| 1 | L1₹2.0 LAccepted-AOC KARUKAPPILLY THATTATHUKUDIYIL BUILDING KOLENCHERY 682311 | KOLENCHERY | ERNAKULAM | KERALA | 682311 | L1 | Accepted-AOC L1 | |
| 2 | L2₹2.2 L+₹20,058 (10.2%)Rejected-Finance 3 333 F M P ARCS VENGACHUVADU VAZHAKKULAM P O CHAITHANYA BUILDING SA ROAD KADAVATHRA MUVATTUPUZHA ERNAKULAM 686670 | MUVATTUPUZHA | ERNAKULAM | KERALA | 686670 | L2 | Rejected-Finance 2ndlowest | |
| 3 | Not Admitted-Fee/PreQual/Technical/Finance 65 905 SEBASTIAN ROAD KALOOR KALOOR ERNAKULAM KERALA 682017 | ERNAKULAM | KERALA | 682017 | - | Not Admitted-Fee/PreQual/Technical/Finance Not qualified for AOC |
| Sl No | Description | Qty | Unit | Power Care Electrical L1 | Linsta Services L2 |
|---|---|---|---|---|---|
| 1.00TRANSFORMER SERVICING | |||||
| 1.01 | Supply and delivery of new, unused, virgin mineral insulating transformer oil conforming to the latest IS standards, suitable for 11 kV / 433 V, 1600 kVA distribution transformer.The oil shall be suitable for initial filling or topping up of the transformer. The specifications as follows (1) Type Mineral insulating transformer oil – new and virgin, (2) Standard IS 335:2018 (latest) or IEC 60296 (3) Appearance Clear and free from suspended matter, sludge, or sediment, (4) Dielectric Breakdown Voltage (BDV) Minimum 60 kV (tested after filtration),(5) Specific Resistance at 90°C Not less than 35 × 1012 ohm-cm,(6) Moisture Content Less than 30 ppm,(7) Acidity (Neutralization Value) Max. 0.03 mg KOH/g,(8) Interfacial Tension Min. 0.04 N/m,(9) Flash Point (Closed Cup) Not less than 140°C,(10) Pour Point Not higher than –6°C,(11) Corrosive Sulphur Test Non-corrosive. | 400 | litre | 203 ₹81,200 Lowest | 225 ₹90,000 |
| 1.02 | Carrying out hot oil filtration and dehydration of the insulating oil of 11 kV/433 V, 1600 kVA transformer using a high-vacuum filtration plant to restore dielectric and insulating properties of the transformer oil. The work shall include testing, filtration, and submission of results conforming to IS 335:2018 and IS 1866:2017 standards. | 2 | job | 3,390 ₹6,780 Lowest | 3,730 ₹7,460 |
| 1.03 | To supply and refill / replace silica gel crystals in the breather unit of a 1600 kVA, 11kV/433V oil-filled distribution transformer, ensuring proper moisture absorption andprotection of the transformer oil from humidity ingress. Work includes removal ofold, discoloured, or saturated silica gel, cleaning of breather assembly, refilling withfresh indicating silica gel, and reinstallation. | 2 | job | 1,806 ₹3,612 Lowest | 2,000 ₹4,000 |
| 2.00VCB SERVICING | |||||
| 2.01 | Servicing, inspection, testing, and functional verification of 11 kV, 630 A Vacuum Circuit Breaker (VCB) associated with a 1600 kVA, 11 kV/433 V transformer. Work shall ensure reliable operation of the breaker, correction of mechanical defects, insulation health check, and satisfactory trip/close performance. | 1 | job | 90,000 ₹90,000 Lowest | 1,00,000 ₹1,00,000 |
| 2.02 | Supply installation testing and commissioning of automatic battery charger for 12V 60 AH battery of VCB panel | 1 | no | 5,863 ₹5,863 Lowest | 6,400 ₹6,400 |
| 2.03 | Supply, installation, and connection of DC control battery for operating the VCB tripping and closing circuits in an 11 kV switchgear panel. The work includes providing suitable battery capacity, mounting arrangement, wiring, testing, and commissioning. 12v, 60AH battery | 1 | no | 9,347 ₹9,347 | 9,000 ₹9,000 Lowest |
Tender Value
₹2.0 L
EMD Value
₹4,950
Closing Date
15 Oct 2025, 6:00 pmClosed
Assistant Executive Engineer
gcda office kadavanthra
Servicing of 1600 KVA transformers at JNIS
2025_GCDA_807043_1
E2/8961/2025/GCDA
Open Tender
Electrical Works
Item Rate
30 days
jniskaloor
Please refer Tender documents.
7 documents required · 7 mandatory
₹440
₹4,950
30 Oct 2025
8 Oct 2025
17 Oct 2025
8 Oct 2025
15 Oct 2025
8 Oct 2025
Amount
TRANSFORMER SERVICING
Supply and delivery of new, unused, virgin mineral insulating transformer oil conforming to the latest IS standards, suitable for 11 kV / 433 V, 1600 kVA distribution transformer.The oil shall be suitable for initial filling or topping up of the transformer. The specifications as follows (1) Type Mineral insulating transformer oil – new and virgin, (2) Standard IS 335:2018 (latest) or IEC 60296 (3) Appearance Clear and free from suspended matter, sludge, or sediment, (4) Dielectric Breakdown Voltage (BDV) Minimum 60 kV (tested after filtration),(5) Specific Resistance at 90°C Not less than 35 × 1012 ohm-cm,(6) Moisture Content Less than 30 ppm,(7) Acidity (Neutralization Value) Max. 0.03 mg KOH/g,(8) Interfacial Tension Min. 0.04 N/m,(9) Flash Point (Closed Cup) Not less than 140°C,(10) Pour Point Not higher than –6°C,(11) Corrosive Sulphur Test Non-corrosive.
Carrying out hot oil filtration and dehydration of the insulating oil of 11 kV/433 V, 1600 kVA transformer using a high-vacuum filtration plant to restore dielectric and insulating properties of the transformer oil. The work shall include testing, filtration, and submission of results conforming to IS 335:2018 and IS 1866:2017 standards.
To supply and refill / replace silica gel crystals in the breather unit of a 1600 kVA, 11kV/433V oil-filled distribution transformer, ensuring proper moisture absorption andprotection of the transformer oil from humidity ingress. Work includes removal ofold, discoloured, or saturated silica gel, cleaning of breather assembly, refilling withfresh indicating silica gel, and reinstallation.
VCB SERVICING
Servicing, inspection, testing, and functional verification of 11 kV, 630 A Vacuum Circuit Breaker (VCB) associated with a 1600 kVA, 11 kV/433 V transformer. Work shall ensure reliable operation of the breaker, correction of mechanical defects, insulation health check, and satisfactory trip/close performance.
Supply installation testing and commissioning of automatic battery charger for 12V 60 AH battery of VCB panel
Supply, installation, and connection of DC control battery for operating the VCB tripping and closing circuits in an 11 kV switchgear panel. The work includes providing suitable battery capacity, mounting arrangement, wiring, testing, and commissioning. 12v, 60AH battery
Linsta Services (BID ID -2389724)
Bidder Name
Linsta Services
Power Care Electrical
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1344863.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .