HQ CWE (AF) Bareilly
HQ CWE (AF) Bareilly-243002
REPAIRS AND PREVENTIVE MAINTENANCE OF VARIOUS POWER DISTRIBUTION TRANSFORMER RMU VCB WITH REPLACEMENT OF HT JOINT CABLES CALIBRATION AND TESTING OF HT PANEL ETC AT AF STN BAREILLY
2022_MES_550969_1
81324/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bareilly
As per NIT
8 documents required · 8 mandatory
₹500
GE (AF) Bareilly
₹45,000
Yes
4 Nov 2022
9 Sept 2022
8 Oct 2022
9 Sept 2022
6 Oct 2022
24 Sept 2022
10 Sept 2022 - 19 Sept 2022
Amount
Servicing of HT panel , detection of defective components, replacement of worn out parts and servicing/ cleaning of mechanical components after drawout of VCB trolly and Testing for smooth operation manual/ remote after caliberation of relay trough OEM of VCB/Test wing of UPPCLand resetting & generation of testing report by the primary injection set for 11 KV VCB for OC/EF ,parameter of relay setting for healthy system, complete all as specified and directed by Engr-in-Charge. Note: (i) Worn out minor parts shall be deemed to included in quoted rate. (ii) Major parts shall be measured and paid separately
Supply only following spare parts for VCB of any make all as specified :-
(a) Spring Charging Motor of VCB 110 V-230 Volt AC supply for the opening and closing of contacts complete all as required and directed at site complete all as per sample.
(b) Indicating lamp LED complete all as specified and directed.
(c) Space heater 60 watt 230 Volt AC supply with thermostat complete all as specified and directed.
(d) Digital multifunction meter 96x96 mm Range 0-300-150 /A Model type 3 phase 4W EN 8400class 1.0, aux supply 110Volt with RS 485 port complete all as specified and directed.
(e) Digital Voltmeter (0 to 12 KV size 96x96 mm class 0.5 , PTR 11000/rt3/110/rt3 complete all as specified and directed.
Horizontal boring under Road, pavement, hard standing complete for inserting GI pipe light grade of size 80/100 mm dia all as specified and directed. Note :- GI pipe shall be measured and paid seperately
M & L for 80 mm dia of Tubes light grade galvanised with all fitting laid in trenches or inserting in horizontal boring complete all as specified and as directed.
Detection of pin point fault in HT cable 33 KV (burried in ground/under road/path up to depth of 1.5 m) by cable fault locating machine comprising impulse generator,acoustic fault locator and reflectometer (laptop based) complete all as specified and as directed by Engr-in-Charge. Notes-(i) Cable fault locating machine to be arranged at site with in 12 hrs after intimation (ii) Earth work will be measured seperatly. (iii) Cost of transpotation in unit rate is deemed to be included.
Supply and laying or fixing jointing and testing 11 KV (E) system XLPE insulated, screened , PVC bedded, galvanised steel strip or wire armoured, electric power cables ISI 7098 marked with aluminium conductor, 11000 Volts ( earthed), laid under floor/ground or fixed on wall complete of cable size 95 Sqmm 3 core complete all as specified and directed.
Laying , jointing and testing OLD 11 KV (E) system XLPE insulated, screened , PVC bedded, galvanised steel strip or wire armoured, electric power cables( heavy duty) ISI 7098 marked with aluminium conductor, 11000 Volts ( earthed), laid under floor/ground or fixed on wall complete of cable size 95 Sqmm 3 core complete all as specified and directed.
M&L cable jointing kit for 11 KV (E) grade cable for indoor end termination heat shrink type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 95 sqmm 3 core complete all as specified and directed.
M&L cable jointing kit for 11 KV (E) grade cable for out door end termination heat shrink type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 95 sqmm 3 core complete all as specified and directed.
M&L cable jointing kit for 11 KV (E) grade cable for straight through heat shrink type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 95 sqmm 3 core complete all as specified and directed.
M&L cable jointing kit for 33 KV (E) grade cable for out door end termination heat shrink type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 300 Sqmm 3 core complete all as specified and directed.
M&L cable jointing kit for 33 KV (E) grade cable for out door straight through heat shrink type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 300 Sqmm 3 core complete all as specified and directed.
M&L for Painting of 33/11 KV Main Receiving Station switch yard including preparation of surface of Steel Structure , removal of dust etc and applying two coat of aluminium paint complete all as specified and directed.
Handling, transportation of transformers of capacity 1000 KVA of any make, model & type including hoisting, taking down from pole (pole mounted) or plinth mounted by any means mechanically pulley/mechanical crane, transportation to workshop for repair/maint. Reinstallation of Transformer in position pole mounted/plinth mounted including connecting all cable, earth lead, clamps and channels etc as per site requirement all as directed by Engineer-in-Charge. Note : If any damage to transformer/OH line/cables occur during handling, transportation or during hoisting/lifting, the same will be rectified by the contractor without any extra cost to the department.
Handling, transportation of transformers of capacity upto 500 KVA of any make, model & type including hoisting, taking down from pole (pole mounted), plinth mounted by any means mechanically pulley/mechanical crane, transportation to workshop for repair/maint. Hoisting/lifting and fixed in position pole mounted/plinth mounted including disconnecting and connecting all cable, earth lead, clamps and channels etc as per site requirement complete all as directed by Engineer-in-Charge. Note : If any damage to transformer/OH line/cables occur during handling, transportation or during hoisting/lifting, the same will be rectified by the contractor without any extra cost to the department.
Disconnecting the transformer of capacity 63 to 500 KVA indoor/outdoor from HT/LT side carefully at site, for top overhauling of transformer dismantling carefully and removing primary and secondary terminals, top cover, conservator tank, neutral earth strips and draining out transformer oil to the required level and storing carefully in cleaned containers, cleaning of terminals, supply and replacing the 5 mm thick rubberised cork sheet gasket for tank top cover, repair of transformer oil leakages from HT/LT bushing,and reassembling the complete, reconnecting the HT/LT supply cable ends at the site and testing complete all as specified and directed.
M&L for changing of Old / Burnt Copper HV winding by new EC grade copper coils with complete including insulation material of transformer complete all as specified and directed.
M&L for changing of Old / Burnt Copper LV winding by new EC grade copper coils including striping out of Insulation of LV Windings and reinsulation of Coil with insulating material of transformer for any type and capacity of transformers complete all as specified and directed by Engr-in-Charge.
Labour only for opening of top cover and allied parts of transformer of cap up to 500 KVAlifting of Core for repair , preheating charges for copper coils, assy of core coil assy including assy of copper coils, Tapping connections , insulation on Tap leads with insulation paper ,star connection by new EC grade copper on HV & LV side ., Baking charges for transformer job for each proper IR value in vacuum Chamber ( Auto Clave ) , refitting of HV / LV bushing and transformer accessories with top cover, M& L for painting of transformer tank having hot oil resistant paint inside complete all as specified and directed.
M&L Transformer oil having di-electric strength of 40 to 60 KV as per IS complete for top up/ replacement all as specified and as directed by Engr-in-Charge. (Oil should be supplied in sealed barrel of Power/Transol brand) Note: oil shall be filled in the transformers/stabilizers to be repaired or installed at site at different locations.
Dehydration/Filteration of transformer oil at site by means of centrifuging machine in order to improve dielectric strength of oil as per IS-355. Breakdown voltage should not be less than 50 KV complete all as specified and directed.
Supply and fix LV porcelain bushing of transformer 1.1KV/250 Amp with metal parts brass as per IS 3347 part iii and 4 Nos hexagonal nuts, complete all as specified and directed.
all as per ser item No 22 hereinbefoe capacity 1.1KV /400 Amp
all as per ser item No 22 hereinbefoe capacity 1.1KV /630 Amp
all as per ser item No 22 hereinbefoe capacity 1.1KV /1000 Amp
Supply and fix HV porcelain bushing of transformer 12KV /250 Amp with metal parts brass as per IS 3347 part iii and IS 2009, complete all as specified and directed.
M&L for hammer tone spray painting of transformer 11 KV/433 volts indoor/outdoor type of capacity 63 KVA to 100 KVA, including cleaning, scraping of exposed surfaces with shade as approved including writing MES number and machine number with black paint, letters 15mm wide and 50mm height complete all as specified and directed.
All as per item No 27 but here in before of Capacity 125 KVA to 250 KVA
All as per item No 27 but hereinbefore of Capacity 300 KVA to 400 KVA
All as per item No 27 but hereinbefore of Capacity above 400 KVA to 750 KVA
Supply and fix in repair Digital Amp meter Flush type (CT operated ) complete all as specified and directed.
Supply and Replacement of silica gel breather assembly of capacity 1.5 MVA to 1.6 KVA complete all as specified and as directed.
All as item No 32 but for transformer capacity 400 KVA to 750 KVA
All as item No 32 but for transformer capacity 250 KVA to 315 KVA
All as item No 33 but for transformer capacity 63 KVA to 200 KVA
Comprehensive maintainance / testing of 11 KV RMU (Make - ABB) for checking of circuit wiring, tightening of loose connections, replacement of burnt out wiring thimbles , setting of numerical relays O/C & E/F , ensuring health test by primary injection at site and submission of test report complete all as specified and directed.
Supply and fixing set consisting of 3 HV- Back up fuse Link for three phases indoor type conforming to IEC 60282-1 suitable for fixing in 11 KV RMUs Make- ABB (for load up to 250 KVA) of current rating (capacity) 10A having short circuit rating not less than 63KA Make ABB Cat No 1YMB531035M0002 complete all as specified and directed.
Supply and fixing set consisting of 3 HV-Back up fuse Link for three phases indoor type conforming to IEC 60282-1 suitable for fixing in 11 KV RMUs Make ABB (for load up to 250 KVA) of current rating (capacity) 16A having short circuit rating not less than 63KA Make ABB Cat No 1YMB531035M0003 complete all as specified and directed.
Supply and fixing set consisting of 3 HV-Back up fuse Link for three phases indoor type conforming to IEC 60282-1 suitable for fixing in 11 KV RMUs Make ABB (for load up to 250 KVA) of current rating (capacity) 25A having short circuit rating not less than 63KA Make ABB Cat No 1YMB531035M0004 complete all as specified and directed.
Labour only for Pruning of trees and branches along the HT/LT over head electric lines, surrounding of LT/HT poles, panels Sub-STN bldgs & transformers at different location, should be cleared upto 3mtr of outer edge of assests & removing/disposal of branches out side the line area including Re-stretching, restraining ACSR conductor laid over, OH LT/HT line on steel/PCC poles after removing the binding from insulators, lowering the ACSR conductor or broken OH line due to any reason, jointing the broken conductor, Re-winding the ACSR with insulators including providing binding wire, jumpering & connecting the existing service cables after re-stretching/Re-straining to OH line & removing unavoidable sag in the lines, complete all as specified. Note : Span of OH line will be measured and paid seperately.
M & L for Cleaning of the area with removing the green grass patches /Bushes/small ornamental plants/herbs from the complete area of 33 KV receiving station with suitable T&P and covering the area with suitable peables of suitable size dressing/cleaning the area complete and afterwards sparying the complete area with suitable herbicide to stop the growth of weeds and grass as desired and directed by Engr-in-charge.( Note: the complete Job will be done only after taking proper shut down of 33 KV HT Line. Shut Down will provided by the Dept. with Liasion of SED.) Note: Rate of cleaning of area to be done once in a three months is seemed to be included in quoated rate.
Supply and fixing in repair dial type temperature gauge 110mm dia temperature range 0-100 degree C complete all as specified and directed by Engr-in-Charge.
Supply and fixing lightning arrestor of 30 KV metal oxide (Gap less type) heavy duty, self supporting station class having nominal discharge current 10 KA (peak), class II , insualation level 28/75KV suitable for 33 KV supply including necessary connections with complete all as specified and directed. Make : Raychem RPG , Oblum ,CG, Rashtriya
Supply and fixing lightning arrestor of 09 KV metal oxide (Gap less type) heavy duty, self supporting station class having nominal discharge current 10 KA (peak), class II , insualation level 70/170KV suitable for 11 KV supply including necessary connections with complete all as specified and directed. Make : Raychem RPG , Oblum , CG, Rashtriya
Dismantling air break GOD 33 or 11 KV switches vertical / Horizontal mounted including insulators and operating mechanism for repair / replacement of broken / worn out components and insulators etc at site all as specified and directed. Note :- spare parts / components will be measured and paid separately.
Supply only male contact / moving contact blade and fix contact jaw 200 / 400 amp , Tinned copper flexible jumper for GOD 11 KV per phase complete all as specified and directed.
Supply only male contact / moving contact blade and fix contact jaw 200 / 400 ampTinned copper flexible jumper for GOD 33 KV per phase complete all as specified and directed.
Supply only 33 KV Post insulator Porclain / Polymer complete all as specified and directed. Make-Jaipuria brother / raychem RPG / Atlas /Rashtriya
Supply only 11 KV Post insulator Porclain / Polymer complete all as specified and directed. Make-Jaipuria brother / raychem RPG / Atlas /Rashtriya
Material and labour for earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to copper earth strip 20x3mm size (upto 7.5 metre from ground electrode) by means of copper/brass bolts, nuts, check nuts and washers all as shown in electrical plate No.3 of MES Schedule Part-I, connected to earth test terminal block and testing on completion with and including 40mm bore light grade GI protection pipe for strip upto plingth protection, PCC pit in mix 1:3:6 type C1, with RCC 1:2:4 type B-1, 40 mm thick cover, reinforced with 6 mm dia MS bars 3Nos. both ways with lifting hook made out of 6 mm dia bar, watering arrangement with funnel and wire mesh and 20 mm bore medium grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work complete all as specified and directed.
Excavation in trenches in any type of soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cables, RCC poles/stays and struts etc or /getting out cable cover and stacking for reuse/ credit , trimming sides and forming bottom surface complete all as specified and directed at site.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and directed.
Removing surplus excavated soil nexc 50 mtr and depositing where directed at a level n-exc 1.5 mtr above the starting point complete all as specified and directed.
M&L for dry sand cushioning to underground cables with 8 CM thick before laying of cables and 15 CM thick after laying and stretching of Cable complete all as specified and directed. Note : Only punned thickness i.e. 18 CM shall be measured and paid.
M & L for sub class 'B' brick for covering to under ground cable laid flat transversally width equal to the lenth of the cable complete all as specified and directed.
Laying only old serviceable brick for covering to under ground cable laid dry, flat transversally width equal to the length of the cable all as specified and directed.
Taking down of HT cable 70 to 240 Sqmm, 3 core from trench/panel/wall for locating the fault and relaying the same after rectification of fault complete all as specified and directed. Note : (i) Excvation and earth work shall be measured and paid seperately under respectve items of BOQ
Supply only HT 11 KV tape 20mm width and 25 Mtr length in different colour complete all as specifed and directed
Supply only tinned copper fuse wire 22 guage or as required at site complete all as specified and directed
Vishal Traders
R.S ENGINEERING TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .