| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.2 LAccepted-AOC | L1 | Accepted-AOC lowest tenderer | |
| 2 | L2₹27.3 L+₹2.9 L (12.0%)Rejected-Finance | L2 | Rejected-Finance other than lowest tenderer | |
| 3 | L3₹29.4 L+₹5.0 L (20.6%)Rejected-Finance KURUPPAMPARAMBIL PERUMPADAPPU PALLURURHY P O ERNAKULAM KERALA 682006 | ERNAKULAM | KERALA | 682006 | L3 | Rejected-Finance other than lowest tenderer | |
| 4 | L4₹33.0 L+₹8.6 L (35.3%)Rejected-Finance 26 2579 THEVARA PO KOCHI ERNAKULAM KERALA 682013 | KOCHI | ERNAKULAM | KERALA | 682013 | L4 | Rejected-Finance other than lowest tenderer | |
| 5 | L5₹35.0 L+₹10.6 L (43.4%)Rejected-Finance | L5 | Rejected-Finance other than lowest tenderer |
Tender Value
₹32.7 L
EMD Value
₹65,400
Closing Date
28 Jun 2022, 6:00 pmClosed
GE NS KOCHI
Military Engineer Services Garrison Engineer (Naval Services) Kataribagh, Naval Base Post Kochi 682004
PERIODICAL/ROUTINE MAINTENANCE OF CENTRAL AC PLANTS, LOWER SIDE MACHINERIES, DX TYPE AC PLANTS AND PREVENTIVE MAINTENANCE OF COLD STORAGE AT OLD BV YARD COMPLEX AND INHS SANJIVANI HOSPITAL AT NAVAL BASE KOCHI
2022_MES_528207_1
8919/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
Kochi
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE NS KOCHI
₹65,400
Yes
8 Aug 2022
3 Jun 2022
30 Jun 2022
3 Jun 2022
28 Jun 2022
14 Jun 2022
3 Jun 2022 - 13 Jun 2022
Amount
Material & Labour for servicing of shell and tube condenser capacity 10 TR to 20 TR by chemical descaling compound after opening with sides of condensers brushing and reconnecting with replacement of suitable size of packing /gasket in same position if required including testing all as directed by Engineer-in-Charge .
Material & Labour for servicing of shell and tube condenser capacity 21 TR to 50 TR by chemical compound after opening with sides of condensers brushing and reconnecting with suitable size of packing /gasket in same position including testing all as directed by Engineer-in-Charge.
Material & Labour for servicing of shell and tube condenser capacity 51 TR to 150 TR by chemical compound after opening with sides of condensers brushing and reconnecting with suitable size of packing /gasket in same position including testing all as directed by Engineer-in-Charge.
Material & Labour for Monthly servicing including taking out complete air filters from AHU carefully and cleaning, removing dust by using pressure water, greasing shaft and bearings, alignment of blower motor, tightening of blower V belt and refixing filters after drying all as specified and directed by Engineer-in-charge. Note:-Replacement of Air Filter shall be responsibility of contractor if damage occurs while removing or refixing.
Material & Labour for Monthly servicing of cooling tower including washing of PVC fills by using mild detergent, clearing bottom tank to remove mud & dust and cleaning of pot strainer after removing the strainer from pot including removal and refixing of nut & bolts of various capacity if required at site all up to 240 TR capacity AC Plant all as specified and directed by Engineer-in-charge.
Material & Labour for attending day to day complaints pertains to various Central AC plant of any capacity as and when required by Ref-Mech and helper, with necessary T&P for checking the equipment at existing location, find out the faults to the equipments, complete and rectification of minor problems (sensor error, compressor control panel resetting, oil/ suction/ discharge pressure, replacement of transducer etc) to make the plant functional in all respect all as directed by the Engineer- in-Charge. Note: 1. The work covered under Sl.No 1 to 3 shall be carried out once in 3 Months. 2. Works covered under item No 1 to 5 of BOQ shall be executed at all AC plants installed at various locations inside the Naval Base and schedule for servicing may be obtained from MES at the time of execution. 3. Complaint shall be collected from JE/Engineer- in-charge on daily basis. 4. Work covered under BOQ Serial No 1 to 6 shall be outside the scope of this item. 5. The item No 6 shall be operated for attending the minor running problems of AC plants under all the area in Naval Base and if any major replacement of spares required shall be intimated to this department.
Material & Labour for painting of central AC plant cooling tower with two coats of synthetic enamel spray paint of existing colour paint after preparation of existing surface upto 100 TR capacity including marking the details of cooling towers all as specified and as directed by EIC.
Preventive Maintenance of monthly and check up of Bitzer Blast cold storage 48000 BTU of 1 unit including 1 ODU+ 1 IDU (-)30 °C operation with R- 404A Refrigerant gas two stage, semi hermetically sealed compressor consisting 4 cylinder, controlled with electronically operated solenoid valve for liquid system complete all as specified and directed.
Preventive Maintenance monthly and check up of Danfoss cold room plant (-)18 °C with(50000 BTU) of 2 units including 2 ODU +2 IDU, R-404 A Refrigerant The compressor hermetically sealed , equipped with electronically controlled solenoid valve system. The system have individual accumulated to verify and control the liquid gas flow including micro processor controlled electrical panel indoor blower unit controlled with fans and other electrical circuits with electronically operated solenoid valve for liquid system, complete all as specified and directed
Preventive Maintenance monthly and check up of Blue star cold room of capacity up to 30000 BTU of 1 units including 1 IDU+1ODU, R-22 Refrigerant temp to be stabled +4 °C equipped with electrically operated micro processor control panel including blower fans and other electrical circuits of the system to be checked complete all as specified and directed by Engineer-in-charge.
Preventive Maintenance monthly and check up of Bluestar cold room at Sanjivani Hospital plant (-) 18 °C with (10000 BTU) of 2 units including 2 IDU + 2 ODU,R-404 A Refrigerant. The compressor hermetically sealed. Equipped with electronically controlled solenoid valve system. The system have individual accumulated to verify and control the liquid gas flow including micro processor controlled electrical panel indoor blower unit controlled with fans and other electrical circuits of the entire system to be checked complete all as specified and directed by Engineer-in-charge.
Preventive Maintenance monthly and check up of Blue star cold room at Sanjivani hospital temp to be stabled +4 °C with capacity up to 12000 BTU of 2 units including 2 IDU+2 ODU, R-22 Refrigerant including in door blower unit equipped with electrically operated micro processor control panel including blower fans and other electrical circuits of the system to be checked complete all as specified and directed by Engineer-in-charge. Notes for serial No 8 to 12 (a) All Major spares shall be measured and paid under relevant items Here in after. (b) Each servicing/checkup of cold storages by OEM/authorised dealers shall be carried out once in two months up to contact duration, and at any time of breakdown call by MES rep. (c)The job above quoted shall be included for all labour cost, except electrical control panels with parts
Supply & fix of suction valve & discharge valves of suitable size for different cold storage units complete all as directed by Engineer in charge.
Supply only evaporator fan motor capacity of 400 mm dia for meat room along with leaf suitable for existing bracket of outdoor unit of Make : Bitzer/Danfoss/blue star complete all as directed by Engineer in charge.
Supply only evaporator fan motor capacity of 600 mm dia for blast room along with leaf suitable for existing bracket of outdoor unit of Make : Bitzer/Danfoss/blue star complete all as directed by Engineer in charge.
Supply only evaporator fan motor capacity of 350 mm dia egg room along with leaf suitable for existing bracket of outdoor unit Make : Bitzer/Danfoss/blue star complete all as directed by Engineer in charge.
Supply only evaporator fan motor capacity of 0.5-0.75 HP for freezer and cold room along with leaf suitable for existing bracket of outdoor unit of Make : Bitzer/Danfoss/blue star complete all as directed by Engineer in charge.
Supply only Condenser fan motor capacity of 0.5 HP-0.75 HP along with leaf suitable for existing bracket of outdoor unit Make : Bitzer/Danfoss/blue star complete all as directed by Engineer in charge.
Supply and replace power contactor MO, 25-45 Amps complete all as directed by Engineer in charge.
Supply and replace single phasing preventer, suitable for 380V-415V, AC all as specified and directed.
Supply and replace thermal overload relay for ML/MO/MNX contractors capacity up to 42 Amp all as specified and directed delay range 6 to 42 Amps all as specified and directed.
Supply and replace MCB TPN 20-32Amp,C curve, 10 KA including taking out old unserviceable one complete all as specified and directed.
Supply and replace MCB TPN 63 Amp,C curve, 10 KA including taking out old unserviceable one complete all as specified and directed.
Supply and fix Amps controller suitable for different cold storage units
Supply only HP/LP Switch
Supply only Solenoid Valve
Supply only Expansion Valve
Supply and fix of digital temperature gauge of subzero model SZ7504 of working Temperature range -50°C to +99°C complete all as specified and directed.
Supply only Catchall -sub cooling Make: Danfoss/Indfoss
Supply only liquid line drier ( Model 604) Make: Danfoss/Indfoss
Supply only Oil Pressure Switch Make: Danfoss
Supply only drain heater working on 230 V complete all as specified and directed
Supply only Cold Room Defrost Heater working on 230 V complete all as specified and directed
Supply and fixing in replacement of weather proof LED tube lights, 230Volt,along with copper cable as required for connecting existing points at inside cold rooms complete all as specified and directed.
Supply only Compressor oil suitable working for existing R-134 and R-404 complete all as specified and directed.
Material & Labour for Leak testing of Cold storage unit of any capacity ,including filling of nitrogen gas for pressure testing, finding leaks, Vacuumising the system, necessary brazing work, charging with suitable refrigerant gas of required quantity, testing for proper functioning complete all as specified and directed. Notes: 1.Nitrogen & refrigerant gas will be measured and paid separately. 2.Empty cylinder will returned to contractor after usage.
Supply and charging Refrigerant Gas R 404A in sealed cylinder
Supply and charging Refrigerant Gas R 22 in sealed cylinder
Supply only Nitrogen gas contains 12 PSI of pressure in each cylinder of 6 cubic metre.
Supply and fixing in replacement of single core copper cable of size 6 sqmm connection along with copper lugs in existing starter connections/pump/motor connections etc complete all as specified and directed
Supply and replace power contactor MO, 25-45 Amps.
Supply and replace thermal overload relay for ML/MO/MNX contractors capacity up to 42 Amp all as specified and directed delay range 6 to 42 Amps complete all directed.
Ditto all as per Sl Item No 42, but for TP 20-32 Amps,C curve, 10 KA.
Ditto all as per Sl Item No 42, but for TP 40-63 Amps,C curve, 10 KA.
Supply & Fix Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc, not exceeding 10 kg each brackets, conforming to Fe-290 Grade-E-165 complete all as directed.
Material & Labour for Repair/Replacement of copper refrigerant pipe lines suitable for existing units as recommended by OEM with insulation between indoors and out door units as per the site condition. Note: Suction & Discharge lines shall be treated as one Unit for One RM
Material & Labour for attending day to day complaints pertains to various capacity of cooling appliances as and when required by Refrigerator Mech and helper, with necessary Tools & Plant for checking the equipment at existing location, find out the faults to the equipments, complete and rectification of minor problems (compressor control panel resetting with electrical components like replacement of lugs/ pins, MCB resetting, electrical wiring connections gas top up (gas shall be measured & paid separately under relevant item), to make the AC functional in all respect all as directed by the Engineer-in-charge. Notes: 1. Works covered under item No.8 to 12 only shall be executed at various locations inside the Naval Base. 2. Complaints/ service schedule list shall be collected from concerned JE/Engineer-in-Charge and report back on daily basis. 3. The schedule items other than 8 to 12 shall be outside the scope of this item. 4. A penalty of Rs.1000/- per day will be levied in case breakdown of equipment more than 48 hrs from the time of complaint registration due to none attending.
Material & Labour for removing of old gland packing of chilled water/condenser water pump motor of any capacity and refixing new gland packing of size existing at site, tightening nuts and bolts properly to arrest water leakage complete all as specified and directed by Engineer in Charge.
Amount of Credit Schedule shall be deducted to arrive the Contract Sum.
General Engineering and Constructions
Albert Rebello and Company
AR Traders
S. M. Enterprises
Sreema Enterprises
Green Ray Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .