alternator as per IS: 13364 or as amended upto date complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy, with Acoustic enclosure with inbuilt fuel tank, fuel line & accessories, PCC foundation work as per manufacture's instructions, anti vibration pads, OEM recommended Standard Panel showing standard parameters of engine & alternator, exhaust pipe & other standard accessories and comprising the following complete as per CPCB-II norms all as specified and directed:- (A) ENGINE (Prime Mover): Diesel Engine, four stroke, 6 cylinders, liquid / water cooled, turbo charged, air to air after cooled, conforming to ISO 8528, capable of giving adequate BHP not less than 310 BHP at 1500 RPM to drive alternator capable of delivering minimum 250 KVA (200 KW) at outdoor atmospheric conditions at Visakapatnam and capable of taking 10% overload for one hour after 12 hours of continuous operation, complete with the standard fittings / fixtures as per manufacturer and following accessories as specified and directed.
Make: Kirloskar, Model: 6SL1500TA or equivalent in Greaves cotton / Ashok Leyland / Cummins. (i) Fly wheel housing and fly wheel. (ii) Air cleaner dry type replaceable paper element type with restriction indicator. (iii) Electronic governor. (iv) Fuel filters as per manufacturers recommendations including water separator, fuel pump, Fuel injection pump (FIP) and injectors. (v) Radiator, Fan & water pump assembly. (vi) Forced lubrication - Pump, Lub oil filter & Lub oil cooler. (vii) Exhaust silencer: As per CPCB-II Norms. (viii) Exhaust gas driven trubo charger. (ix) First fill lube oil and coolant and diesel during commission and testing. (B) ALTERNATOR: Alternator shall be self excited, self regulated, brush less for 200 KW / 250 KVA at the speed of 1500 RPM at 415 Volts, 50Hz, three phase, 4 wire system with advance electric voltage regulator to ensure high voltage accuracy with + 0.5 % with class H insulation and enclosure IP 23 ingress protection, directly coupled with engine through flexible coupling and confirming IS- 4722 complete-1 No. Make of Alternator: Stamford (CGT) / Kirloskar Electric / Leroy Somer / Crompton Greaves.
(C) BASE FRAME & FOUNDATION: Common base frame for Engine & Alternator made from structural steel channel, PCC foundation including adequate number of suitable anti-vibration pads all as per the recommendation of the manufacture. (D) ELECTRICAL STARTING SYSTEM: Electric starting system with battery charging alternator and axial type starter motor including adequate number of high capacity maintenance free batteries as recommended by OEM / manufacturer including interconnecting cables / leads with terminals complete with starting / stopping switch, Voltmeter etc - 01 Set. (E) ACOUSTIC ENCLOSURE: Corrosion resistant, acoustic and weather proof enclosure with durable industrial locking system on doors, doors with gasket made of high quality EDPM Material, with arrangement for fresh air intake for cooling of Engine & Alternator, extraction and discharging of hot air to the atmosphere, made out of CRCA sheet with 11 tank pre treatment process and UV resistant powder coating and high quality noise absorbant & fire retardant grade acoustic insulation material (Rockwool) complying to IS 8183 well suitable for 250 KVA DG set to reduce noise level to 75 dbA, measured at 1.00 meter distance conforming to CPCB II norms.
Enclosure shall have inbuilt base frame mounted fuel tank of standard capacity of minimum 450 litres, fabricated out of 14 SWG MS sheet mounted inside the encloser along with fuel piping from tank to engine capacity as recommended by OEM with drain valve, air vent, inlet, outlet connection and suitable exhaust pipe duly cladded with glass wool and covered with aluminimum sheet inside the encloser and exhaust trail pipe with muffer complete all as per manufacture's design. (F) DG SET mounted Microprocessor based Control Panel: Fitted with & having digital display for the following :- (a) Phase voltages & Currents, frequency, Reverse Power, Gen set KVA, KW, KWH, KVAR, Power factor, Canopy temperature. (b) Lub Oil Pressure, Engine Temperature, RPM, Run hours, Number of starts, fuel level, Auto / Manual stop, battery charge condition, AMF feature. (c) Battery charging failure, Over / under speed, Over current, Over / under voltage, over KW, phase seq, phase missing, Mains under voltage, Earth fault trip, Fuel usage alarm. (d) Low Lub oil pressure, High Engine temperature, Low / High battery voltage, Low fuel level, over crank protection, routine maint indicator, Gen set test facility, Mains frequency.
(G) AMF PANEL: Supply Fabricate, install, connect, test and commissioning of LT AMF & Electrical panel board, AC, 3 phase, 4 wire, 415 / 500 V, 50 Hz, outdoor weather proof type, fabricated with 3.15 mm thick mild steel and suitable sized pressed steel frame work, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit, chamber for aluminium bus bars of suitable capacity insulated with colored PVC sleeves mounted on suitable insulators and separators, holes drilled for connections including provision of AMF panel & 320 Amps Change over switch chamber for metering equipment complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip / rods insulated, complete mounted on PCC pillars including painting of panel board with two coats of synthetic enamel paint over one coat of red oxide primer complete all as specified and comprising of the followings:- (i) MCCB 4 Pole, 415 V, Thermal Magnetic type, 400 Amps with breaking capacity 36 KA - 02 Nos. Make: L&T / ABB (As EB & DG Incomer). (ii) Power Contactors of Capacity 400 A, 4 pole -02 Nos. Make: L & T / ABB (iii) MCB of rating 6 A, 240 volts, SP - 07 Nos. (iv) MCB of rating 16 A, 240 volts, SP - 04 Nos. (v) Line Voltage monitor 240 V AC 3P 4 W - 01 No.
Supply, Installation, testing, Commissioning of 11kV Indoor type Metal Clad, totally enclosed & fully interlocked draw out type Vacuum Circuit Breaker as per IEC 62271-100/200. single break trip free breaker with SPMX mechanism, mounted on a truck carraige, complete with self contained operated fully interlocked rack in & rack out mechanism. Breaker is featured with mechanical ON & OFF Indicator with hand trip device, Spring release coil, Shunt trip coil & auxiliary switch of 6NO+6NC, with maximum system voltage rating of 12kV consisting of 2 Incomers of 800A VCB + 1 Outgoing Feeder of 800A VCB, Short Circuit Capacity of 26.3kA, Fully compartmentalised sheet steel enclosure floor mounting type with automatic safety shutters, independent pressure discharge flaps alongwith heat shrinkable PVC sleeved busbars, foundation bolts etc. with provision for termination of 2-Nos. 3-core PVC / XLPE / PILC cable using M-SEAL type or equivalent termination kits, Busbar Rating of 1250A, Bus-bars shall have full Voltage Sleeving on it and shall be self-supported type, i.e. without any support insulators. The Incomer Panels shall contain Line PT arragement. Bus bar should be of electrolyte Copper.The relay shall have integral arc-protection based on simultaneous detection of current and light to ensure reduced cubicle damage and increase personal safety (<15 ms). The Circuit Breaker shall be of floor rolling design with encapsulated Vacuum bottles and shall have all fool-proof interlocks as : Interlocks shall be provided to prevent a ‘Closed’ breaker to rack out from ‘Service’ to ‘Test’ / 'Isolated’, position or insert a ‘closed’ breaker from ‘Test’ to ‘Service’ position including removing the existing VCB of any type after disconnecting electric cables and depositing to MES storeyard.
In either case the breaker contacts must remain in open position. Before racking out the breaker must be fully discharged from any static charge. All Panels shall have integral earth Switch with making capacity. Type Test reports shall be submitted for the same. The VCB panel shall comprising of following:- Current Transformer: CT Ratio: 150/75/1-1A Core 1: Class 0.5; 10VA (for metering) Core 2 : Class 5P20,10VA (for protection) STC - 40KA for 1 Sec. * Rated VA shall be as per actual burden calculation at the CT secondary side & feasibility at the time of detailed engineering - 03 Nos for Each VCB. Potential Transformer: 3 Nos. (2 Nos for incomer VCb and 1 No for outgoing VCB) Potential Transformer backed by HT & LT fuses (Mounted on VCB Truck) PT Ratio :: 11KV/rt3 / 110V/rt3 / 110V/rt3 Core #1 :: class 0.5, 100VA Core #2 :: class 3P, 50VA Breaker panel indication lamps : Breaker On / Off / Trip / Trip Circuit Healthy / Spring charged / Breaker in service / Breaker in test / R - Phase + Y - Phase + B - Phase
SWITCHES AND OTHER ACCESSORIES: (i) DC ON/OFF Switch-1No (ii) AC ON/OFF Switch - 1No (iii) Heater with heater switch & thermostat - 1 No (iv) Cubicle illumination lamp - 1No (v) 15A, 230V, 3 pin plug plug & socket - 1 No (vi) Local Remote Switch - 1 No (vii) T-N-C Switch - 1 No (viii) Mech. ON-OFF push button - 1 No (ix) Hooter - 1No (x) 6 Window Annunciator (xi) Multi function meter with 4 line didital display Relays: (i) Numerical Relay with built in protection feature (50/51/50N/51/27/59 with inbuilt trip circuit supervision) with RS-485 port - 01 No. (ii) Master trip / Lock out relay (86) : VAJH13 / equivalent - 01 No. Make: ABB or equivalent in Siemens / Schneider / Crompton Greaves.
Supply, Installation, testing, Commissioning of 11kV Indoor type Metal Clad, totally enclosed & fully interlocked draw out type Vacuum Circuit Breaker as per IEC 62271-100/200. Single break trip free breaker with SPMX mechanism, mounted on a truck carraige, complete with self contained operated fully interlocked rack in & rack out mechanism. Breaker is featured with mechanical ON & OFF Indicator with hand trip device, Spring release coil, Shunt trip coil & auxiliary switch of 6NO+6NC, with maximum system voltage rating of 12kV consisting of 1 Incomers of 800A VCB + 1 Outgoing Feeder of 800A VCB, Short Circuit Capacity of 26.3kA, Fully compartmentalised sheet steel enclosure floor mounting type with automatic safety shutters, independent pressure discharge flaps alongwith heat shrinkable PVC sleeved busbars, foundation bolts etc. with provision for termination of 2-Nos. 3-core PVC / XLPE / PILC cable using M-SEAL type or equivalent termination kits, Busbar Rating of 1250A, Bus-bars shall have full Voltage Sleeving on it and shall be self-supported type, i.e. without any support insulators. The Incomer Panels shall contain Line PT arragement. Bus bar should be of electrolyte Copper.The relay shall have integral arc-protection based on simultaneous detection of current and light to ensure reduced cubicle damage and increase personal safety (<15 ms). The Circuit Breaker shall be of floor rolling design with encapsulated Vacuum bottles and shall have all fool-proof interlocks as : Interlocks shall be provided to prevent a ‘Closed’ breaker to rack out from ‘Service’ to ‘Test’ / 'Isolated’, position or insert a ‘closed’ breaker from ‘Test’ to ‘Service’ position. In either case the breaker contacts must remain in open position including removing the existing VCB of any type after disconnecting electric cables and depositing to MES storeyard.
Before racking out the breaker must be fully discharged from any static charge. All Panels shall have integral earth Switch with making capacity. Type Test reports shall be submitted for the same. The VCB panel shall comprising of following:- Current Transformer: CT Ratio: 150/75/1-1A Core 1 : Class 0.5; 10VA (for metering) Core 2 : Class 5P20, 10VA (for protection) STC - 40KA for 1 Sec. * Rated VA shall be as per actual burden calculation at the CT secondary side & feasibility at the time of detailed engineering - 03 Nos for Each VCB. Potential Transformer : Potential Transformer backed by HT & LT fuses (Mounted on VCB Truck) for incomer VCB PT Ratio :: 11KV/rt3 / 110V/rt3 / 110V/rt3 Core #1 :: class 0.5, 100VA Core #2 :: class 3P, 50VA Breaker panel indication lamps : Breaker On / Off / Trip / Trip Circuit Healthy / Spring charged / Breaker in service / Breaker in test /R - Phase + Y - Phase + B - Phase SWITCHES AND OTHER ACCESSORIES: (a) DC ON/OFF Switch-1No (b) AC ON/OFF Switch - 1No
(c) Heater with heater switch & thermostat - 1 No (d) Cubicle illumination lamp - 1No (e) 15A, 230V, 3 pin plug plug & socket - 1 No (f) Local Remote Switch - 1 No (g) T-N-C Switch - 1 No (h) Mech. ON-OFF push button - 1 No (j) Hooter - 1No (k) 6 Window Annunciator (l) Multi function meter with 4 line didital display Relays: (i) Numerical Relay with built in protection feature (50/51/50N/51/27/59 with inbuilt trip circuit supervision) with RS-485 port - 01 No (ii) Master trip / Lock out relay (86) : VAJH13 / Equivalent - 01 No Make: ABB or equivalent in Siemens / Schneider. Note for Sl Item Nos. 10 & 11: VCB PANEL SHOULD COMPRISE OF THE FOLLOWING FEATURES: (a) Push buttons for accepting faults and reset. (b) LED indicating lamps for (duly control wired up) (i) Auto trip (ii) Spring charge (iii) Fault Alarm
(iv) Trip Circuit Healthy (v) Trip circuit Unhealthy (vi) Breaker ON (vii) Breaker OFF (c) RS 485 communication (d) Motor operated spring stored energy trip for closing and opening of the breaker. (e) Manual charging / operating arrangement. (f) Fuses for metering and protection system (g) One No. internal bus earthing with flat GI strip of size 50x 6mm (h) one No. of space heater with thermostat (j) One No. of inside LED lamp with switch (40W 230V) (k) One No. of plug point with switch (5A, 230V) (l) Copper bus bar common for out going feeders with PVC sleeves (m) Complete control panel wiring with copper wire of size not less than 2.5 sqmm. (n) Power pack of capacity 110 V with necessary maintenance free batteries mounted on structural steel frame with all necessary connections - 1 No (o) Armoured copper cable 12core 1.5sqmm for control wiring from VCB to Transformer. (p) Civil design for foundation should be done all as per instructions manual of manufacturer.
Note: The VCB shall be tested for High Voltage test, Primary Injection test & Secondary Injection test individualy at site after erection before commissioning and the same is deemed to be to included in the quoted rate. MAKE FOR VCB - SIEMENS / ABB / Schneider / Crompton Greaves.
Supply, Install, testing and commissioning of Auto / Manual Synchronizing Panel 2 x 750 KVA HT 11KV generator relay and engine control panel made out of 2mm thick CRCA sheet with suitable MS angle iron frame with front and back openable, double door system lockable / openable by keys with louvers complete with powder coated with pure polyster simens grey structural RAL 7032 shade and air vent gasket for natural flow of air, U gasket for making complete vermin proof, ingress protection IP-52, the bottom plate shall be detachable plate type having provision for entry of armoured cables of adequate sizes with glands, gland plates and lugs with powder coated metal stand with provision for earthing stud at bottom and lifting lugs of suitable size at top danger notice plate having conventional symbol of bone and skull, IP-52, base frame on MS channel of suitable size with provision of incoming and outgoing cable entry with controlling and protection relays capable of synchronizing of two DG sets of capacity 2 x 750 KVA HT 11 KV Kirloskar Make Alternator with mains and with necessary protections and Command Controller PCC 3300 for Model KTA 2300 of make Cummins Engine and Kirloskar make alternators DG sets with NGR, 3 phase, 50Hz totally enclosed, factory made TYPE TESTED, (short time current withstand temperature rise degree of protection) comprising of following specifications and accessories complete all as specified and directed including removing the existing panel board of any type after disconnecting electric cables and depositing to MES storeyard.
(a) Calibration of PCC 3300 controller with Auxiliary 105 and control panel wiring Harness for 2 DG sets. (b) RTG and synchronisation panel with accessories. (c) Auto Synchronization. (d) Auto load Sharing (Active and Reactive). (e) LDSS - Load dependent start and stop. (f) All necessary potections through Sync Relay i.e. OV, UV, OF, UF, OC, OL, RPR, RKVAr etc. (g) SMPS based Battery chargers - 2Nos. (h) Digital Metering for V, A Hz, KWH, MFM - 2Nos. (j) Analogue Metering for DCV, DCA - 2 Nos. (k) HT / CTs and PTs of suitable size including necessary connected Control Cables complete. (l) Relay suitable for synchroniging panel with control wiring. (m) Extendable type feeder configuration. (n) Control cables from 11 KV DG sets to synchroniging panel. (o) Civil works and PCC foundation as per manufacturer's recommendation. Note: Any components and accessories required for commissioning of synchroniging panel shall be provided by the contractor without any extra cost to the department and the rate quoted shall be deemed to be included.
Leo Air and Power Solution pvt Ltd.
M/s Rohit Construction Co.
SERVO-TECH ENTERPRISES
SUPREET CONSTRUCTIONS
MURALI KRISHNA ASSOCIATES
eldi techs
GAGANSRI INFRA
Prasur Electricals & Engineering Co.
SOOD ASSOCIATES PVT LTD
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .