EXECUTIVE ENGINEER JAL SHAKTI DIVISION GHUMARWIN
EXECUTIVE ENGINEER JAL SHAKTI DIVISION GHUMARWIN
SH Supply and errection of pumping machinery with allied accessories including automation for LWSS Seo Badhghat Naswal 2nst stage 2x90 180 HP
2024_HPIPH_94291_1
GMR-BLP02-737(6136-41)JobNo.5
Open Tender
Civil Works
Item Rate
90 days
GHUMARWIN
Please refer Tender documents.
7 documents required · 7 mandatory
₹400
Yes
EE JAL SHAKTI DIVISION GHUMARWIN
₹60,150
Yes
15 Mar 2025
15 Oct 2024
22 Oct 2024
15 Oct 2024
21 Oct 2024
15 Oct 2024
15 Oct 2024 - 21 Oct 2024
Amount
Providing & Installation of horizontal spindle horizontal split casing / end suctions (back pull out arrangement ) single /double/multistage centrifugal pump or combination of pump in series of KSB /Kirloskar and mather and platt make as per BIS 1520-1980 with up to date amendments, read with IS:9137-1978 or latest edition suitable for lifting clear water . The pump should be fitted with bronze impellers, priming funnels , casing rings, shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on MS/ Cast steel base plate ( base plate to be provided from the manufacturer,s of the pumping unit only) to squirrel cage drip proof induction motor of standard make such as Kirloskar/Crompton/ KSB confirming to BIS 9238-1979 latest with up to date amendments and suitable for operation on 400 (+/-) 10% volts, 50 cycles / second, three phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of + 10% and - 15% of the duty point head. The motor should be as per IS 325-1978 with up to date amendments.The pump set should suitable for operation on data given below:- ( 2No. Pumping set i.e. 2x 90= 180.00 HP)
Discharge:- 9.07 LPS per set, Total dynamic head :- 322.67 metre,Suction Lift:- postive, Dia of Rising Main:- 125 mm , Length of Rising Main:- 3000 Rmt, Pumping Hours:- 8 hours, Coupling and base plate :- 1 sets, Turbidity :- less than 50 NTU, Temprature 20 degree to 45 degree centigrade.
Providing and fixing double flanged GMS piping network for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as rappers, flanges, rubber gaskets minimum 3 mm in thickness as per IS 2712-1979, nuts and bolts as per IS:1364-1983, bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as per drawing up to 5 metre away from the outer wall of pump houses. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated.The size of various components are as under:-
Suction pipe 150 mm dia M.C Minimum length= 5 metre
Delivery pipe 100 mm dia M.C Minimum length= 10 metre
Common header 125 mm dia M.C Minimum length = 10 metre
The GMS tube confirming to IS :- 1239-1979 part-I Medium class flanged with MS flanges of table 5 in suction pipe and heavy class flanged with MS flanges of table 17 in delivery side and common header.
Providing and laying suitable size copper PVC insulated armoured power 3.5 core cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
Motor side: suitable capacity Min length = 20 mtrs.
Supply side: suitable capacity Min. length =10 mtrs.
Providing and fixing double loop earthing with copper plate 600mmx600mmx3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx3mm. G.I strips and G.I wire as per IS: 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Providing and instalation of VFD Starter for centrifugal pump with SCADA based Automation
Supply , Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each of the rating 90 HP . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric/Tricolite/L S Controls/Adlec
Energy Saving Variable Frequency Starter of 90 HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer Make: JSV Approved
Power and Control Wiring and Busbar
Installation, Commissioning and Software Development
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T/reputed approved make
Supply Installation, Testing and Commissioning of PLC Control Panel with appropriate digital and analog inputs and outputs to give automatic command to Star Delta Starter Panel/ Energy Saving Variable Frequency Starter Panel Make Siemens/Allen Bredley/reputed approved make
Electronic relay card 8 channel
SMPS 4.5 Amps to energise PLC system
HMI (Human Machine Interface) 7" display for Monitoring and Controlling of Centrifugal pumps Make: Bechoff Automation/Roackwell/ reputed approved make
Control MCB for Automation System
Level Sensor to indicate the water level of tank remotely
Shielded Data Cable for Communication of Level Sensor with PLC
Supply of Mobile App (Android/IOS) with User ID and Password to monitor and control the pumping operation from Mobile for 3 users. Make: JSV Approved
Cloud GateWay for Data Clouding to Server
SCADA software to be installed in Laptop/PC to remotely monitor and control the operation of pumps and also to analysis the pump start and stop history logging, fault status, fault history, Power Quality Parameters like PF, Current, Voltage, KWH, THD etc Make JSV Approved
Cloud Space for data storage at cloud/server
Installation, Commissioning and Software Development
Note:-If any item is missing in pannel board of pump/PLC/automation of submersible and centrifugal pump requored to make the system functional will have to be executed in the above cost and two years maintanence cost is included in the cost of pannel board of pump and automation.
mohitchandel (BID ID -444400)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .