Superintending Engineer, CEC, PWD.
Office of the SUPERINTENDING ENGINEER, Central Electrical Circle 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Construction of 50 Bedded Critical Care Block (CCB) in the New General Campus of Murshidabad Medical College and Hospital, Berhampore Murshidabad---- SITC of AC Machine.
2025_WBPWD_809042_1
WBPWD/CEC/NIT/04/Q/24-25
Open Tender
A/C ORG
Item Rate
70 days
Berhampore
Please refer Tender documents.
5 documents required · 5 mandatory
₹5.2 L
Central Electrical Circle, PWD.
27 May 2025
30 Jan 2025
11 Apr 2025
4 Feb 2025
10 Apr 2025
7 Feb 2025
6 Feb 2025
Amount
Supply, Installation, Testing, & Commissioning of AHRI certified micro-processor controlled Variable speed Air Cooled Screw Chillar having actual capacity of minimum 80 TR (Actual Capacity at design condition), comprising of semi-hermetic Screw Compressors and direct driven motor, each chiller shall have single or multiple compressors and individual refrigerant circuits, chiller shall be equipped with insulated shell and tube type flooded/ DX type cooler/evaporator, air-cooled condenser made of copper tube and aluminium fins as per OEM Standard, high efficiency condenser fans, including spring isolators mounting for chiller unit. The chiller package shall also be complete with refrigerant copper piping, factory charged R-134a refrigerant gas and Automatic feedback control system wiring, incoming suitable electrical isolator complete with accessories as required, automatic & safety controls including electronic expansion valve etc. Each compressor must be equipped with dedicated VFD. [MCHE (Micro Chanel Heat Exchanger) will not be acceptable] (2W+1S)
1. Minimum Cooling Capacity : 80 TR Screw - (Actual Capacity @ following Design Conditions) 2. Type of Refrigerant : R-134A 3. Chilled Water 'In' : 12 Deg C 4. Chilled Water 'Out': 7 Deg. C 5. Chiller Fouling Factor : 0.0001 (FPS) 6. The electrical panel should be IP55 protected (As per OEM Satndard) 7. Ambient Temperature: 104 Deg F / 40 Deg 8. Minimum IKW/TR should be less than equal to 1.46 at design condition (Including Fan Power) 9. Minimum COP at AHRI Condition not less than 3.0 & IPLV Minm 3.70 at AHRI conditions as per ECBC gudiline. 10. EVAP Pressure drop as per OEM standard. (Make : Daikin / Climaveneta/ Kirloskar/ Carrier/ Bluestar/ Voltas/ Johnson Control/ Mitsubishi/Clivet) SITC of 125/150 mm dia Butterfly Valve (Make - Honeywell/ AUDCO/ Advance) (Installed at inlet/outlet pipe of chiller) - 2 Nos. SITC of 125/150 mm dia Balancing Valve(Make-Honeywell/ AUDCO/ Advance) (Installed at inlet/outlet pipe of chiller for proper flow control) - 1 No. SITC of Flexible Connection - 125/150 mm dia(Make - Cori/ Resistoflex) - 2 Nos.
SITC of 4" Dial SS Pressure Gauge complete with syphon and isolation gauge cock. (HGURU/ AWAREE) (Installed at inlet/outlet pipe of chiller for monitoring pressurel) - 2 Nos. Supply, erection, testing & commissioning of Alcohol in glass type industrial thermometer complete with thermowell. (Make : HGURU/ AWAREE) (Installed at inlet/outlet pipe of chiller for monitoring temperature) - 2 Nos. SITC of 25 mm NB Ball Valve For descalling and drain (Make - Honeywell/ AUDCO/ Advance) (Installed at inlet/outlet pipe of chiller for drain water & descalling). --- 2 Nos. SITC of 15 mm NB Ball Valve For air purge valve /auto air vent(Make - Honeywell/ AUDCO/ Advance) (Installed at inlet/outlet pipe of chiller to remove air from system) - 1 No. SITC of Water flow switch for chillers (Make - Honeywell/ ANERGY) - 1 No.
Design, Supply, Installation,Testing & Commissioning of HVAC Electrical Control Panel with Microprocessor Controller - 1 No. There should be provision for Integrated Electrical distribution system for power circuit & control circuit with MCCBs for Compressors & water pumps, Starters with push button (start & stop ), Bus Bar arrangement (Cu.), control copper wiring and inter connections. Customer will provide Single Point Electrical Power Source to HVAC Panel. Bidder should design & supply the HVAC Panel accordingly. The Panel should have one incomer and three sets of separate outgoing circuits for three chillers and pump motors (having electrical interlocking between Chiller & Chiller pump). Cu. Tubing & placement of instrument like Pressure Gauge of Refregerant System, Supply of Heater for Compressor, Compressor oil, Oil Pressure Indicator, Trip arrangement for High Pressure & Low Pressure Cut Off, Anti-freezing Cut Off, Reversal of Phases & Phase failure Cut Off, Flow Switch Cut Off, Automatic Chilled Water Bypass System in case of partial load condition.
CHILLED WATER PUMP Supply, erection, testing & commissioning of Chilled water duty, end suction back pull out type centrifugal pumpset at (having Bronze/CI Impeller) with TEFC, IP-55, Class F insulated Sq. cage induction motor, complete with common base frame, spring vibration isolators, coupling and coupling guard for the following duty & including items as specified below : (Make - Kirloskar/ Grundfoss/ xylem/ Armstrong/ Flowmore/ KSB) Rated Flow 240 USGPM or higher at required water column head as per site condition (2 W + 1 S)
SITC of Following sizes valves incl. necessary fixing materials as required. 150 mm dia Sluice Valve (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ audco/ zoloto/sant/C &R)(Outgoing Header & Return)
125/150 mm dia Check Valve/NRV (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ audco /zoloto/sant/C &R) (Installed at Outlet of each pump)
125/150 mm dia Sluice Valve (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ audco/ zoloto/sant/C &R)(Installed at inlet & outlet of each pump)
150 mm dia butterfly Valve (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ audco/ zoloto/sant/C &R)(Installed at inlet & outlet of each pump)
100 mm dia butterfly Valve (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ audco/ zoloto /sant/C &R)(Installed at inlet & outlet of each pump)
SITC of 125/150mm dia Y Strainer (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ audco/zoloto/sant/C &R) (Installed at Inlet of each pump to isolate the perticals from system)
4" Dial SS Pressure Gauge complete with syphon and isolation gauge cock.(Make - HGURU/ Tameson/ Equivalent) ( Installed at Inlet & Outlet of each pump to monitor pressure)
25 mm NB Ball Valve For drain (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ audco/zoloto/sant/C &R) ( to drain out water during maintenance)
SITC of Purgeing Valve/Auto air vent with 15 mm Ball valve (Installed at each Room branch header & main headers) (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ audco/zoloto/sant/C &R)
Supply, Erection, Testing & Commissioning of MS ERW Chilled Water (Supply & Return) Piping (Class C) complete with flange , Tee, bend & other necessary fittings including weilding joints & MS supports and TF quality thermocol density 16kg/cum insulation with chicken wire mesh sand cement plaster (Pipes upto 150 NB shall be Heavy Grade as per IS: 1239 Part I and from 200 NB & above Pipes shall be as per IS: 3589 of specified thickness.) (Make-Tata/ Jindal/ SAIL) 150mm NB (Insulation 50 mm thick)
100mm NB (Insulation 50 mm thick)
80 mm NB (Insulation 50 mm thick)
65 mm NB (Insulation 50 mm thick)
50mm NB (Insulation 50 mm thick)
32mm NB (Insulation 50 mm thick)
25 mm NB (Insulation 50 mm thick)
Floor Mounted Outdoor type Air Handling Unit - SITC of site assembled type modular double skinned construction with continuous insulation with thermal break. The AHU enclosure's outer & inner Skin layer of 0.6 mm or higher & outer skin has to be polymer coated and insulation panel should be made of thermal break profile - PUF insulation with thickness of at least 40mm or better. The AHU should have heat recovary ventilator or exchanger for extrating @ 400 CFM stale air with the arrangement of VCD and injection of fresh air @ 360 CFM with VCD and mixing chamber for balance return air and fresh air with 02 (Two) stage filtration system (Prefilter having efficiency (EU - 4/MERV7) 90% down to10 micron & Fine Filter having efficiency 95% down to 5 micron (MERV-14) (Make - FMI/ Spectrum/ Thermi) including UV lamp of suitable rating for each of the air-suction & discharge of condition space as well as injection of fresh air and emmission of stale air as per direction of EIC). The AHU Coil to be with hydrofolic coating. The addon suitable gadgets shall be a set of butterfly, balancing & control valve with pressure gauge & temparature gauge each AHU.
The AHU Fan assembly should be either motor directly coupled with Impeller or Belt driven as per OEM standard suitable for air velocity range 7.3 - 8.2 ft./Sec through the multi-layer (6-8 row)12 mm - 19 mm dia Copper tubes with Alluminium Fins (as per OEM standard). There should be AHU fans of Forward/ Backward Curve, with discharge not less than 3400 CFM, compatable for 415V, 50 Hz supply continuous duty Class IE 1 (Make for Fan Unit - Nicotra/ Kruger/ Caryaire) (Make for Motor - Crompton / Kirloskar/ NEC/ ABB/ Siemens).External Static pressure shall be within 10 - 20 mm Wg +obstruction to overcome hepa filter at laminer bench. There should be electrical interlocking/switching arrangement for running the system in possitive or negetive pressure mode as per requirement. (Make : Zeco / System Air/ Edgetech/Daikin/Jaypee/Carrier India) (AHRI/EUROVENT CERTIFIED) --For OT-2
SITC of site assembled type modular Single skinned construction with continuous insulation with thermal break. Outer skin has to be polymer coated and insulation panel should be made of thermal break profile - PUF insulation with thickness of at least 40mm or better. The AHU should have heat recovary ventilator or exchanger for extrating @ 400 CFM stale air with the arrangement of VCD and injection of fresh air @ 360 CFM with VCD and mixing chamber for balance return air and fresh air with 02 (Two) stage filtration system (Prefilter having efficiency (EU - 4/MERV7) 90% down to10 micron & Fine Filter having efficiency 95% down to 5 micron (MERV-14) (Make - FMI/ Spectrum/ Thermi) including UV lamp of suitable rating for each of the air-suction & discharge of condition space as well as injection of fresh air and emmission of stale air as per direction of EIC). The AHU Coil to be with hydrofolic coating. The addon suitable gadgets shall be a set of butterfly, balancing & control valve with pressure gauge & Water Bypass system in case of partial load condition.
The AHU Fan assembly should be either motor directly coupled with Impeller or Belt driven as per OEM standard suitable for air velocity range 7.3 - 8.2 ft./Sec through the multi-layer (6-8 row)12 mm - 19 mm dia Copper tubes with Alluminium Fins (as per OEM standard). There should be AHU fans of Forward/ Backward Curve, with discharge not less than 3400 CFM, compatable for 415V, 50 Hz supply continuous duty Class IE 1 (Make for Fan Unit - Nicotra/ Kruger/ Caryaire) (Make for Motor - Crompton / Kirloskar/ NEC/ ABB/ Siemens).External Static pressure shall be within 10 - 20 mm Wg +obstruction to overcome hepa filter at laminer bench. There should be electrical interlocking/switching arrangement for running the system in possitive or negetive pressure mode as per requirement. (Make : Zeco / System Air/ Edgetech/Daikin/Jaypee/Carrier India) (AHRI/EUROVENT CERTIFIED) --For OT-1
SITC of site assembled type modular Single skinned construction with continuous insulation with thermal break. Outer skin has to be polymer coated and insulation panel should be made of thermal break profile - PUF insulation with thickness of at least 40mm or better. The AHU should have Heat Recovery ventilator or exchanger for extrating @ 940 CFM stale air with the arrangement of VCD and injection of fresh air @ 850 CFM with VCD and mixing chamber for return air and fresh air with 03 (Three) stage filtration system (Prefilter having efficiency (EU - 4/MERV7) 90% down to10 micron, Fine Filter having efficiency 99% down to 0.3 micron (MERV-14 (Make - FMI/ Spectrum/ Thermi) and HEFA filter MERV-17 0.3 micron for both Inlet & Outlet including UV lamp of suitable rating for each of the air-suction & discharge of condition space as well as injection of fresh air and emmission of stale air as per direction of EIC).The AHU Coil to be with hydrofolic coating. The addon suitable gadgets shall be a set of butterfly, Water Bypass System in case of partial load condition
The AHU Fan assembly should be either motor directly coupled with Impeller or Belt driven as per OEM standard suitable for air velocity range 7.3 - 8.2 ft./Sec through the multi-layer (6-8 row)12 mm - 19 mm dia Copper tubes with Alluminium Fins (as per OEM standard). The AHU shall consist of 1 no. Centrifugal Blower with 2 nos. (I W + lS) TEFC Squirell cage induction motor with Supply Air Damper. There should be AHU fans of Forward/ Backward Curve, with discharge not less than 10000 CFM, compatable for 415V, 50 Hz supply continuous duty Class IE 1 (Make for Fan Unit - Nicotra/ Kruger/ Caryaire) (Make for Motor - Crompton / Kirloskar/ NEC/ ABB/ Siemens).External Static pressure will be within 10 - 20 mm Wg. There should be electrical interlocking/switching arrangement for running the system in possitive or negetive pressure mode as per requirement.(Make : Zeco / System Air/ Edgetech/Daikin/Jaypee/Carrier India) (AHRI/EUROVENT CERTIFIED) --For ICU & HDU
SITC of site assembled type modular Single skinned construction with continuous insulation with thermal break. Outer skin has to be polymer coated and insulation panel should be made of thermal break profile - PUF insulation with thickness of at least 40mm or better. The AHU should have Heat Recovery ventilator or exchanger for extrating @ 960 CFM stale air with the arrangement of VCD and injection of fresh air @ 960 CFM with VCD and mixing chamber for return air and fresh air with 02 (Two) stage filtration system (Prefilter having efficiency (EU - 4/MERV7) 90% down to10 micron, Fine Filter having efficiency 95% down to 5 micron (MERV-14 (Make - FMI/ Spectrum/ Thermi) for both Inlet & Outlet including UV lamp of suitable rating for each of the air-suction & discharge of condition space as well as injection of fresh air and emmission of stale air as per direction of EIC).The AHU Coil to be with hydrofolic coating. The addon suitable gadgets shall be a set of butterfly, balancing & control valve with pressure Water Bypass System in case of partial load condition.
The AHU Fan assembly should be either motor directly coupled with Impeller or Belt driven as per OEM standard suitable for air velocity range 7.3 - 8.2 ft./Sec through the multi-layer (6-8 row)12 mm - 19 mm dia Copper tubes with Alluminium Fins (as per OEM standard). The AHU shall consist of 1 no. Centrifugal Blower with 2 nos. (I W + lS) TEFC Squirell cage induction motor with Supply Air Damper. There should be AHU fans of Forward/ Backward Curve, with discharge not less than 10000 CFM, compatable for 415V, 50 Hz supply continuous duty Class IE 1 (Make for Fan Unit - Nicotra/ Kruger/ Caryaire) (Make for Motor - Crompton / Kirloskar/ NEC/ ABB/ Siemens).External Static pressure will be within 10 - 20 mm Wg. There should be electrical interlocking/switching arrangement for running the system in possitive or negetive pressure mode as per requirement.(Make : Zeco / System Air/ Edgetech/Daikin/Jaypee/Carrier India) (AHRI/EUROVENT CERTIFIED) --For 24 Bed Ward
Ceiling Suspended Indoor type Air Handling Unit - SITC of site assembled type modular single skinned construction with continuous insulation with thermal break. The AHU enclosure's outer skin has to be polymer coated and insulation panel should be made of thermal break profile - PUF insulation with thickness of at least 40mm or better. Extrating stale air @ 100 CFM with the arrangement of VCD and injection of fresh air @ 90 CFM with VCD and mixing chamber for return air and fresh air with 03 (Three) stage filtration system (Prefilter having efficiency (EU - 4/MERV7) 90% down to10 micron, Fine Filter having efficiency 95% down to 5 micron (MERV-14) & Hepa filer 99% down to 0.3 micron (Make - FMI/ Spectrum/ Thermi). The addon suitable gadgets shall be a set of butterfly, balancing & control valve with pressure gauge & temparature gauge each AHU.
The AHU Coil to be with hydrofolic coating. The AHU Fan assembly should be either motor directly coupled with Impeller or Belt driven as per OEM standard suitable for air velocity range 7.3 - 8.2 ft./Sec through the multi-layer 12 mm - 19 mm dia Copper tubes with Alluminium Fins (as per OEM standard). There should be AHU fans of Forward/ Backward Curve, with discharge not less than 2000 CFM, compatable for 415V, 50 Hz supply continuous duty Class IE 1 (Make for Fan Unit - Nicotra/ Kruger/ Caryaire) (Make for Motor - Crompton / Kirloskar/ NEC/ ABB/ Siemens). External Static pressure will be within 10 - 20 mm Wg. (Make : Zeco / System Air/ Edgetech/Daikin/Jaypee/Carrier India) (AHRI/EUROVENT CERTIFIED) (--For Isolation Room 1 & 2)
Ceiling Suspended Indoor type Air Handling Unit SITC of site assembled type modular double skinned construction with continuous insulation with thermal break. The AHU enclosure's outer & inner Skin layer of 0.6 mm or higher & outer skin has to be polymer coated and insulation panel should be made of thermal break profile - PUF insulation with thickness of at least 40mm or better. Extrating stale air @ 350 CFM with the arrangement of VCD and injection of fresh air @ 350 CFM with VCD and mixing chamber for return air and fresh air with 02 (Two) stage filtration system (Prefilter having efficiency (EU - 4/MERV7) 90% down to10 micron & Fine Filter having efficiency 95% down to 5 micron (MERV-14) (Make - FMI/ Spectrum/ Thermi). The addon suitable gadgets shall be a set of butterfly, balancing & control valve with pressure gauge & temparature gauge each AHU.
The AHU Coil to be with hydrofolic coating. The AHU Fan assembly should be either motor directly coupled with Impeller or Belt driven as per OEM standard suitable for air velocity range 7.3 - 8.2 ft./Sec through the multi-layer 12 mm - 19 mm dia Copper tubes with Alluminium Fins (as per OEM standard). There should be AHU fans of Forward/ Backward Curve, with discharge not less than 3400 CFM, compatable for 415V, 50 Hz supply continuous duty Class IE 1 (Make for Fan Unit - Nicotra/ Kruger/ Caryaire) (Make for Motor - Crompton / Kirloskar/ NEC/ ABB/ Siemens). External Static pressure will be within 10 - 20 mm Wg. (Make : Zeco / System Air/ Edgetech/Daikin/Jaypee/Carrier India) (AHRI/EUROVENT CERTIFIED) (--For Pre & Post OT)
SITC of UVC Emitter for the above AHU'S for prevention of fungus in the child water coolong coils. The minimum UV intensity in in the coils should be greater than 1000 UW-SEC/CM2 for Ots. The unit shall be UL Listed(UL-1995)(Make-Alfa)
SITC of Aluminium laminar bench with perforated sheet cover to accommodate inside HEPA filter bank along with necessary support as per standard of minimum 6 ft X 8ft dimension for OT Area as per approved drawing necessary flange joints of air duct shall have to be fixed with sealant adhesive to prevent leakage.
Chilled water In-duct type Indoor FCU units with compact 3 Row Cu. cooling coil, multi-speed fan motor, the blower shall be dynamicaly balanced and designed for silent operation, the filters shall be washable synthetic media type arranged for convenient cleaning and replacement and inbuilt drain pump. The Unit should be equipped with Ball Valves / Stainer & Actuator as required. The unit is to be supplied with chorded remote controller. 2.5 TR (Make - Daikin/ Johnson Control/ EdgeTech/ Zeco/ VTS/ Citizen/Jaypee /Carrier India) (Allocation- LDR - 1&2-2 no each, Point Care Lab, USG, Doctor Room-GF, Proc. Room-1&2-1st Fl, Dialysis Room-2no, Doctors Room-1st Fl, Proc. Room-2nd Fl, Doc. Room-2nd Fl)
2 TR (Make - Daikin/ Johnson Control/ EdgeTech/ Zeco/ VTS/ Citizen/Jaypee /Carrier India) (Allocation- Procedure Room- 2nd Fl)
1.5 TR (Make - Daikin/ Johnson Control/ EdgeTech/ Zeco/ VTS/ Citizen/Jaypee /Carrier India) (Allocation- Minor Proc. Room, Radiology-2no.,)
Supply, erection, testing & commissioning of 2000 litre capacity PVC double-layer expansion / cushion tank, insulated with cover of thermocol, sand, cement plaster as per chilled water piping (Make - Syntex/ Patton/ Supreme), provision of make up water inlet, overflow outlet, Air release vent, etc.
Supply and Laying of Rigid PVC Drain Pipe (Medium Class)with respective fittings ,proper supports at 5 feet interval and duly insulated with 6 mm thick closed cell nitrile rubber insulation. (Make : Oriplast/ Supreme/ Filolex/ Ashirbad/ Astral) 20 mm NB
Supply and fixing of Flexible double Canvas connection in between each FCU & Al. Supply Air grill mounted on Gypsum Boxing cover. (Custom Make or Asper direction of EIC)
Supply & fixing of Al Powder coated extruded Alluminium return air grilles (Make : Premier/ Systemair/ Caryaire/ Air Enterprise) without volume control dampers.
Supply & fixing of Al powder coated extruded Alluminium Supply air grilles (Make : Premier/ Systemair/ Caryaire/ Air Enterprise) with alluminium volume control damper.
Major & minor civil works required to execute before and after the HVAC works for mending good damages to original finish painting.
SITC of GI DU CT of Class - VIII grade for supply/ return air duct along with pre fabricated plenum for supply and return air with necessary supports, flanges etc. as required and as per IS 655 and IS -277 standards of following gauges. (Make- Sail/Jindal/Tata)) 24 SWG thick
22 SWG thick
Supplying,fitting & fixing in position suspended boxing for (concentric) return and supply air arrangement for ducting incl false ceiling for boxing of IDU with frame work of aluminium hollow section of size 50mm X 25mm (2.0mm thickness) combined with aluminium corners of size 38mm X 25mm, suspended by aluminium hollow tube section of size 38mm X 25mm having size as suitable with aluminium composit panels (ACP) - Interior grade of thickness 3.0 mm comprising of proctective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent incl.suitable arrangement of grill fixing complete in all respect including all incidental charges etc. as per direction of EIC.
Supply and fixing acoustic lining of supply air duct and plenum with 13 mm thick open cell Nitrile rubber (Class-O) of density 140Kg/cum-160Kg/cum insulation with cadmium plated nuts, bolts, stick pins, CPRX compound etc. completed as per direction of EIC (Make-Accroflex/ K-flex/Armacell).
Supply and fixing Heat Retardant closed cell Class'O' 50 mm thick Nitrile Rubber insulation with AI Foil Faced Outside Supply Air duct. (Make-Armacell/K-flex /Accroflex)
Supply & Fixing of underdeck insulation with 50mm thick TF quality Expanded polysterene slab(Make-Thermowell/ Board sell)
Supply & Fixing of Motorised Fire Damper, Galvanized Steel Sheet with 125 GSM Zink Coated, Certified by CBRI ( U-555, 1995) with minimum fire rating not less than 120 min, must be Fusiable Link Spring with 74°C Temerature rating Ul Listed with actuator as per requirement. (Make-Greenheck/Systemair/Air master/Caryaire)
SITC of heavy duty anti vibrational pad to protect the system from any kind of unwanted vibration.
S & Laying of 1.1 KV Grade PVC/ XLPE insulated, PVC sheathed cable, copper unmoured control cable incl. to laid on wall surface by suitable clamping, proper glanding & finishing the cable ends with solderless sockets for following cables(Make-Gloster/Polycab/Havells) 7 Core 1.5 Sq. Sq.mm XLPE round copper Cable
4 Core 2.5 Sq. Sq.mm XLPE copper Cable
4 Core 16 Sq.mm XLPE Al. Armoured Cable
4 Core 10 Sq.mm XLPE Al. Armoured Cable
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. (i) With 25x25x3mm angle iron support 200x50x1.25mm (18SWG)
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections.
SITC of wall mounted AHU Electric control panel, having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 25 x 25 x 5 mm MS )angle.The panel is to be properly gasketed to prevent the dust & vermin. The panel consist of following accessories.
i)32A FP MCB- 1No. (L&T/ABB/Siemens) As incomer Bus Bar: 63 A Aluminium Bus bar -1 Set Out Going: i)25A FP MCB- 1No. (L&T/ABB/Siemens) ii) 6 A SP MCB -1No. (L&T/ABB/Siemens) iii) DOL Starter-1No. (L&T/ABB/Siemens) iv) 4Pole Power contactor-1 No. (L&T/ABB/Siemens) v) On delay timer-1no. (L&T/ABB/Siemens) vi) ON/OFF Push Button- 1 Set (L&T/ABB/Siemens) vii) LED indicationg Lamp ON/OFF-1Set
SITC of wall mounted AHU Electric control panel, having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 25 x 25 x 5 mm MS )angle.The panel is to be properly gasketed to prevent the dust & vermin. The panel consist of following accessories.
i)63A FP MCB- 1No. (L&T/ABB/Siemens) As incomer Bus Bar: 100 A Aluminium Bus bar -1 Set Out Going: i)63A FP MCB- 1No. (L&T/ABB/Siemens) ii) 6 A SP MCB -1No. (L&T/ABB/Siemens) iii) DOL Starter-1No. (L&T/ABB/Siemens) iv) 4Pole Power contactor-1 No. (L&T/ABB/Siemens) v) On delay timer-1no. (L&T/ABB/Siemens) vi) ON/OFF Push Button- 1 Set (L&T/ABB/Siemens) vii) LED indicationg Lamp ON/OFF-1Set
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: (a) By ISI-Medium GI pipe
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. Solid GI wire No. 4 SWG
Lyric International (BID ID -6285832)
ANAMICA ENTERPRISE (BID ID -6287660)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
BOQ.xls
BOQ • 0.28 MB
Tenderdocument.pdf
Tender Documents • 0.54 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .