Loading…
Loading…
Tender Value
₹25 L
EMD Value
₹20,000
Closing Date
22 Sept 2026, 3:00 pmClosed
EXECUITVE ENGINEER (O&M), VYARA DIVISION, DGVCL
TENDER FOR ARC FOR LAYING, TESTING & COMMISSIONING OG 11/22KV UG XLPE CABLE(185/240 SQ MM XLPE CABLE TO BE SUPPLIED BY DGVCL) WITH CABLE END TERMINATION & STRAIGHT THROUGH JOINTING KITS (TO BE SUPPLIED BY CONTRACTOR ) JURIDICATION OF ALL FEEDERS EMANATING FROM 66KV NIMBHORA S/S OF KUKARMUNDA SDN.UNDER VYARA DIVISION UNDER VARIOUS SCHEME.
340621
VYD/O&M/TECH/TENDER NO-94/ NO-6136 DT.31.08.2026
Open
Electrical and Maintenance Works
Works
Tapi
3 documents required · 3 mandatory
₹1,180
DAKSHIN GUJARAT VIJ COMPANY LTD.
₹20,000
22 Sept 2026
1 Sept 2026
22 Sept 2026
1 Sept 2026
9 Sept 2026
1 Sept 2026
1 9925000001 Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any type of soil for laying of cable of Meter
size up to 240 mm2 (For additional cable 200 mm additional width shall be considered i.e. half trench length is to be
2 9925000002 Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any type of soil for laying of cable of Meter
size up to 240 mm2 (For additional cable 200 mm additional width shall be considered i.e. half trench length is to be
3 9925000003 Labour charge for excavation of cable trench of 400mm width x 1500mm depth, in any type of soil for laying of cable of Meter
size up to 240 mm2 (For additional cable 200 mm additional width shall be considered i.e. half trench leng th is to be
4 9925000004 Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 & preparation of sand layer 100mm thick, in Meter
the cable trench & covering the cable with 150 mm dia (Outer), thickness 25 mm, 1.0 meter long RCC half round muffs
and providing and fixing of 4inch width yellow colour polyethylene tape with printing"CAUTION ELECTRIC CABLE
BELOW' at 0.75 m depth from ground surface after laying cable in trench. This will provide indication that electric cable
is passing underground so as to protect cable from mechanical injuries, refilling the same, as per Instruction of E gineer
in Charge (EIC) .
5 9925000005 Labour charge for horizontal drilling using Auger machine without damage to surface road at max 2.0 mtrs depth & Meter
putting of 6.11 kg/cm2 , class-4,Green color, 110mm 0.D. 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd
revision) and BIS certification and laying of 11KV/22KV XLPE cable of size up to 240 mm2 in HDPE pipe, as per Site
Condition (excluding cost of pipe). The detail map obtained from HDD machine and excel sheet hard and soft copy)
indicating the respective depth and distance from adjacent landmark for each segment for HDD is must require to be
submitted. HDD to be carried out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and as er instruction of EIC.
6 9925000006 Labour charge for horizontal drilling manually without damage to surface road at max 2.0 mtrs depth & putting of 6.11 Meter
kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and
BIS certification and laying of 11KV/22KV XLPE cable of size up to 240 mm2 size, as per Site Condition (excluding cost of
pipe). The detail map and excel sheet (hard and soft copy) indicating the respective depth and distance from adjacent
landmark for each segment of cable to be submitted. Drilling to be carried out at depth Minimum 1.2 mtrs to 2.0 mtrs
as per site conditions as per instruction of EIC.
7 9925000007 Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5 mm thickness H.D.P.E. pipe confirms to IS 4984 and BIS Meter
certification for laying of underground 11KV/ 22KV XLPE cable up to 240 mm 2 size.
8 9925000008 Labour work for RCC concreting on disputed location and repairing of damage portion of road crossing for the work CMT
carried out for roads crossing as well as concreting & muffing of poles including all materials
9 9925000009 Providing & fixing concrete stone route marker of 300 mm width x 150 mm thick x 650 mm height embedded in earth No
at least 300 mm below & 350 mm above ground level respectively at distance approx. 50 meters along the length of
cable. The RCC concreting (1:2:4)(all necessary materials will be in bidder's scope) of route marker is to be carried out
300 mm width x 150 mm thick x 300 mm below ground level as per instruction of EIC. The route marker should be with
name of company with approved yellow colour-DGVCL. The distance from marker to cable and cable depth with feeder
name etc., marked with arrow sign is to be painted on it. The route marker is to be fixed at location near to any fixed
permanent location (not necessary to fix exact on top of cable) as per instruction of EIC.
10 9925000010 Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable connection arrangement along with fitting No
of necessary fabrication for 11KV cable including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
11 9925000011 Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable connection arrangement along with fitting of No
necessary fabrication for 11KV/22 KV cable including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles
12 9925000012 Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable connection arrangement along with fitting of No
necessary fabrication for 11KV cable including excavation of pit & refilling of earth as per instruction of EIC. (Exclusive
of concreting & muffing of poles
13 9925000013 Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection arrangement along with fitting of No.
necessary fabrication for 11KV/22 KV cable including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting& muffing of poles
14 9925000014 Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 240 mm 2 on DP Structure with fixing of 02 Nos Per Job
polymer cleats on top and middle part. Polymer cleats, nut bolts etc. fixing material to be provided by contractor.
15 9925000015 Providing & fixing of 6.11kg/cm2 , class4,Green color, 110mm O.D. 8.5mm thickness H.D.P.E. pipe confirms to IS 4984 perJob
and BIS certification on the erected DP structure for the mechanical protection of cable by inserting the cable inside
HDPE pipe. The HDPE pipe shall be erected in such a way that 300mm shall be below the ground level and the rest
mm shall be supported on the DP Structure with 01 No Polymer cleat. All materials including polymer cleat and Nut
bolt to be provided by contractor.
16 9925000016 Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with pit to be filled with salt & coke and No
construction of chamber as per DGVCL Drg. No. dg /100 for DP and cable. The earthing pit should be joined with cable
by G.I. strip of size 1" width & 2 mm thick. All material GI pipe, Coke Salt etc will be supplied by bidder.
17 9925000017 Supply & fixing of heat shrink type end terminations (outdoor) for up to 11kV 3C x 185 mm2 size XLPE cable as per No
DGVCL technical s ecification
18 9925000018 Supply & fixing of heat shrink type end terminations (outdoor) for up to 22kV 3C x 185 mm2 size XLPE cable as per No
DGVCL technical s ecification
19 9925000019 Supply & fixing of heat shrinkable type end terminations (indoor) for up to 11kV 3C x 185 mm 2 size XLPE cable as per No
DGVCL technical specification
20 9925000020 Supply & fixing of heat shrinkable type end terminations (indoor) for up to 22kV 3C x 185 mm 2 size XLPE cable as per No
DGVCL technical specification
21 9925000021 Supply & fixing of heat shrinkable straight through joint for up to 11kV 3C x 185 mm 2 size XLPE cables as per DGVCL No
technical specification.
22 9925000022 Supply & fixing of heat shrinkable straight through joint for up to 22KV 3C x 185 mm 2 size XLPE cables as per DGVCL No
technical specification.
23 9925000023 Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep joint pits for installation of 11kV / 22kV No
Straight through joints as per instruction of engineer-in-charge & covering the cable with 150 mm dia (Outer), thickness
25 mm, 1.0 meter long RCC half round muffs & refilling same as per instruction of EIC .
24 9925000024 Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE cable after removal of semi conducting layer and No
applying of PVC heat shrinkable antitracking core insulating tubing (1.1KV), on both end terminal using Aluminium long
barrel heavy duty up to 240 sq mm lugs, Aluminium bus connector. Taping with PGclamp for bus conductor as per
drawing and as per instruction of EIC. The Allurninium lugs and PG clamp shall be covered with 11KV/22KV HT
insulating tapes.(11KV/22KV XLPE cable will be in scope of DGVCL while all other materials will be in bidder's scope.
25 9925000025 Testing of cable at various points and commissioning the feeder as per instruction of engineer-in-charge.Test result No
shall be submitted by contractor with bill.
26 9925000026 Preparation and submission of 6 (six) copies, of complete layout drawings with GIS mapping as per actual cable routing Set
showing road crossing, HDPE pipe sleeving, jointing locations, markers etc.
27 9925000027 Providing and fixing of Sign Board at junction point Made out of 2 mm aluminium sheet size 750x300 mm (2.5 x 1 ft) No
rectangle, as per design, pretreated with phosphate process and acid etching coated with one coat of epoxy primer and
two coats of best quality paints, reflectorized with Hi Intensity retro — reflective sheeting as per the latest and frame
fabricated from suitable size iron angle. The Sign Board is to be fixed on the base prepared from channel and bracing
angles which is grouted by means of cement concreting of 1:2:4 for size of 300 mm dia x 800 mm height (500 mm to be
grouted in ground). The details to be displayed on sign board will be given by InchargeEngineer. (a) Hi intensity Micro
prismatic Grade
28 9925000028 Providing and fixing of Sign Board (Danger Board) on Distribution Transformer Centers Made out of 2mm aluminium No
sheet size 300x300mm (1X1 ft) as per design, pre treated with phosphate process and acid etching coated with one coat
of epoxy primer and two coats of best quality paints, reflectorized with Hi-Intensity retroreflective sheeting as per the
latest and frame fabricated from suitable size iron angle. The Sign Board (Danger Board is to be fixed at the location as
per instruction of In-charge Engineer. (a) Hi intensity Micro prismatic Grade
29 9925000029 Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 mm aluminium sheet along with 1.0 mm dia No
aluminium binding wire for fixing of aluminium tag near end termination joint at DP structure for identifying the cable.
The details of feeder i.e. 11 / 22 KV with feeder name should be punched on the tag by letter punch of size 16 mm as
per instruction of In-charge Engineer.
30 9925000030 Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x 240 mm2 size XLPE cable as per DGVCL No
technical specification.
31 9925000031 Supply & fixing of heat shrink type end terminations (outdoor) for 22kV 3C x 240 mm2 size XLPE cable as per DGVCL No
technical specification.
32 9925000032 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 240 mm2 size XLPE cable as per DGVCL No
technical specification
33 9925000033 Supply & fixing of heat shrink type end terminations (indoor) for 22kV 3C x 240 mm2 size XLPE cable as per DGVCL No
technical specification
34 9925000034 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 mm2 size XLPE cables as per DGVCL technical No
35 9925000035 Supply & fixing of heat shrinkable straight through joint for 22kV 3C x 240 mm2 size XLPE cables as per DGVCL technical No
36 9925000038 Installation ,Testing and commissioning of 11 KV ,630 A SCADA Compatible ,RRL type-3 Way RMU including Two No
numbers of earthing as per Drawing (materials in bidders scope ) and as per DGVCL Technical specification.
37 9925000039 Installation ,Testing and commissioning of 11 KV ,630 A SCADA Compatible ,RRLL type-4 Way RMU including Two No
numbers of earthing as per Drawing (materials in bidders scope ) and as per DGVCL Technical specification.
38 9925000040 Installation ,Testing and commissioning of 22 KV ,630 A SCADA Compatible ,RRL type-3 Way RMU including Two No
numbers of earthing as per Drawing (materials in bidders scope ) and as per DGVCL Technical specification.
39 9925000041 Installation ,Testing and commissioning of 22 KV ,630 A SCADA Compatible ,RRLL type-4 Way RMU including Two No
numbers of earthing as per Drawing (materials in bidders scope ) and as per DGVCL Technical specification.
40 9925000042 Construction of plinth for 11KV ,RRL type-3 Way (i.e Two numbers of Isolator & One number of Breaker) Ring Main Unit No
as per DGVCL`s techanical specification mentioned in drawing no: Drg. 11kv-01.All required will be supplied by
41 9925000043 Construction of plinth for 11KV ,RRLL type-4 Way (i.e Two numbers of Isolator & Two number of Breaker) Ring Main No
Unit as per DGVCL`s techanical specification mentioned in drawing no: Drg. 11kv-02.All required will be supplied by
42 9925000044 Construction of plinth for 22KV ,RRL type-3 Way (i.e Two numbers of Isolator & One number of Breaker) Ring Main Unit No
as per DGVCL`s techanical specification mentioned in drawing no: Drg. 22 kv-01.All required will be supplied by
43 9925000045 Construction of plinth for 22KV ,RRLL type-4 Way (i.e Two numbers of Isolator & Two number of Breaker) Ring Main No
Unit as per DGVCL`s techanical specification mentioned in drawing no: Drg. 22 kv-02.All required will be supplied by
44 9925000045 Modification e.g. Providing and fixing of terminasl protector i.e. Re-use ablr boot (HT side 11/22 KV ,LT side 1.1 KV No
insulating taps and LT (1.1 KV) insulating taps ,Busbar ,Tapping from Bus Bar (11/22 KV XLPE cable) through P.G. Clamp
for HT jumper to D.O. Fuse to busing of Transformer center .providing & fixing of jumper and fuse to bushing of
transformer center ,providing & fixing of jumper and providing & fixing of Heat Shrinkable and Tracking Core Insulating
Tubing (Insulation level 11/22 KV) in HT jumper ,clamping arrangement of cable support frame on both side of existing
Over head type Distribution transformer to utilize in under ground cable network as per connection of D.O. fuses .HT
bushing etc. shall be covered with fixing of 11/22 KV HT insulating taps.(11/22 KV XLPE cable will be in scope of DGVCL
while all other materials will be in bidders`s scope)
45 9925000047 Laying of any size of 11/ 22 KV XLPE /PILCCable in readymade trench or in open space per cable
46 9925000060 Labour charges for Laying of O/H XLPE cable pole to pole KM
47 9925000064 Supply of 150mm dia 9inner) ,thickness 25mm,1.0 meter long RCC half round pipe. No
9605000008 Work of fault finding 11KV cable underground XLPE cable fault locating exact place of fault.
Consecutive more than one fault finding on same cable till the cable faulty charged fully.
TOTAL ESTIMATE RS. TWENTY FIVE LACS ONLY.
EXECUTIVE ENGINEER(O&M)
DIVISION OFFICE,VYARA
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
(1) SCHEDULE A KUKARMUNDA.pdf
(2) Bid Document.pdf
(3) Integrity Pact.pdf
(4) SCHEDULED-B UG CABLE KUKARMUNDA 25 LACS.pdf
(5) Signed OH HT XLPE Cable Drawing 1.pdf
(6) Signed OH HT XLPE Cable Drawing 2.pdf
(7) Signed OH HT XLPE Cable Drawing 3.pdf
(8) Signed OH HT XLPE Cable Drawing 4.pdf
(9) Signed Overhead RE standard drawings.pdf
(10) Route Marker with concreting drawing_0001.pdf
(11) Technical Specification of Termination Kit of XLPE cable.pdf
(12) Drawing GPRD 16 AND 17.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .