| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.6 LAccepted-AOC MAIN ROAD KUJJU RAMGARH JHARKHAND 825316 | KUJJU | RAMGARH | JHARKHAND | 825316 | L1 | Accepted-AOC Since accepted as L1 | |
| 2 | L2₹7.8 L+₹53,303.45 (7.31%)Rejected-Finance ARGADA RAMGARH JHARKHAND 829101 | RAMGARH | JHARKHAND | 829101 | L2 | Rejected-Finance Rejected since L2 | |
| 3 | L3₹8.3 L+₹1.0 L (13.9%)Rejected-Finance | L3 | Rejected-Finance Rejected since L3 |
Tender Value
Refer Docs
EMD Value
₹10,000
Closing Date
18 Mar 2024, 6:55 pmClosed
SO(EnM)
GM UNIT KUJU
Strenghtening,Earth continuity and changing of rusted pole in 11KV Over head line from Ara Kanta substation to Sarubera substation colony and IWSP Substation and changing of rusted/damaged poles , insulators and conductor of 440V OHL at EnM Workshop,
2024_CCL_304233_1
GM (K)/EnM/eTender/23-24/184
Open Tender
Electrical and Maintenance Works
Item Rate
15 days
GM UNIT KUJU
2 documents required · 2 mandatory
₹10,000
2 Jul 2024
8 Mar 2024
19 Mar 2024
8 Mar 2024
18 Mar 2024
8 Mar 2024
8 Mar 2024 - 15 Mar 2024
Amount
A) 11KV OVERHEAD LINE
Erection of RCC/ PCC pole of following length in brick ballast and ramming the foundation, finishing with 150mm thick cement concrete (1:3:6) layer on top with including excavation and refilling etc as requiredAbove 8.0 metre and upto 11.0 metre
Supply of 09 metre long LT Cement pole at working site (300kg)
Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter and above including binding etc. as required.
cost of supply of 6 SWG G.I. wire for cradling and earth continiuty
Erection of G.I. Wire No. 8 SWG including binding etc. as required.
Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required.
Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required
Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required
Supplying and erection of bow stay set complete (galvanised) with 19/20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm, thimble, stay clamps, turn buckle ( 20 mm X 60 cm ), 7/ 4.00 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling and also with 0.6 m long brace of size 50 mm X 50 mm X 6 mm angle iron with 50 mm dia pulley fixed at one end of the brace as required
Supply & fixing of 1core 25sqmm aluminium cable
Supplying & fixing of 35 sqmm Aluminium lug
Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required.
Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) V shape cross arm for two 11 KV over head line conductors complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) pole top bracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required
Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/33 KV as required.
Earthing With 2 metre G.I. pipes having outer pipe dia of 50mm having 80-200 micron galvanizing, Inner pipe dia. of 25mm having 200-250 micron galvanizing, connection terminal dia. of 12mm in nominal soil with 25 kg (one Bag) back filling bentonite compound UL listed and confirm to relevant International/Indian standards around electrode upto ground level.
B) 440V OVERHEAD LINE
Erection of RCC/ PCC pole of following length in brick ballast and ramming the foundation, finishing with 150mm thick cement concrete (1:3:6) layer on top with including excavation and refilling etc as requiredAbove 8.0 metre and upto 11.0 metre
Supply of 09 metre long LT Cement pole at working site (300kg)
Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter and above including binding etc. as required.
Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required.
Supplying and erection of 100 mm X 110 mm shackle insulator with G. I. Bolt, nuts and straps etc. as required
Supplying and erection of 100 mm X 80 mm pin insulator complete with G. I. Spindle and nuts etc. as required .
Supplying and erection of bow stay set complete (galvanised) with 19/20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm, thimble, stay clamps, turn buckle ( 20 mm X 60 cm ), 7/ 4.00 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling and also with 0.6 m long brace of size 50 mm X 50 mm X 6 mm angle iron with 50 mm dia pulley fixed at one end of the brace as required
Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required.
Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for 4 wire over head line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulator pins etc (as per drawing) and painting with primer and finished paint as required .
Total impact of GST for the purpose of CTC
M/S VAISHALI ELECTRIC COMPANY
M/S SANTOSH ELECTRIC
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .