Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹33,172
Closing Date
2 Mar 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Chief Engineer [C & O], Wanakbori TPS
Supply of Fire Alarm system spares at WTPS.
273066
WTPS/S/ET/01/2026/SUPPLY-10 RFQ NO-75147E
Open
Miscellaneous Goods
Supply
Kheda
7 documents required · 7 mandatory
₹1,770
GUJARAT STATE ELECTRICITY CORP. LTD. [NEFT/RTGS/online payment -PAYABLE AT BANK OF BARODA WTPS BRANCH]
₹33,172
9 Feb 2026
9 Feb 2026
9 Feb 2026
2 Mar 2026
9 Feb 2026
No. CODE Reqd.
MICROPROCESSOR BASED FIRE
1 2 Numbers
ALARM CONTROL PANEL
ACTIVE REPEATER PANEL FOR
2 FIRE ALARM MAKE :NOTIFIER BY 2 Number
3 Photo electric smoke detector 180 Number
ADDRESSABLE RATE OF RISE
4 30 Number
HEAT DETECTOR
ANALOUGE ADDRESSABLE
5 5 Number
MANUAL CALL POINT
6 HOOTERS 10 Number
FAULT ISOLATOR MODULE MAKE
7 8 Number
ADWARDS FOR AF OF CHP
ADDRESSABLE CONTROL
8 MODULE WITH FLASHSCAN 8 Number
MODEL:FCM-1 NOTIFIER MAKE
INTELLIGENT ADDRESSABLE
9 FIRE ALARM AND ANNUNCIATION 8 Number
DIGITAL TEMPERATURE
10 2 Number
CONTROLLER
Technical Specification of Material
Sr.No.-1 Intelligent Addressable Fire Alarm Control Panel,
Model No.: NFS
Make : NOTIFIER by Honeywell.
Microprocessor based 1 loop capacity analogue Addressable Fire Alarm Control Panel with minimum
80 characters LCD display, 800 event plus 200 alarm log history events, QWERTY keypad for
programming. The panel should be equipped with sufficient numbers of loops considering 20% spare
capacity in each loop. Each Loop shall have a capacity of minimum 300 analog addressable devices.
The panel shall work in degrade mode in case of CPU failure. Four access levels, flash EPROM,
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for
hours normal working and 30 mins in alarm condition. Designed to meet UL 864, 10th Edition.
(1) Certified for seismic applications when used with the appropriate seismic mounting kit.
(2) Approved for Marine applications when used with listed compatible equipment. See DN-
(3) One isolated intelligent Signaling Line Circuit (SLC) Class A, B, or X.
(4) Wireless fire protection using SWIFT Smart Wireless Integrated Fire Technology. See DN-
(5) Up to 159 detectors and 159 modules per SLC; 318 devices maximum.
(6) Detectors can be any mix of photo, thermal, or multi-sensor; wireless detectors are available
for use with the FWSG(A).
(7) Modules include addressable pull stations, normally open contact devices, two-wire smoke
detectors, notification, or relay; wireless modules are available for use with the FWSG(A).
(8) Standard 80-character display.
(9) Network options:
- High-speed network for up to 200 nodes (N16e/x, NFS2-3030,NFS2-640, NFS-320(C), NFS-
320SYS, NCD, NCA-2, DVC-EM,ONYX Works, NFS-3030, NFS-640, and NCA).
- Standard network for up to 103 nodes (N16e/x, NFS2-3030,NFS2-640, NFS-320(C), NFS-
320SYS, NCD, NCA-2, DVC-EM,ONYX Works, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-
300/400, AFP-1010, and AM2020). Up to 54 nodes when DVCE is used in network paging.
(10) 6.0 A power supply with four Class A/B built-in Notification Appliance Circuits (NAC).
(11) Built-in Alarm, Trouble, Security, and Supervisory relays.
(12) VeriFire Tools online or offline programming utility. Upload/ Download, save, store, check,
compare, and simulate panel databases. Upgrade panel firmware.
(13) Auto programming and Walk Test reports
(14) Multiple central station communication options:
(a) Standard UDACT
(b) Internet
(c) Internet/GSM
(15) 80-character remote annunciators (up to 32).
(16) EIA-485 annunciators, including custom graphics.
(17) Printer interface (80-column and 40-column printers).
(18) History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm- only
(20) Presignal /Positive Alarm Sequence (PAS).
(21) Silence inhibit and Auto Silence timer options.
(22) NAC coding functions:
(23) March time.
(24) Temporal
(25) California two-stage coding.
(26) Canadian two-stage.
(27) Strobe synchronization.
(28) Optional cloud connectivity for remote off site monitoring through CLSS (see HON-62034)
(29) Monitor multiple buildings through one off-campus central station,and report through the CLSS
(30) Optional remote programing through CLSS
(31) Field-programmable on panel or on PC with VeriFire ? Tools program check, compare, simulate.
(32) Full QWERTY keypad.
(33) Battery charger supports 18 ? 200 AH batteries.
(34) Non-alarm points for lower priority functions.
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
(35) Remote ACK/Signal Silence/System Reset/Drill via monitor modules.
(36) Automatic time control functions, with holiday exceptions.
(37) Extensive, built-in transient protection.
(38) Powerful Boolean logic equations
Power Supply : 240 V AC power supply
Make : NOTIFIER by Honeywell only
Model No.: NFS
Sr.No.- 2 Active Repeater Panel
Model No.: LCD2
Make : NOTIFIER by Honeywell
Active Repeater Panel with 80 Characters Liquid Crystal Display with backlit control.
(1) 80-character backlit Liquid Crystal Display (20 characters x 4 lines).
(2) Display mimics panel or NCA:
- Event message.
- 20 characters for point label.
- 12 characters for extended label.
- Time, date and point address.
(3) Control switches for System Acknowledge, Signal Silence Drill and System Reset.
(4) LEDS for general off-normal events with UL 864 9th Edition Panels.
NOTE: The LEDs are only applicable when used with UL864 Ninth Edition listed panels: NFS-320,
NFS2-640, NFS2-3030, and NCA-2.
(VeriFire Tools 6.90 or higher required to program points.)
(6) Up to 6000 foot segments between units.
(7) Local piezo sounder with alarm/trouble resound.
(8) Displays all analog, addressable points.
(9) Displays device type identifiers.
(10) Displays device and zone custom alpha labels LCD2-80 mounts with any CHS-4 chassis slot
(11) Slide-in label can be customized.
(12) Flush/surface/panel mount option.
(13) LCD2-80 displays time, date, and custom messages received from the compatible panel or
network annunciator.
(14) LCD2-80 is 8.25" (20.96 cm) high, 4.375" (11.11 cm) wide, and 1.75" (4.45 cm) deep.
(15) Up to 32 LCD2-80s may be used on one EIA-485 circuit.
Power Supply : 24 V DC
Make : NOTIFIER by Honeywell only
Model No.: LCD2
For Item Sr.No:-3 Addressable Photoelectric Smoke Detector
Model No.: FSP
Make: NOTIFIER by Honeywell.
Addressable Photoelectric Smoke Detector with sensitivity range of 0.5 to 4.0% obs/ft. The detector
shall have group decision technology for faster response & avoid false alarms. The detector shall have
twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches.
Designed to meet UL268, 7th Edition. The intelligent photoelectric smoke detector shall use the
photoelectric (light-scattering) principal to measure smoke density and shall, on command from the
control panel, send data to the panel representing the analog level of smoke density.
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
A.SLC LOOP:
(1) Two-wire SLC loop connection
(2) Unit uses base for wiring
(3) Compatible with Flash Scan and CLIP protocol systems
(4) Stable communication technique with noise immunity
B. ADDRESSING:
(1) Addressable by device
(2) Rotary, decimal addressing (Refer to the NOTIFIER panel manuals for device capacity.)
C. ARCHITECTURE:
(1) Sleek, low-profile, stylish design
(2) Unique single-source design to respond quickly and dependable to a broad range of Fires.
(3) Integral communications and built-in device-type identification
(4) Built-in tamper resistant feature
(5) Remote test feature from the panel
(6) Walk test with address display (an address on 121 will blink the detector LED: 12- [pause]-1
(Flash Scan systems only)
(7) Built-in functional test switch activated by external magnet
(8) Removable cover and insect-resistant screen for simple field cleaning
(9) Expanded color options
D. OPERATION:
(1) Designed to meet UL 268 7th Edition
(2) Factory preset at 1.5% nominal sensitivity for panel alarm threshold level.
(3) LED blinks when the unit is polled (communicating with the fire panel) and latches in alarm.
(4) Low standby current
E. MECHANICALS:
(1) Sealed against back pressure
(2) SEMS screws for wiring of the separate base
(3) Designed for direct-surface or electrical-box mounting
(4) Plugs into separate base for ease of installation and maintenance
TECHNICAL SPECIFICATION
1. Designed to meet UL268 7th Edition.
2. Modern profile with White color for improved aesthetics.
3. Sensitvity Range of 0.5% to 4.0% obs/ft
4. Stable communication technique with noise immunity.
5. Low standby current. 200 micro Amps @ 24 VDC
6. Two-wire SLC connection.
7. Rotary, decimal addressing
8. Dual bi-color LED design providing 360 viewing angle.LEDs blink green in normal condition and
illuminate steady red on alarm
9. Remote test feature from the panel.
10. Walk test with address display
11. Built-in functional test switch activated by external magnet.
12. Built-in tamper-resistant feature.
13. Sealed against back pressure.
14. Expanded color options.
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
15. Optional relay, isolator, and sounder bases.
For Item Sr.No:- 4 Addressable Rate of Rise Heat Detector
Model No.: FSP 951 R
Make : NOTIFIER by Honeywell
Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min. The detector shall have twin bi-colour
LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches.
The intelligent thermal detectors shall be addressable devices rated at 135 degrees Fahrenheit (58
degrees Celsius) and have a rate-of-rise element rated at 15 degrees F (9.4 degrees C) per minute. A
high heat thermal detector rated at 190 degrees Fahrenheit (87.8 degrees Celsius) shall also be
available. The thermal detectors shall connect via two wires to the fire alarm control panel signaling line
A.SLC LOOP:
(1) Two-wire SLC loop connection
(2) Unit uses base for wiring
B. ADDRESSING:
(1) Addressable by device
(2) Rotary, decimal address in (Refer to the NOTIFIER panel manuals for device capacity.)
C. ARCHITECTURE:
(1) Designed to meet UL 268 7th Edition
(2) Sleek, low-profile, stylish design
(3) State-of-the-art thermistor technology for fast response
(4) Integral communications and built-in device-type identification
(5) Built-in tamper resistant feature
(6) Built-in functional test switch activated by external magnet
D.OPERATION:
(1) Fixed temperature model (FST-951) factory preset to 135 F (57C)
(2) Rate-of-rise model (FST-951R),15 F (8.3 C) per minute
(3) High-temperature model FST-951H) factory preset to 190 F (88 C)
(4) 360 deg field viewing angle of the two visual alarm indicators, LEDs blink red in Normal condition
and turn on steady red in Alarm
(5) LEDs blink every time the unit is polled
E. MECHANICALS:
(1) Sealed against back pressure
(2) SEMS screws for wiring of the separate base
(3) Designed for direct-surface or electrical-box mounting
(4) Plugs into separate base for ease of installation and maintenance
(5) Separate base allows interchange of photoelectric, ionization and thermal sensors
F.OTHER SYSTEM FEATURES:
(1) Remote test feature from the panel
(2) Walk test with address display
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
(3) Low standby current
G.OPTIONS:
(1) Remote LED output connection to optional RA100Z remote LED annunciator
TECHNICAL SPECIFICATION
1. Modern profile with White color for improved aesthetics.
2. Advanced thermal technology for fast response.
3. Fixed temperature model factory preset to 135 F
4. Rate of Rise model preset to 15 F/min
5. High temperature model factory preset to 190 F
6. Low standby current. 200 micro Amps @ 24 VDC
7. Two-wire SLC connection.
8. Rotary, decimal addressing
9. Dual bi-color LED design providing 360 viewing angle.LEDs blink green in normal condition and
illuminate steady red on alarm .
10. Remote test feature from the panel.
11. Walk test with address display
12. Built-in functional test switch activated by external magnet.
13. Built-in tamper-resistant feature.
14. Sealed against back pressure.
15. Optional relay, isolator, and sounder bases.
For Item Sr.No.5 Supply of Intelligent Addressable Manual Pull Station,
Make: Notifier
Model: NBG -12 LX
For Item Sr.No.6 Supply of Hooter, Make: Notifier, Model: HR/P2RL
For Item Sr.No.7 Supply of Fault Isolator Module , Make: Notifier, Model: ISO- X
For Item Sr.No.8 Supply of Intelligent Addressable Control Module, Make: Notifier, Model:
For Item Sr.No.9 Supply of Intelligent Addressable Monitor Module, Make: Notifier,
Model: FMM-1
For Item Sr.No.10 Supply of Digital Tempreture Controller, Make:-Masibus, Model:-5006-
RN, Control Type-On-Off, Output Type-Relay, Input Type-RTD, ISO
Latest Certification of Manufacturer-Yes, Performance Parameter:-Frequency-50 Hertz &
Voltage-230 Volt & Dimensions-Size (mm) 96 x
GENERAL TERMS AND CONDITION
1) Bidder should must produce certificate of Authorized Dealership Certificate of Notifier, Honywell.
OR You have to submit Manufacturers Authorization form (MAF) of Notifier, Honywell.
2) Bidder should submit the LATEST product catalogue & detailed specification of offered
materials along with the offer.
3) Material should be offered and supply as per our technical specification and Make and Model
4) Party has to submit Guarantee / Warranty certificate for supply of materials against the any
Manufacturing defect / poor workmanship / faulty design for the period of 12 months along with
the supply.
5) In case of any defects reported to Bidder / contractor the same should be replaced /rectified
within 15 days without any extra cost.
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
6) Payment will be released as per GSECL standard terms and conditions as after supplying of
material at WTPS main store.
7) Bidder shall have to submit the sample before bulk supply for approval. (For Item Sr.No.-
8) Bidder shall have to submit the test certificate before bulk supply for approval.(For Item
9) The supply material should be one to one replacement with existing system.
10) The supplied material along with sample should be marked / embossed with manufacturing
brand name / trade mark &, without which material will be rejected.
11) Delivery period: Within 3 Months from date of LOI.
Chief Engineer (C&O)
GSECL, WTPS
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
DECLARATION FORM
ON LETTER HEAD OF SUPPLIER
Subject: Supply of Fire Alarm system spares at WTPS.
Reference No.:- WTPS/S/TECH/RFQ - 75147E/EMD Colony
1. I/We hereby declare that I/We have carefully & thoroughly studied the entire tender placed on
the website and General terms & conditions, technical specification, PQR and other documents
of the tender mentioned under reference along with the Commercial terms and conditions.
2. I/We hereby confirm and certify that the offer submitted by me/us is strictly in accordance with
the GSECL’s Tender specifications, Guaranteed Technical Particulars and drawing as
mentioned in the Tender Specifications. There is no commercial or Technical deviation (except
the deviations shown in respective Annexure-12 of Technical Deviations of this tender
document) in the offer from the Board’s Tender Specification. I undertake to abide by the
GSECL’s Technical specification / Guaranteed Technical Particulars / Drawing, I undertake to
supply materials strictly as per the GSECL’s Technical specification / Guaranteed Technical
Particulars / Drawing, even if any technical deviations are mentioned by me. I also undertake
to abide by all commercial conditions of the GSECL, including delivery schedule. I have
submitted all the annexure-1 to 15,form of integrity pact etc along with the technical Bid dully
filled along with all the details”
3. I / We, hereby declare that our Technical Bid is strictly in line with the Tender specifications
(except the deviations shown in Annexure-12 of Technical Deviations of this tender document).
4. I / We also agree that additional conditions / deviations, if any, found in the Commercial terms
& conditions (except the deviations shown in Annexure-12 of Technical Deviations of this
tender document) our offer shall be out rightly rejected without assigning any reason thereof.
5. I/We hereby abide to execute the contract agreement & submitted the same along with the
acceptance of LOI and the same will be acceptable to me/us.
6. I/We hereby accept and confirm that any dispute on this regard shall not be entertained by the
7. The full value of the “Earnest Money Deposit” paid herewith should be absolutely forfeited to
the Corporation, should I/ we do not deposit the specified amount of specified Security Deposit
within 10 Days from receipt of the Letter of Intent.
8. If, I fail to submit all required documents with application or tender copy ( in each tender ) then
my tender will be cancelled, which is binding to me.
authorized signatory of M/s ______________________________________________ here by
certify that M/s _________________________________________________ and their
proprietor / any partner / any directors of the firm is not stop deal and / or banned for business
dealing and / or black listed by GUVNL and / or their any subsidiary company viz. GSECL /
GETCO / DGVCL / MGVCL / UGVCL / PGVCL as well as Government and / or Semi
Government company / department.
10. We here by confirm that we have not stake in one or more other agencies / bidders who are
participating in same tender and if it is found that the submitted information / declaration are
wrong in the tender / enquiry as stated in tender terms, than we will be disqualified
automatically &it will be accepted to us. EMD / SD will be forfeited. More over if GSECL shall
take stern action including stop dealing with our firms which is also accepted to us
Seal of the Firm Signature of the Tenderer with Designation.
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
<On the letterhead of the vendor/ payee>
To, Date : __________
Subject : Declaration for TDS/TCS under the Income Tax Act (IT Act)
Reference : Provisions of S. 206AB/ 206CCA/139AA of the IT Act
Dear Sirs,
This is with reference to the determination of appropriate Tax deduction at source (TDS) or Tax
collected at source (TCS) as per the provisions of the Act i.e. Section 206AB/ 206CCA/139AA of the IT
Act. In relation to the said provision of the Act: I / We, having status of <<mention status i.e.
Individual/Company/ Firm etc.)>>hereby declare and confirm that: -
a) I/We have<<mention PAN>>Permanent Account Number (PAN) under the IT Act.(Copy of
PAN card is enclosed herewith.)
b) I/We have linked / will be linking Aadhar number with PAN as required under section 139AA (2)
read with Rule 114AAA.latest by 30th June
c) I/We have/have not filed income tax returns (ITR) for two previous years immediately prior to
the year in which tax is required to be deducted and for which last date of filing of income tax
return is expired u/s139(1) of the Act.
I/ We am/ are hereby attaching a copy of acknowledgment of ITR filed for any one of previous
two financial years of which due date u/s139(1) is expired, as proof of filing ITR. (Strike out full
sentence if not filed IT returns)
d) The aggregate amount of Tax Deductible at Source (TDS) and Tax Collectible at Source (TCS)
exceed/don’t exceed Rs. 50,000 or more in each of the two aforesaid previous years in my/our
case (Vendor has to provide the extract of its Form 26AS if copy of ITR is not provided as
e) I/ We shall, indemnify the Company for any consequences arising out of any acts of commission
or omission including incorrect declaration basis which the Company would act upon.
I/We agree that Company shall determine applicability of section 206AB/206CCAof the IT Act
based on the aforesaid declaration/documents filed by me/us and would deduct TDS/TCS
accordingly. The decision of Company shall be final and acceptable to me/us. Strikeout
whichever is not applicable.
Thanking you,
Yours faithfully,
<<Signature>>
< Full Name of Vendor & seal >
BIDDER’S SIGN WITH SEAL
RFQ- 75147E Page
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NIT - RFQ- 75147E -EMD COLONY.pdf
TECHNICAL BID - RFQ- 75147E -EMD COLONY .pdf
Document
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .