| 1 | L1₹13.0 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹13.6 L+₹66,597.20 (5.13%)Rejected-Finance | L2 | Rejected-Finance Not being lowest | |
| 3 | L3₹13.9 L+₹95,575.80 (7.36%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L3 | Rejected-Finance Not being lowest | |
| 4 | Rejected-Technical | - | Rejected-Technical The firm has not been enlisted in the requisite category i.e. Category b(ii) as per NIT. |
Tender Value
Refer Docs
EMD Value
₹26,400
Closing Date
22 Oct 2022, 6:00 pmClosed
CWE Ambala
Headquarter Commander Works Engineer Ambala Mansfield Road Ambala Cantt
PROVISION OF 200 KVA TRANSFORMER ALONGWITH CONNECTED WORKS FOR SMR UNDER GE (UTILITY) AMBALA
2022_MES_553290_1
CWE/AMB/UTILITY-27 OF 2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Ambala Cantt
All as per tender documents
9 documents required · 9 mandatory
₹500
GE UTILITY AMBALA CANTT
₹26,400
Yes
15 Dec 2022
21 Sept 2022
24 Oct 2022
21 Sept 2022
22 Oct 2022
10 Oct 2022
21 Sept 2022 - 8 Oct 2022
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes,for under ground cable / erection of poles, stays, locating fault of LT Cable and stay assembly and in other situation not exceeding 10 Square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and as directed.
All as per item No. 1.00 here-in-before but depth exceeding 1.5 metre & not exceeding 3.0 metre complete all as specified and as directed.
Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed.
Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Supply and laying of un-reinforced precast concrete cable cover ,class HVP, type-1 with peak, size 300X180X40mm complete all as specified and directed.
Supply and laying of un-reinforced precast concrete cable cover ,class LV, type-1 with peak, size 250x150x40mm complete all as specified and directed.
Material and labour for Sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and as directed. Note:- Punned thickness 18cm shall be measured for payment purposes.
Supply, Installationg, testing and commissioning of air breaker gang operater triple switch ( GODO) outdoor type, vertical mounting type of capacity 200 Amp with drop out fuse consisting 12 insulators ISI marked mechanically operated mounted on insulator and frame work with operating GI rods and mechanical work from ground level with locking arrangement including Godrej pad lock with two keys complete with fuse carried and HT fuse element having upto 200 Amp rating suitable for HT 11 KV 50 HZ AC supply including necessary electric connection complete all as specified and directed .
Material and labour for earthing complete with galvanised earth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 25x6 mm GI strip earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore (light grade) and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe (light grade) for watering and 40mm bore GI protection pipe, funnel, wire mesh, cast iron cover and frame etc, complete, all as specified or indicated and as directed including testing on completion complete all as specified and directed. Note : The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way.
Supplying and laying of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 11000 Volts grade, cross sectional area 95 Sqmm 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part - 2 for insulation and for conductors Class 2 to IS 8130 - 84, in trenches, floors, ducts passing through pipe for road crossing etc., complete all as specified and directed. Note : Excavation, earth work, cable cover protection, sand cushioning and GI pipe etc shall be measured & paid for separately.
Supplying and laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 1100 Volts grade, cross sectional area 150 Sqmm 3.5 core, suitable for 1.1 KV earthed system, in trenches, floors, ducts passing through pipe for road crossing etc, including connecting and testing complete all as specified and directed. Note : Excavation, earth work, cable cover protection, sand cushioning and GI pipe etc shall be measured & paid for separately.
Supplying and laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 1100 Volts grade, cross sectional area 240 Sqmm 3.5 core, suitable for 1.1 KV earthed system, in trenches, floors, ducts passing through pipe for road crossing etc, including connecting and testing complete all as specified and directed. Note : Excavation, earth work, cable cover protection, sand cushioning and GI pipe etc shall be measured & paid for separately.
Supplying and laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 1100 Volts grade, cross sectional area 16 Sqmm 4 core, suitable for 1.1 KV earthed system, in trenches, floors, ducts passing through pipe for road crossing etc, including connecting and testing complete all as specified and directed. Note : Excavation, earth work, cable cover protection, sand cushioning and GI pipe etc shall be measured & paid for separately.
Supply and fixing LT feeder pillar panel size 1.2 mtr x1.2 mtr x50Cm with out door type cubical panel board outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front and rear openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI for 35 MVA rupturing capacity at 415 Volts factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 and LT panel shall be tested from CPRI type test for 4000 Amp with breaking capacity not less than 65 KA and IP 56 as confirming to IS- 61439/2011 Part I and Part 2 type test certificate comprising of the following :- (a) TPN Aluminium bus bar 630 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators not less than 1.0 mtr long (b) Incoming MCCB 400 Amps 4 pole 415 Volts AC with thermal magnetic adjustable type 36 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier complete all as directed. - 01 No
Supply, installation, testing and commissioning of step down transformer out door type complete with standard fittings and accessories, HT 11 KV 3 Phase, LT 433 Volt, 3 Phase 4 wire with off load tap changer on primary side to carry secondary voltage + 5% to -10 with tappings at every 2.5 % all as per IS 1180 Part-I (2014 , With Latest Amendment) Level-2, for Transformer manufacturing and all as per IS 2026 for Transformer Testing, Energy Efficiency Level – 2 of capacity 200 KVA, copper wound, oil cooling with fins vector group : DYn 11, including initial oil filling (oil confirming to IS 335 and ISI Mark) complete all as specified including the following accessories :- (a) Three Nos porcelain bushing HT 11 KV with brass bushing rods, nuts, bolts & washers etc inside cable end box. (b) One cable box LV side consisting of 4 Nos porcelain with brass bushing rods complete with nuts and washers suitable for runs of 3.5 core LT UG cable. (c) Oil conservator with filler type drain valve and oil level gauge. (d) Dehydrating breather with first fill of dehydrating agent. (e) Explosion vents. (f) Thermometer pocket on tank cover. (g) One No 100mm dia, dial type thermometer vapour pressure type having range 0 to 120 degree centigrade.
(h) Rating plate and terminal marking plate (j) Earthing arrangement.(k) Oil level gauge. (l) Oil drain filter valve. (m) Oil drain valve. (n) Lifting hook. (o) Oil conservator with filling hole and cap. (p) Air relief valve plug. (q) Four plate solid cast steel detachable rollers. (r) Earth bushing for neutral outside the cable box for providing independent earthing for neutral. (s) Necessary channel on foundation for fixing the transformer with joint and stopper. Note :- The transformer should be Star rating and energy conservation (Energy conservation Binary Corps) for which necessary test certificate to be produced by contractor from manufacturer of the trasformer.
Supply and fixing of GI tubing, 80mm bore, light grade, on poles/on walls/under floors/ road crossing as required at site complete all as specified and directed. Note : Clamps. Nuts bolts, saddle etc will be measured and paid seperately.
Material and labour for cable end termination jointing kit , LT 1.1 KV, earthed system, (heat shrinkable), outdoor type joint complete with jointing material and accessories suitable for LT XLPE cable of size 240 sqmm 3.5 core 1.1 KV grade earthed system complete all as specified and as directed.
Material and labour for cable end termination jointing kit , LT 11 KV, earthed system (heat shrinkable), outdoor type joint complete with jointing material and accessories suitable for LT XLPE cable of size 120-150 sqmm, 3.5 core, 11 KV grade, earthed system complete all as specified and as directed.
Material and labour for cross arms,bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and as directed.
Material and labour for PCC 1:4:8 type D-2 (using 40 mm graded mechanically crushed stone aggregate), as in foundation filling and mass concrete, complete, all as specified and as directed.
Supply and fixing in replacement of lightning arrestor, expulsion type, suitable for 11000 volts, with all fittings, trasmission class, discharge capacity 65 KA, including connecting with HT line complete all as specified and as directed.
Material and labour for brick work, using sub class ‘B’ bricks, straight or curved on plan to any radius, exceeding 6mtr mean radius, built in cement mortar 1:6 complete all as specified and as directed.
Material and labour for 100 mm thick PCC (1:2:4) type B-2, using 40 mm graded mechanically crushed stone aggregates, as in floor, finished even and smooth without using extra cement complete all as specified and as directed.
Material and labour for hardcore of broken bricks filling of gauge not exceeding 63 mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and as directed.
Material and labour for rendering 10 mm thick on surfaces of brick work or concrete surfaces, in cement mortar 1:4, finished even and smooth without extra cement complete all as specified and as directed.
Excavating in post holes or similar holes, each not.exceeding 0.5 cu mtr, getting out, in soft/loose soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering, and removing surplus soil to a distance not exceeding 50m and making good surface complete all as specified and directed.
Supply and fixing of rolled mild steel angle iron posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc. and similar work conforming to Fe-290 Gde E-165 etc. complete all as specified and directed.
Material and labour for mild steel bolts, purpose made, with hexagonal or square head one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, dia of shank 5 to 10mm and length of bolt exceeding 5cm and not exceeding 10cm complete all as specified and directed.
Supply only 4 / 5mm dia galvanised mild steel wire chain link fencing of mesh size 50 to 100mm, complete all as specified and directed.
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. with and including MS binding wire complete all as specified and directed.
M&L for Plate girder or single stanchions built up of one beam or channel, section with flange plates, caps, bases. splices, angle brackets,cleats and other connections (Mild steel flat iron fillets for securing wire mesh etc.) including all necessary drilling, bolting or riveting and painting on MS work etc., and similar work conforming to Fe 410-O or Fe 310-O. complete all as specified and as directed.
Material and labour for preparation of new steel surfaces, of any description not otherwise described, over 10 cm width or girth and applying two coats of approved colour synthetic enamel paint, over a coat of red oxide zinc crome primer complete all as specified and as directed.
Material and labour for mild steel round bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips 10mm dia round bars confirming to Fe 500/550 D as in stiffeners to chain link fencing complete all as specified and as directed.
Supply and fixing on load change over switch with sheet steel enclosure 415V, 4 pole, 400 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cables from LT panels to change over switches complete all as specified and as directed.
Supply and erect steel tubular swaged HT poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified, type 410 SP-55 (11.0 metres long), conforming to IS-1678 and including two coats of synthetic enamel paint marking five numbers alternate black and white strips of 30cm height each from coping of the pole, complete all as specified and directed. Note: Excavation and earth wok and PCC for foundation, channel, clamps nuts, bolts to be measured and paid separately
Material and labour for earthing complete with galvanised earth plate electrode 600mm x 600mmx 6mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 4.00 mm GI wire earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 15mm dia (medium grade) and connected to main switch or main control board all as shown in Electrical Plate No.3 of SSR Part-I & including necessary excavation and earth work in any type of strata, PCC (1:3:6) type C1 in pit, RCC cover slab 50mm thick in 1:2:4 type B-1 using 8mm dia TMT bars @10cm c/c both way with one 8mm dia bar as handle for lifting, 20mm dia GI medium grade watering pipe, funnel, wire wesh, charcoal or coke & salt in alternate layers, etc.all as indicated including testing on completion complete all as specified and directed.
Material and labour for PCC 1:3:6 type C-1 (using 20 mm graded mechanically crushed stone aggregates) as in fixing of hold fast, coping of pole and strut, bed plates and the like, finishing the surface fair and even, including necessary form work, complete, all as specified and as directed. Material and labour for PCC 1:3:6 type C-1 using 20mm graded aggregate mechanically crushed stone for mass filling in stay pits and pole foundation all as specified.
Material and labour for cable end termination jointing kit, HT 11 KV, earthed system (heat shrinkable), outdoor type joint complete with jointing material and accessories suitable for HT XLPE cable of size 50-95 sqmm, 3 core, 11 KV grade, earthed system complete all as specified and as directed.
Material and labour for aluminium conductor steel reinforced (ACSR) weasel/ squirrel conductor, including fixing, stretching on poles and proper noseling with binding wire with insulator of any size as required at site complete all as specified and directed.
BAL SINGH & SONS
Raman Electric Trading Co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .