Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.2 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹7.2 L+₹88,807 (14.1%)Rejected-AOC | L2 | Rejected-AOC Other than lowest bidder |
| Sl No | Description | Qty | Unit | R. P. Suppliers and Construction Co. L2 | M/S SUKHMANI ENGINEERS L1 |
|---|---|---|---|---|---|
| 1.00 | Supply & fix in Repair single pointed air termination Aluminium rod, 12 mm dia, 300 mm long, complete all as specified and as directed by Engr-in-Charge. | 10 | Each | 100 ₹1,000 Lowest | 200 ₹2,000 |
| 2.00 | Supply & fix in Repair Aluminium strip 25 x 3.15mm with saddles and fixing screws etc., complete all as specified and as directed by Engr-in-Charge. | 120 | RM | 120 ₹14,400 Lowest | 186 ₹22,320 |
| 3.00 | Supply & install in Repair GI strip 32 mm x 6 mm buried In ground, complete all as specified and as directed by Engr-in-Charge. | 40 | RM | 226 ₹9,040 | 72 ₹2,880 Lowest |
| 4.00 | M&L for Test point terminal block for lightening conductors made out of gun metal or phosphorus bronze size of 75 x 75 x 25 mm drilled and screwed incl 3 Nos 6mm dia 25 mm long hexa head screws including connected with earthing and GI / Aluminium strips, complete all as specified and as directed by Engr-in-Charge. | 5 | Each | 777 ₹3,885 | 400 ₹2,000 Lowest |
| 5.00 | Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level, connecting to the Galvanised iron strip 25x4 mm by means of bolts, nuts , check nuts and washers of galvanized iron and steel earth wire protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit made from PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angle iron 40 x 40 x 6 mm and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 1.50 metre long placed on top edge of earth plate, common salt & charcoal filling, with fixing arrangement , funnel, wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus soil to a distance not exceeding 50 metres, all as per electrical plate No 5 of SSR 2009 Part-I and connecting to Transformer / Poles all as specified or indicated including testing on complete all as specified and as directed by Engineer-in-Charge. | 8 | Each | 4,588 ₹36,704 Lowest | 4,786 ₹38,288 |
| 6.00 | Supply & fix in repair MCB 40 TO 100 Amps 4 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge. | 8 | EACH | 4,500 ₹36,000 | 1,488 ₹11,904 Lowest |
| 7.00 | Supply & fix in repair MCB 63 Amps 2 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge. | 14 | EACH | 750 ₹10,500 | 648 ₹9,072 Lowest |
| 8.00 | Supply & fix in repair MCB 6 to 32 Amps 2 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge. | 20 | EACH | 300 ₹6,000 | 129 ₹2,580 Lowest |
| 9.00 | Supply and Fix in repair metal enclouser for DB double door SPN DB 8 way, complete all as specified and as directed by Engr-in-Charge. | 10 | EACH | 1,850 ₹18,500 Lowest | 1,969 ₹19,690 |
| 10.00 | Supply and Fix in repair sheet metal enclouser for DB double door TPN DB 4 way, complete all as specified and as directed by Engr-in-Charge. | 8 | EACH | 2,500 ₹20,000 | 1,324 ₹10,592 Lowest |
Tender Value
₹9.9 L
EMD Value
₹19,800
Closing Date
21 Jul 2025, 6:00 pmClosed
Sh K K Soni AE (Civ) AGE I R and D Manali
AGE I R AND D MANALI PIN 175103 PH 01902255014
REPAIR/MAINTENANCE OF LT OVERHEAD LINES, TRANSFORMERS AND OTHER CONNECTED ITEMS AT TRANSIT CAMP PALCHAN UNDER AGE (I) R and D MANALI.
2025_MES_714970_1
AGE(I)/MNL-39/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
150 days
Palchan
As per NIT and tender documents
5 documents required · 5 mandatory
₹500
AGE(I) R and D MANALI
₹19,800
Yes
7 Aug 2025
17 Jun 2025
23 Jul 2025
17 Jun 2025
21 Jul 2025
1 Jul 2025
Amount
Supply & fix in Repair single pointed air termination Aluminium rod, 12 mm dia, 300 mm long, complete all as specified and as directed by Engr-in-Charge.
Supply & fix in Repair Aluminium strip 25 x 3.15mm with saddles and fixing screws etc., complete all as specified and as directed by Engr-in-Charge.
Supply & install in Repair GI strip 32 mm x 6 mm buried In ground, complete all as specified and as directed by Engr-in-Charge.
M&L for Test point terminal block for lightening conductors made out of gun metal or phosphorus bronze size of 75 x 75 x 25 mm drilled and screwed incl 3 Nos 6mm dia 25 mm long hexa head screws including connected with earthing and GI / Aluminium strips, complete all as specified and as directed by Engr-in-Charge.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level, connecting to the Galvanised iron strip 25x4 mm by means of bolts, nuts , check nuts and washers of galvanized iron and steel earth wire protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit made from PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angle iron 40 x 40 x 6 mm and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 1.50 metre long placed on top edge of earth plate, common salt & charcoal filling, with fixing arrangement , funnel, wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus soil to a distance not exceeding 50 metres, all as per electrical plate No 5 of SSR 2009 Part-I and connecting to Transformer / Poles all as specified or indicated including testing on complete all as specified and as directed by Engineer-in-Charge.
Supply & fix in repair MCB 40 TO 100 Amps 4 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge.
Supply & fix in repair MCB 63 Amps 2 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge.
Supply & fix in repair MCB 6 to 32 Amps 2 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge.
Supply and Fix in repair metal enclouser for DB double door SPN DB 8 way, complete all as specified and as directed by Engr-in-Charge.
Supply and Fix in repair sheet metal enclouser for DB double door TPN DB 4 way, complete all as specified and as directed by Engr-in-Charge.
Supply and Fix in repair HDPE couregated Pipe 80/90 mm, complete all as specified and as directed by Engr-in-Charge.
Supply and Fix in repair HDPE couregated Pipe 40/50 mm, complete all as specified and as directed by Engr-in-Charge.
Supply & fix in repair MCCB 400 Amps 4 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge.
Supply & fix in repair MCCB 250 Amps 4 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge.
Supply & fix in repair MCCB 200 Amps 4 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge.
Supply & fix in repair MCCB 100 Amps 4 Pole, 50 Hz, 415 V C Frame with ruptruing capacity 35 KA with adjustable thermal and adjustable magnetic setting, complete all as specified and as directed by Engr-in-Charge.
Supply and laying XLPE insulated armoured cable (heavy duty) electric cable with aluminium stranded conductor 1100 volts grade of following size after taking down complete all as specified and directed by Engr-in-charge and directed as follows :
10 Sqmm x 2 Core
16 Sqmm x 2 Core
16 Sqmm x 4 Core
25 Sqmm x 3.5 Core
Supply and fixing in repair/replacement, installing, testing and commissioning factory made LT ( 415 Volts, 50 Hz , 3-phase, 4 wire supply ) CPRI approved and tested Street Light TIme switch Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class ( IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel angle iron frame work ( made out of 40 mm X 40 mm X 6 mm thick ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035 embedded in ground with and including bocks of PCC 1:2:4 type B1 of block size 30x30x30 cm, The scope of work also comprising of the following(18.01 to 18.03):-
The panel manufacturer should have following Govt. Approved Certificates: 1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011) 2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011) 3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk 4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 6300 A with rated insulation voltage 660V 5. ISO 9001 CERTIFIED
Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC platform incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Excavation, in trenches not exceeding 1.5 mtr wide and not exc 1.5 mtr in depth for laying cable in any type of soil and getting out complete all as specified & directed by Engineer-in-Charge.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick all as specified & directed by Engineer-in-Charge.
Removal of surplus excavated material to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge.
M & L Sand cushioning to under ground cable with dry sand locally available 8cm thick before laying the cable and 15 cm above the cable, stretching and testing of cable complete all as specified & directed by Engineer-in-Charge.
Taking out old unserviceable / serviceable class 'B' bricks from excavated trenches all as specied and directed by Engineer-In-Charge. Note:- Serviceable class 'B' bricks kept in safe custody for reuse at site and unserviceable bricks to be through in low lying area.
Supply and laying old size sub class ‘B’ bricks well burnt for cable protections laid flat with length equal to width of brick over cable perpendicular to length of cable complete all as specified and directed by Engr-in-Charge
Laying only serviceable sub class ‘B’ bricks as retrieved from Srl item No 23 complete all as specified and directed by Engr-in-Charge.
M & L for Heat Shrinkable 1.1 KV XLPE Straight Joints of following size including taking down complete all as specified and directed by Engr-in-charge and directed as follows :
10 sqmm to 25 sqmm size
35 sqmm to 50 sqmm size
Arranging fault locating machine to locate the fault in underground electric power cable of any length & any type of 1.1 KV grade HT/ LT cables & pin point the fault, it also include testing of the cable after locating fault and cutting the cable at Fault to fix the joint including excavation and earth wotrk in any type of soil, complete all as specified and as directed by Engr-in-Charge. Note : Cable joint shall be measured and paid separately under respective of Sch 'A' (ii) If fault is not rectifed within 24 hours after receivng message , the contractor shall be charged penalty for Rs 500/- per Hours & the same has been deducted from his account during RAR.
S & F in replacement of MCCB Encloser for 63/100/125 Amps MCCB, complete all as specified and as directed by Engr-in-Charge.
Isolate/de-energize the supply to the LT Panel Board of capacity ranging from 100 Amps to 400 Amps and voltage 415 Volts/230 Volts, opening the doors/covers of the cubicle enclosure for carrying out the servicing/maintenance/repairs of the Panel Board, switch gear,MCCB, metering etc and re-fixing the same/New in place after repairs including testing and commissioning of the panel board comprising of the following:- a) Cleaning the inside switch gear chambers for removing dust, carbon and rusted surfaces including cleaning with blower . b) Check the condition of the DMC/SMC support insulators including cleaning applying Dr beck red for better IR values and replacement of insulators if required. c) Tightening up of all bus bar connections, cable connections, replace bolt, nuts wherever required. Note :- Spares will be measured and paid under relevant items of schedule. , complete all as specified and as directed by Engr-in-Charge.
Supply only 3 phase digital multi function meter with suitable accessories and fixing arrangements, complete all as specified and as directed by Engr-in-Charge.
Supply only Voltmeter of range 0 to 500 Volts as per existing model/ capacity, complete all as specified and as directed by Engr-in-Charge. Make :- L&T/Schneider/Siemens/AE/C&S
Supply only Ammeter of range 0 to 500 Volts as per existing model/ capacity, complete all as specified and as directed by Engr-in-Charge.
Supply only Indicator lamp neon/ LED type, RBY as per existing model/ capacity, complete all as specified and as directed by Engr-in-Charge.
Supply only CT coil ratio 200/5 as per existing model/ capacity, complete all as specified and as directed by Engr-in-Charge.
Supply only in repair of 1.50 sqmm size FRLS, PVC insulated, unsheathed 1100 volts grade single core multi-stranded copper conductor cable in proper colour coding drawn, complete all as specified and as directed by Engr-in-Charge. (Make:- Polycab/Havells/Finolex/Gloster/Grandlay)
Supply and fixing in repair and replacement of mild steel hinges suitable for LT panel board shutters including welding, riveting, complete all as specified and as directed by Engr-in-Charge.
Material and Labour for preparation of surface by scrapping existing painted inside and out side surfaces of LT Panel board /Feeder piller of size not more than 1.5m x 0.75m x 1.2m and applying one coat of synthetic enamel paint (1st grade quality) and one coat of heat resistant paint of approved quality and colour, complete all as specified and as directed by Engr-in-Charge.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m, complete all as specified and as directed by Engr-in-Charge.
R. P. Suppliers and Construction Co. (BID ID -3357443)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .