Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.7 CrAccepted-AOC 9TH FLOOR 920 WAVE SILVER TOWER SECTOR 18 NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201301 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | ₹1.7 Cr | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹1.8 Cr+₹9.6 L (5.64%)Rejected-Finance | ₹1.8 Cr+₹9.6 L (5.64%) | L2 | Rejected-Finance L2 Bidder |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not participated in verification process. |
Tender Value
₹2.0 Cr
EMD Value
₹4.0 L
Closing Date
24 Oct 2019, 3:00 pmClosed
Administrative Officer
CSIR-Indian Institute of Chemical Biology, 4, Raja S.C. Mullick Road, Jadavpur, Kolkata-700032
Repair and Renovation of Research Laboratory Building to facilitate Animal Experimentation Facility at CSIR-IICB, Salt Lake Campus.
2019_CSIR_32475_1
CSIR_IICB / Admn 26(457) / E / 2018
Open Tender
Construction Works
Works
150 days
CSIR-IICB, Salt Lake Campus
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹4.0 L
18 Feb 2020
24 Sept 2019
25 Oct 2019
24 Sept 2019
24 Oct 2019
25 Sept 2019
Amount
Dismantling of Ducts of AC Systems, Electrical Power boards, Light Fittings, Fans, Fire Detectors including surface/ recessed wiring / Cabling etc. The dismantled materials are to be kept at the specified location within the Institute campus as directed by the Engineer-in-charge of the work. For removal of Fire Detectors / Alarm System, persons having knowledge in the similar field, are to be engaged.
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In cement mortar
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.
Taking out of 4 Nos Fire door of sizes 1.35m X 2.10m, 1 No. Fir door of size 1.00m X 2.10m and 4 Nos Aluminium doors of sizes 1.00m X 2.10M from Research Block of CSIR-IICB, Salt Lake Campus and loading the same to appropriate transport and unloading the same to CSIR-IICB, Jadavpur Campus as Directed by the Engineer-in-Charge.
Loading of 4 Nos Fire door of sizes 1.35m X 2.10m, 1 No. Fire door of size 1.00m X 2.10m and 4 Nos Aluminium doors of sizes 1.00m X 2.10M from Research Block of CSIR-IICB, Salt Lake Campus and unloading the same to CSIR-IICB, Jadavpur Campus as Directed by the Engineer-in-Charge.
Dismantling aluminium/ Gypsum/ wooden partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable surplus material and stacking of serviceable material within 50 meters lead as directed by Engineer-in-charge.
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand)
Removing dry or oil bound distemper, water proofing cement paint, Putty and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
20 mm cement plaster of mix : 1:4 (1 cement: 4 coarse sand)
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface : Water thinnable cement primer
Applying two coat of water thinnable cement primer (Anti fungal) of approved brand and manufacture on wall surface : Water thinnable cement primer (Anti fungal)
Extra for providing and applying two coat of Anti fungal chemical with SIKAGARD- 67 Combined mixed Part (A+B) of approved brand and manufacture on the fungus and mould attacked wall surface : Anti fungal chemical with SIKAGARD- 67 Combined mixed Part (A+B)
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work.
Cement concrete pavement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete.
Wall cutouts and installation of pass box (the pass box to be issued by CSIR-IICB separately)
Making chases up to 7.5x7.5 cm in walls including making good and finishing with matching surface after housing G.I. pipe etc.
Epoxy screed coving (50R) , finished with epoxy putty and two coats of epoxy paint.
3.1 mm thick epoxy flooring including rubbing and scratching the existing vitrefied floor (surface preparation) and primer. For laying of self levelling epoxy flooring.
Supply & Installation of Double skin modular wall panels, 50 mm thick, made with Precoated Coated GI sheets (0.6 mm thick) on both sides with PUF of density 40 ± 2 kg/m³ as infill, recessed male edge on one side and roll-formed female edge on the other side to create an interlock, ensuring a snug insulated fit. Wall joints to be filled with suitable sealant. Appropriate reinforcement shall be provided between the panels from the floor to ceiling near the doors. (Tongue and groove joints are not accepted)
Supply & Installation of HEAVY DUTY CLEANROOM COMPATIBLE WALKABLE CEILING Systems and supporting hardware with supporting grid along with Blanks, 50 mm thick, made with Precoated Coated GI sheets (0.6 mm thick) on both sides with PUF of density 40 ± 2 kg/m³ as infill & totally flush Walkable false ceiling. The Joints shall be sealed with cleanroom compatible silicone sealant. Ceiling Grid system shall comprise all the suspension material in Galvanized finish, reinforcing clamps and brackets complete
Aluminum linear Covings (wall to wall and wall to ceiling) with Aluminium Backing-R-42
3D Aluminium powder coated internal R-42 coving
Two way external piller-50 mm thk
External corner-50 mm panel
Bottom profile for wall
C Channel powder coated
L angle powder coated
Supply & Installation of GI Powder Coated double skin door with 50 mm leaf thickness made of 0.80 mm GI sheet for door leaf with PUF/ paper honeycomb infill and door frame made out of 1.20 mm thick GI profile. Doors are designed to fit flush into the wall panel system on both sides and are supplied in different dimensions. Shall have frame width of 50 mm and shutter width of 46 mm. Doors are including all accessories, standard arms door closer. Doors Accessories shall include SS D handle Back to back / SS D Handle one side and one side SS push Plate, Dead Lock with Both side key operation, SS ball bearing Hinges, SS Kick plate 0.8 mm thick up to 300 mm height, Door closer & Door stopper, Concealed type Bottom Drop seal, Concealed type Flush Bolt for Double leaf door, Double glazed view panel of 400 X 800 mm with 6 mm thick toughened glass
Single leaf door - 1000 x 2100
Emergency exit door with panic bar- 900 x 2100
Double leaf door - 1500 x 2100
Supply & fixing of Cleanroom windows/ vision Panels of flush double glazed fixed to the partition panels for the required sizes and quantity Tempered Glass thickness minimum 6 mm Window glazed, Extruded aluminium midline frame in powder baked ‘designer white’ finish and gasket. 1000 x 1000 mm
Rodent Barrier for 1500 wide door consisting of U channel sliding panels of GI powder coated construction, all as required. All edges of sliding panel shall be covered with C channel duly poeder coated.
Door interlock system:Interlock panel, magnetic lock, pushbottom , exit bottom, etc.
2 door system
Dismantling of flexible pavement (bituminous courses) by mechanical means and disposal of dismantled material up to a lead of 1 kilometre, as per direction of Engineer-in-charge.
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.
Brick soling with picked jhama bricks including preparation of bed as necessary with brick joints properly filled in and packed with powdered earth and including necessary cushion of similar material below the soling (and in between layers when more than one layer is used) completes as per direction. (a) Single brick flat soling (thickness 75 mm.)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm nominal size)
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size)
Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts
Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. 1.00 mm thick with zinc coating not less than 275 gm/m²
Providing and fixing 15 cm wide, 45 cm overall semi-circular plain G.S. sheet gutter with iron brackets 40x3mm size, bolts, nuts and washers etc., including making necessary connections with rain water pipes complete. 0.80 mm thick with zinc coating not less than 275 gm/m²
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shade
Providing and fixing mild steel round holding down bolts with nuts and washer plates complete.
Providing and laying Bitumen Penetration Macadam with hard stone aggregate of quality, size and grading as specified, with bitumen of suitable penetration grade, including required key aggregate as specified, spreading coarse aggregate with the help of self propelled/ tipper tail mounted aggregate spreader and applying bitumen by a pressure distributor and then spreading key aggregate with the help of aggregate spreader complete, including consolidation with road roller of minimum 8 to 10 tonne capacity to achieve specified values of compaction and surface accuracy : For 50mm compacted thickness using coarse aggregate of size 50-20 mm graded @ 0.60 cum per 10 sqm key aggregate of size 12.5 mm graded @ 0.15 cum per 10 sqm. With paving asphalt grade VG - 10 @ 50 kg/ 10 sqm.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion. Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15)
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15)
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineerin-charge. Pre-laminated particle board with decorative lamination on both sides
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm)
Providing and fixing bright finished brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.
Providing and fixing chromium plated brass handles with necessary screws etc. complete: 125 mm
Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete.
Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete.
Design, Supply, installation, testing and commissioning of Air-conditioning system (HVAC) comprising of the followings. The system shall be designed to maintain, Temperature: 23⁰C ± 1⁰ C ; Relative Humidity: (40 - 60)%, Differential Pressure: Positive (5 – 10 Pa), 100 % Fresh Air, No. of Air Changes Per Hour: 14 to 20 etc. The Unit shall be suitable for Clean Room Application.
Supply, installation, testing and commissioning of Double skin Once through type air handling unit with 2 mm thick thermal break aluminium profile, 43 ±2 mm thick Puf panel having a density not less than 38 kg/m. Panel shall have 0.6mm precoated G.I sheet as outer skin and 0.6mm thick plane GI inner skin. The Unit shall be suitable for clean room applications with coving inside. The AHU shall consist of fresh air intake louvre, G4 filter, cooling coil section with minimum 10 row deep Chilled water cooling coil, space for humidifier pipe for injection of steam to inlet air, fan section with DIDW centrifugal backward curved fan with TEFC squirrel cage induction motor. Fine filter section with F6 filter after the fan section and HEPA Filter section with filter frame. AHU shall be complete with supply air Aluminium low leakage damper. Fan section & filter sections shall have service door of not less than 500 mm width. AHUs will have following capacities
AHU : 3500 cfm @ 125mm WC static head once through type
AHU : 2000 cfm @ 125mm WC static head once through type
Supply, installation, testing and commissioning of HEPA Filter H-13 inside AHU plenum. Filers shall have leak test certificate from factory as per relevant standard and shall be tested by the agency for leak proofness during cleanroom validation at site.
HEPA Filter 610 x 610 mm of 2000 CFM capacity
HEPA Filter 610 x 305 mm of 1000 CFM capacity
Supply, installation, testing and commissioning of Activated carbon filter (ACF) with following details: a) Filter frame : CRCA epoxy powder coated b) Filter media: cylindrical activated carbon filter pallet c) Media to frame sealing: Epoxy sealed d) Gasket : PU foam tape e) Final Pressure drop : 50 mm WG
Activated carbon Filter 610 x 610 x 150 mm of 2000 CFM capacity
Activated carbon Filter 610 x 305 x 150 mm of 1000 CFM capacity
Supply, Installation, testing and commissioning of 48 TR Nominal capacity Air cooled HVAC chiller with multiple scroll compressor, skid mounted, R22 refrigerant complete with control unit and other accessories complete as required.
Supply, Installation, Testing and Commissioning of centrifugal EXHAUST FAN with motor assembly mounted inside double skin casing outside pre coated GI and inside plain GI sheet. Panel thicknes 23 ±2 with imported DIDW/ SISW centrifugal forward curved fan, motor, v-belt & drive set. Unit consists of Pre filter with pre filter, filter frame for Activated carbon filters 150 mm thick, Fan section with fan motor assembly complete. Fan shall have following ratings:
3500 cfm at 100 mm WG Static pressure
2000 cfm at 100 mm WG Static pressure
1750 cfm at 100 mm WG Static pressure
Supply, Installation, testing and commissioning of INLINE FAN For IVC exhaust capacity 600 cfm with 20 mm SP, complete with all accessories.
Supply, Installation, testing and commissioning of suitable rating Canvass connection at inline fans complete with all accessories.
GI Powder coated Cowl & bird screen for exhaust fan, to be mounted on outside face of wall opening for exhaust air
Supply, Installation, testing and commissioning of Thyristor controlled SS heater Bank for monsoon RH control and winter heating with contactor with internal wiring. Heater shall have control panel in built. Thyristor controlled duct mounted heaters of following ratings
Supply, Installation, testing and commissioning of Safety thermostat for heaters complete with all accessories.
Supply, Installation, testing and commissioning of Air flow switch with contactor complete with all accessories.
Supply, Installation, testing and commissioning of pan humidifier made of stainless steel sheet of minimum 2 mm thick complete with steam outlet nozzle, immersion heaters, low level cut out, humidistat, safety stat, float valve, sight glass, ball valve for drain connection etc.
Supply, Installation, Testing and Commissioning of Chilled water circulation pump 140 UGPM at 30 m head, back pull out type. CI casing with bronze impeller and TEFC motor complete with coupling and base frame complete as required.
Supply, installation, testing and commissioning of Magnhelic gauges with GI box with SS cover plate and sensors with necessary tubing for filters across AHUs HEPA Filters
Supply, installation, balancing and commissioning of factory fabricated GSS sheet GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
Thickness 0.63 mm sheet
Thickness 0.80 mm sheet
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self-adhesive nitrile rubber tape insulation complete as per specifications and as required.
Supply, Installation, testing and commissioning of Duct acoustic insulation in inner side of ducting, made of glass wool / UP twiga 50 mm thick complete with wooded batton and covered with hassian cloth and perforated aluminum sheet 24 swg.
Supply and installation of closed cell nitrile rubber insulation wrapped with 5 mill fibre glass cloth and coat of UV barrier paint for weather protection on supply & return air ducts SR 998 / SR 505 adhesive and tape. 19 mm thick
Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sqmm) for integration within AHU room
Damper
Supply, installation, testing and commissioning of Fusible link type MS fire damper at AHU inlet.
Supply, installation, testing and commissioning of Fusible link for fire damper
Aluminum powder coated removable core diffusers with collar damper for supply and return air.
Providing and applying RTV silicon sealant at duct seam and longitudinal joints.
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
100 mm dia
80 mm dia
65 mm dia
50 mm dia
32 mm dia
Supplying, fixing, testing and commissioning of Butterfly Valve (Manual) with CI body SS disc, Nitrile rubber seal & O ring PN 16 pressure rating as specified
100 mm dia
80 mm dia
65 mm dia
50 mm dia
Supplying, fixing, testing and commissioning of NON RETURN VALVE wafer type CI body PN 16 pressure rating for chilled water / hot water circulation as specified
80 mm dia
Supplying, fixing, testing and commissioning of BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.
65 mm dia
50 mm dia
Supplying, fixing, testing and commissioning of Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.
80 mm dia
65 mm dia
50 mm dia
Supplying, fixing, testing and commissioning of 25 mm dia SS BALL VALVE PN 16.
Supplying, fixing, testing and commissioning of 3 way modulating valve for chilled water flow control to AHU coil, complete with Modulating Actuator as required
50 mm dia 3 way modulating valve
25 mm dia 3 way modulating valve
Supplying, fixing, testing and commissioning of WATER FLOW SWITCH for chilled water flow at chiller
Supply and installation of closed cell nitrile rubber insulation wrapped with 5 mill fibre glass cloth and coat of UV barrier paint for weather protection on supply & return air ducts SR 998 / SR 505 adhesive and tape. (19 mm thick.)
80 mm dia
65 mm dia
50 mm dia
32 mm dia
25 mm dia
Supplying, fixing, testing and commissioning of of 4" Dial Type Pressure Gauge with ball valve. Pressure gage should be directly connected in water line.
Supplying, fixing, testing and commissioning of 4" Dial Type Temperature Gauge with thermowell (3 inch Long) for chilled water line
Supplying, fixing, testing and commissioning of AUTO AIR VENT WITH BALL VALVE- 20 mm dia
Insulation of valves and strainers of various types and sizes.
Supply and erection of AHU Drain piping arrangement - 40 mm dia HEAVY DUTY poly vinyl chloride (PVC) pipe complete with fitting and accessories for drain.
Supply and erection of AHU Drain piping arrangement - 125mm height U trap made from HEAVY DUTY PVC
Supply, installation, testing and commissioning of Variable frequency drives independently with bypass starter panel and also differential pressure near with cabling from the sensor located on the duct to the VFD for air handling units / exhaust fan of following capacity motors including necessary fittings and fixing accessories etc. complete
For 1.5 KW motor
For 2.2 KW motor
Supply, installation, testing and commissioning of Pressure sensor for VFD, speed control.
Supply of following sizes of 1.1 kV grade multicore aluminium conductor XLPE / PVC sheathed armoured cable.
4C X 35 Sq.mm.
4C X 70 Sq.mm.
4C X 185 Sq.mm.
4C X 240 Sq.mm.
Supply of 1.1 KV copper conductor PVC Insulated armoured cable of following sizes for power and control cabling
4c x 4 sq. mmx cu cable For PH
4c x 10 sq. mm x cu cable for Heater
3c x 4 sq. mmx cu cable for AHU
3c x 6 sq. mmx cu cable for AHU
2c x 6 sq. mmx cu cable
1c x 10 sq. mm x cu. Flexible cable for UPS
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
Upto 35 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 X 35 sq. mm (32mm)
4C X 70 sq. mm
4CX 185 sq. mm
4CX 240 sq. mm
Supplying and fixing of following way, SPN / TPN 240 / 415 volts distribution board with suitable size of cable end box (Two Nos.) with tinned copper busbar, neutral link, earth bar, din bar, detachable gland plate, interconnection including painting, earthing, connection, testing, commissioning etc as required. (Excluding supply of MCB /MCCB / RCBO / Isolator)
12 way, VTPN DB, double door Incomer-MCCB. (Cat No DBVTL012DD of L&T or its Equivalent)
8 way, VTPN DB, double door MCCB Incomer-(Cat No. MCCB DBVTL008DD of L&T or its Equivalent)
12 way, SPN DB, double door
6 way MCB Enclosure Single Door
Supply, of following size and type, 240 / 415 volts, 'C' series, miniature circuit breaker suitable for inductive load.
6 to 32A SP MCB
40 to 63A SP MCB
6 to 32A TP MCB
6 to 32A DP MCB
40 to 63A TP MCB
40 to 63A TP&N/FP MCB
100 A TPN MCB
125 A TPN MCB
Supply and fixing of Blanking plate for above DB.
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
2 X 10 sq. mm + 1 X 6sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required.
3X1.5 sq.mm.
3X2.5 sq.mm.
3X4 sq.mm.
3X6 sq.mm.
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
3 Module (100mmX75mm)
4 Module (125 mmX75 mm)
6 Module (200mmX75mm)
8 Module (125 mmX125 mm)
12 Module (200 mmX150 mm)
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
3 Module
4 Module
6 Module
8 Module
12 Module
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
15/16 A switch
5 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Supply, Installation and Testing of Telephone Socket Outlet including PVC box.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A, 415 V “C” curve TP MCB complete with connections, testing and commissioning etc. as required.
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying, installation, testing & commissioning of Clean compatible ceiling mounted flush type light fixtures 36w LED (BOTTOM OPENABLE) with all accessories complete suitable for cleanroom. Dimension 2 ' x 2'
Clean compatible ceiling mounted flush type light fixtures 18w LED (BOTTOM OPENABLE) with all accessories complete suitable for cleanroom. Dimension 1'x 1'.
Supplying, installation, testing & commissioning of Red light for mice room for emergency working at night with switch from outside the mice room. The light shall get automatically switched off after 15 mins time. Price shall be included with light, switch and control system etc. complete as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I.pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Supply, Installation, Testing and Commissioning of 20 KVA Online UPS Unit (3 Phase In / 1 Phase Out, Backup Time:15 Minutes) complete with Isolation Transformer, SMF Batteries, Heavy Duty Battery Rack, Input and Outout Cables ( Length appx. 5 Mtrs. each), Connectors etc. complete as required. The UPS shall be comprising ofthefollowings. a)Graphical LCD Display b)Communication : Lan and RS485 c) Mannual Bypass Arrangement
Design, Supply, installation, testing, commissioning & handing over of the Integrated Building Management System Suitable for Animal Experimentation Facility comprising of the followings :
BMS Computer System: Server grade Pentium Core i7 (Latest Generation) with 3GHz minimum CPU speed, 512 KB cache, Minimum 8 GB RAM, Minimum 2 TB hard disc, Minimum 42” LED Display (Full HD), DVD/CD-RW Drive, Optical Mouse, 106 keys keyboard, 10/100 Mbps Ethernet card , USB connection, internal modem, Windows 7 and MS-Office installed in Licensed Version etc. complete as required.
BMS System Software : Web Based Graphical Software meeting the requirements in the Given I/O Summary & technical specifications including configuration and facility to create / provide the graphic mapping for all I/O Summary points, animate the Graphics, Navigation between pages, display of logs, changing the time zones, popup alarms, configurable password protection for Building Mgmt. System as per Specifications. Software shall be able to communicate with Lon works, Bacnet, Modbus devices simultaneously, with unlimited user license capacity.
UL listed, BTL certified, Hardware Interface/Soft integrators with inbuilt web browser for third party equipment, Open Protocol Software Integration. These integrators shall be of same make as DDCs and shall contain all necessary ports for software intgeration of below mentioed equipment-
DDC Controller with I/O module, expandable to meet the IO summary listed, The controllers shall be minimum 32 bit Double microprocessor based standalone working on TCP/IP on Bacnet IP with integral web browser, calender fundtion complete with day, month, week, year etc, real time clock & 1 second scan time. DDC working on 230V AC are preferred. The DDC's shall be capable of peer to peer communication without help of communication controller / router / system interface controller / PC and shall communicate with the building LAN directly. These shall come with lockable mounting cabinets duly powder coated connector strip, internal wiring and space to house controller & relays, connector strip step down transformer, MCB, internal wiring. (Contractor shall confirm his I/O provision w.r.t requirement on basis of data point) on AHRAE approved Bacnet protocol only. DDCs shall work on either 230V power supply or shall contain UL listed SMPS in the panel.
DDC for AHUs as per IO summary with 15% spare
Smart Managed 24 Port Switch, Gigabit with 2 SFP Ports.
DDC for Dimmable Lights for control of LUX (not only on & off)
Supply, installation, testing, commissioning of necessary Input sensor transmitters/transducers comprising the following:
Duct type temperature sensor.
Duct type temperature & RH sensor
Differential pressure switch for filters & Blowers
CO² sensor for mice room
CO sensor
On/Off type motorized actuator of 5 Nm torque with operating voltage of 24 Volt AC/DC.
Damper actuator modulating type 5NM
Supply, installation, testing and commissioning of following cables for BMS:
2 Core 1.5 Sqmm, armoured ATC conductor multistranded, Outersheathed, FRLS twisted shielded cable for signals and communication, Surface Laying Considered.
Cat-6 networking cable (Including Accessories)
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required.
Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required.
Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required
4 Zone Fire panel
Supplying, installation, testing & commissioning of CCTV DVR 8 CHANNEL metal body, 4 Audio, AV output, 16 channel. Price shall inlcude voltage converter, Plug points for each camera
Supplying, installation, testing & commissioning of Dome camera 2 MP rating.
Supply and Laying of Video Cable RJ-11 for CCTV camera complete with Connector, Pipes etc. as required.
Supply, Installation, Testing and Commissioning Access Control System compirising of the following- a)Biometric and RF Card Reader- 2 Nos. c)Application Software d) Supply of RF Card suitable for above mentioned Access control System -100 Nos.. The job is completed with supply and installation of Magnetic Door Lock for two Doors, compete with all accessories and suitable for Clean Room Facility.
Supply, Installation, Testing and Commissioning Air Shower, GI powder coated construction single entry type comprising of the followings- a) Working Area: suitable for single entry b) Construction Material : GI c) Cleanliness : Class 1000 / ISO 6 d) Air Balancing : 100 % Fresh Air e) Shower Duration Time : Adjustable f) Particle Retention : 0.3 Micron & Above g) Hepa Filter: Rated 99.97 % @0.3 µm( Micron) Particles h) Pre Filter : 10 -15 Micron, Efficiency : Not less than 90%. i) Door : Flushed Type Entry and Exit Doors made of 5 mm thick Toughened Glass to view inside the metallic frame. The door should have automatic door closures and Electromagnetic Interlocking. j) Control System: Interlocking by Electromagnets through Control Card / Logic Card. Shower duration shall be adjusted through Electronic Timer with LED / LCD Display. k) Entry & Exit : Dual Entry l) Lighting : Complete with LED Lighting Fitting. l)Power Supply : 3 Phase, 415 V AC, 50 Hz.
FABTECH Technologies International Ltd
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .