NAMDHA WATER SUPPLY PROJECT: VAPI MUNICIPAL CORPORATION PHASE 2
291914
09/WSS/2025-26
Open
Civil Works - Water Works
Works
Vapi
16 documents required · 16 mandatory
₹21,240
Municipal Corporation City of Vapi
₹12.5 L
31 Mar 2026
31 Mar 2026
31 Mar 2026
30 Apr 2026
31 Mar 2026
SUMMARY (SCHEDULE-B)
NAMDHA WATER SUPPLY PROJECT (PHASE-2)
BID DOCUMENTS FOR
NAMDHA WATER SUPPLY SCHEME: WORKING SURVEY, SOIL INVESTIGATION,DESIGN OF WATER SUPPLY SCHEME.WORK INCLUDING DESIGN &
CONSTRUCTION, TESTING & COMMISSIONING OF PROVIDING, SUPPLYING, LOWERING, LAYING AND JOINTING DI PIPELINE FOR RISING MAIN & GRAVITY MAIN,
PROVIDING, SUPPLING, ERECTING & TESTING OF PUMPING MACHINERIES, CONSTRUCTION OF HOUSE CONNECTION & RCC ROAD REINSTATEMENT & SITC
WORK OF INSTRUMENTATION WORK & SCADA SYSTEM AT GRAVITY DISTRIBUTION NETWORK LOCATION ETC. FOR NAMDHA WATER SUPPLY SCHEME (PHASE-2),
WORK INCLUDING 5 YEARS OF OPERATION & MAINTENANCE FOR VAPI MUNICIPAL CORPORATION,DISTRICT: VALSAD.”
SR NO SCHEDULES NAME OF WORK AMOUNT (RS.)
NAMDHA WATER SUPPLY SCHEME
1 SCHEDULE - B1 GRAVITY MAIN PIPELINE
2 SCHEDULE - B2 RISING MAIN PIPELINE
3 SCHEDULE - B3 SUPPLYING, ERECTING, TESTING & COMMISSIONING OF PUMPING MACHINERIES
4 SCHEDULE - B4 CONSTRUCTION OF HOUSE CONNECTION- 2013 Nos.
SITC WORK OF INSTRUMENTATION WORK & SCADA SYSTEM AT GRAVITY DISTRIBUTION NETWORK
5 SCHEDULE - B5
LOCATION FOR NAMDHA WATER SUPPLY
Total Amount (1+2) in Rs.
Total Amount (1+2) in Rs.
6 SCHEDULE - C1 Operation & Maintenance (For 5 Years) NAMDHA WATER SUPPLY SCHEME
Total Amount (1+2) & with O & M Rs.
Total Amount (1+2) & with O & M Rs.
I / We am / are willing to carry out the work at…………………………………… % above / below percent/at par (should be written in figures and words) of the
estimated rates mentioned above . Amount of my/ our tender works out as under.
* Estimated amount * Estimated amount
Put to tender Rs …… Put to tender Rs ……
Deduct :....... % below Rs……… Add :....... % above Rs………
Total Rs…………. Total Rs………….
* ( Please strike out whichever is not applicable ).
SUMMARY (SCHEDULE-B)
NAMDHA WATER SUPPLY PROJECT (PHASE-2)
NAMDHA WATER SUPPLY SCHEME: WORKING SURVEY, SOIL INVESTIGATION,DESIGN OF WATER SUPPLY SCHEME.WORK INCLUDING DESIGN & CONSTRUCTION, TESTING
& COMMISSIONING OF PROVIDING, SUPPLYING, LOWERING, LAYING AND JOINTING DI PIPELINE FOR RISING MAIN & GRAVITY MAIN, PROVIDING, SUPPLING, ERECTING &
TESTING OF PUMPING MACHINERIES, CONSTRUCTION OF HOUSE CONNECTION & RCC ROAD REINSTATEMENT & SITC WORK OF INSTRUMENTATION WORK & SCADA
SYSTEM AT GRAVITY DISTRIBUTION NETWORK LOCATION ETC. FOR NAMDHA WATER SUPPLY SCHEME (PHASE-2), WORK INCLUDING 5 YEARS OF OPERATION &
MAINTENANCE FOR VAPI MUNICIPAL CORPORATION,DISTRICT: VALSAD.”
SCHEDULE - B1 : GRAVITY MAIN PIPELINE
SR. No. ITEM DESCRIPTION QTY UNIT RATE (RS.)
Item No.1: Providing and supplying D. I. K-7 grade pipes for following nominal bore diameter with internal cement mortar
lining including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading,
1 conveyance to departmental stores, stacking etc. complete. (IS 8329-2000).
Item No.2: Manufacture, Supply & Delivery of Ductile Iron Flange socket spigot bends, tees, reducers or any other specials
as per BS-EN-545/1995 Class-A series K12 suitable for use with DI pipes manufactured as per IS:8329/1994 delivery of
specials is to be made to GWSSB store or site of works any where in Gujarat including all taxes, liading, unloading, carting,
2 stacking, insurance, inspection charges, octroi etc. complete. (With external bitumen & zinc coating & internal cement
mortar lining) Socket & Spigot Type
Upto 300 mm Dia. 7761.34 Kg 148.00
2a Above 300 mm Dia. 4133.81 Kg 151.00
Item No.3: Providing and supplying ISI mark CI D/F Sluice Valves as per IS : 14846 (Latest Edition )of following class and
diameter including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading,
3 conveyance to departmental stores, stacking etc. complete. PN-1 With hand/wheel cap operated (Alt-1 type long body)
Item No.4: Providing and supplying C. I. Temper proof Air valves with ss 304 Float gun metal- nozzle of approved make &
quality of following class and diameter including all taxes, insurance, transportation, freight charges, octroi, inspection
4 charges, loading, unloading, conveyance to departmental stores, stacking etc. complete. Air Valves Double Acting (DS2)
Item No.5: Excavation for pipe line trenches incl. all safety provisions using site rails and stacking excavated stuff up to a
5 lead of 90 mts. cleaning the site etc. complete for lifts and strata as specified. 0 to 1.5 Mt. Depth
In all sorts of soil and soft murrum 5638.50 Cu.M 102.35
5a In hard murrum,boulders,incl. Macadam road 4027.50 Cu.M 155.25
5b Soft rock 4027.50 Cu.M 187.45
5c In Hard rock. 2416.50 Cu.M 427.80
1.5 to 3 Mt. Depth
In all sorts of soil and soft murrum 59.25 Cu.M 112.70
5e In hard murrum,boulders,incl. Macadam road 71.10 Cu.M 170.20
5f Soft rock 59.25 Cu.M 205.85
5g In Hard rock. 47.40 Cu.M 446.20
Item No.6: Lowering, laying and jointing C. I. S & S Spun pipes suitable for Tyton joints / Mortar lined D. I. Pipes of various
classes with CI / MS specials of following diameters in proper position, grade and alignment as directed by Engineer-in-
6 charge including hydraulic testing etc. comp.
6i 600 mm dia 15.00 Rmt 464.60
Item No.7: Lowering, laying and jointing in position following C. I. / D/F Sluice valves including cost of all labour, jointing
7 material, including nut bolts and giving satisfactory hydraulic testing, etc. complete. Sluice valve
Item No.8: Lowering, laying and jointing in position following C. I. / D/F Air valves including cost of all labour, jointing
8 material, including nut bolts and giving satisfactory hydraulic testing, etc. complete.(double ball Flanged )
Item No.9: Construction of valves chambers in brick or bela stone masonry, locally available in CM 1:6. Foundation concrete
150 mm thick in CC 1:4:8 of trap metal size 25 mm to 40mm thick, inside cement plaster in CM 1:3 and cement pointing
outside in CM 1:3 and top cover of precast RCC slab 100 mm thick (with key hole in two parts, each with handles or MS bar
9 etc. completed as giver size) upto 1 mt depth from GL to pipe invert level incl. completed civil works but excluding cost of
excavation and refilling, with cast in situ RCC slab in one single piece with fixing of CI MH frame and cover with 23 mm thick
brick masonary wall in CM 1:6 : With precast slab in two parts 15 mm-
SV & ScV. Chamber - 0.6 x 0.6 x 1.0 m (For valves of 50, 65, 80, 100, 125 & 150 mm dia.)
9a Air Valve Chamber - 1.3 x 1.3 x 1.0 m (For 40 to 200 mm dia.) 34.00 No. 13053.65
10 Item No.10: Extra depth of Valve chamber beyond 1.00 mt. depth.
10a SV & ScV. Chamber - 0.6 x 0.6 x 1.0 m (For valves of 50, 65, 80, 100, 125 & 150 mm dia.) 3.70 mt 3767.40
10b Air Valve Chamber - 1.3 x 1.3 x 1.0 m (For 40 to 200 mm dia.) 16.10 mt 6996.60
SR. No. ITEM DESCRIPTION QTY UNIT RATE (RS.)
Item No.11: Thurst Block : Providing and Casting in situ C.C. for Thrust Block in grade M-20 (Proportions as per mix design or
as per table 9 of IS456 2000 in masses by weight batching) using granite, quartzite trap metal of size 6 mm to 20 mm for
11 RCC work, including scaffolding centering, formwork, needle vibrated consolidation, curing complete up to 6 meter depth or
height etc. complete for Thrust Block work. (excluding cost of reinforcement)
Footing for column or foundation ( with form work) 65.68 Cum 6348.00
Item No.12: Reinforcement for Thrust Block : Supplying cutting, bending, binding and placing in position steel as per plan
12 and design and as per ISS 2502 including cost of steel and binding wire for structures only including lift up to 6 meter height
or depth below G.L., Do-Thermo mechanically treated (TMT) bars Fe-415 grade for all diameters. 3940.82 Kg 84.19
Item No.13: Culvert crossing.- Constuction of RCC support for culvert crossing at various location on pipeline route. Work
including excavation of pits in all type of strata, 100 mm thick PCC in M10 grade concrete, Providing and casting RCC
Column and Footing in situ mass cement concrete in grade M-15 ( proportions as per mix design or as per table 9 of IS:456-
2000 ) RCC work, including scaffolding centering, formwork, needle vibrated consolidation, curing complete upto 6 m depth
13 or height with centering and shuttering etc. complete.Supplying cutting, bending, binding and placing in position steel as
per plan and design and as per ISS 2502 including cost of steel and binding wires for reservoirs / structures only including lift
upto 6 m height or depth below GL for all diameters. Supply, and installaion of 8 mm thick MS clamp for pipe anchorage
with required nut bolts and 3 mm sacrificing plate at RCC column and bottom of pipe etc. completed as per drawing and
minimum BoQ.- RCC Support @ 4 mt C/C
Item No.14: Refilling the pipeline trenches incl. ramming, watering, consolidating disposal of surplus stuff as directed
within a radius of 3 km 15445.00 Cum 25.30
Item No.15: RCC Road Reinstatement : Construction of RCC roads including all civil works with labour and material cost.
Providing and laying RCC M20 grade concrete complete work including form work, curing etc. completed 10302.15 SQ. mt 963.16
Asphalt Road Reinstatement : asphalt roads with 150 mm sand, 200 mm spouls, 150 mm black trap metal (25-40 mm size),
150 mm aggregate (6-12 mm), quarry dust as inert material, watering, ramming with roller, tack coat 1 kg/ sqm, pre-mix
15a carpet 50 mm and seal coat 6 mm of bitumen 80/100 over refilled soil of at least 200-300 mm on top of pipe (depending
upon minimu cover of 0.9 m to 1 m depending upon topography) 3435.00 SQ. mt 704.78
Total for Schedule-B1(Rs.) =
SUMMARY (SCHEDULE-B)
NAMDHA WATER SUPPLY PROJECT (PHASE-2)
NAMDHA WATER SUPPLY SCHEME: WORKING SURVEY, SOIL INVESTIGATION,DESIGN OF WATER SUPPLY SCHEME.WORK INCLUDING DESIGN & CONSTRUCTION, TESTING &
COMMISSIONING OF PROVIDING, SUPPLYING, LOWERING, LAYING AND JOINTING DI PIPELINE FOR RISING MAIN & GRAVITY MAIN, PROVIDING, SUPPLING, ERECTING &
TESTING OF PUMPING MACHINERIES, CONSTRUCTION OF HOUSE CONNECTION & RCC ROAD REINSTATEMENT & SITC WORK OF INSTRUMENTATION WORK & SCADA
SYSTEM AT GRAVITY DISTRIBUTION NETWORK LOCATION ETC. FOR NAMDHA WATER SUPPLY SCHEME (PHASE-2), WORK INCLUDING 5 YEARS OF OPERATION &
MAINTENANCE FOR VAPI MUNICIPAL CORPORATION,DISTRICT: VALSAD.”
SCHEDULE - B2 : RISING MAIN PIPELINE
RATE TOTAL AMOUNT
RATE TOTAL AMOUNT
SR. No. ITEM DESCRIPTION QTY UNIT
Item No.1: Providing and supplying D.I. K-9 grade pipes for following nominal bore diameter with internal cement mortar
lining including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading,
1 conveyance to departmental stores, stacking etc. complete. (IS 8329-2000). For sewerage project cement mortor lining
shall be with sulphate resistance cement.
Item No.2: Manufacture, Supply & Delivery of Ductile Iron Flange socket spigot bends, tees, reducers or any other
specials as per BS-EN-545/1995 Class-A series K12 suitable for use with D.I.Pipes manufactured as per
2 IS:8329/1994delivery of specials is to be made to VPMC store or site of works any where in Gujarat including all taxes,
liading, unloading, carting, stacking, insurance, inspection charges, octroi etc. complete.Socket & Spigot Type
Above 300 mm Dia. 5428.63 Kg 151.00
Item No.3: Providing and supplying ISI mark CI D/F Sluice Valves as per IS : 14846 (Latest Edition) of following class and
diameter including all taxes, insurance, transportation, freight charges, octroi, charges, loading, unloading, conveyance
to departmental stores, stacking etc. complete. Hand operated Alt1 type : PN
Item No.4: Providing and supplying C. I. Temper proof Air valves with SS 304 Float gun metal- nozzle of approved make &
quality of following class and diameter including all taxes, insurance, transportation, freight charges, octroi, inspection
4 charges, loading, unloading, conveyance to departmental stores, stacking etc. complete. Temper Proof AV With Isolating
Sluice Valve (PN 1.6)
Item No.5: Excavation for pipe line trenches for water supply, sewerage line, manhole etc. all with shoring and struting if
required as per required gradient and line including safety provisions using site rails and stacking excavated stuff including
5 up to all required lead cleaning the site etc. complete for all lifts and strata as specified. For 0 to 1.5 m :
In all sorts of soil and soft murrum
5a In hard murrum,boulders,incl. Macadam road 720.15 Cum 155.25
5b In soft rock and/or masonry in CM or L M or Lime Concrete. 720.15 Cum 187.45
5c In hard rock and / or in C. C. 1:2:4 or RCC with blasting and chiseling or by chiseling only. 432.09 Cum 427.80
5d For 1.5 to 3.0 m : In all sorts of soil and soft murrum 41.43 Cum 112.70
5e In hard murrum,boulders,incl. Macadam road 49.72 Cum 170.20
5f In soft rock and/or masonry in CM or L M or Lime Concrete. 41.43 Cum 205.85
5g In hard rock and / or in C. C. 1:2:4 or RCC with blasting and chiseling or by chiseling only. 33.15 Cum 446.20
Item No.6: Lowering, laying and jointing C. I. S & S Spun pipes suitable for Tyton joints / Mortar lined D. I. Pipes of
various classes with CI / MS specials of following diameters in proper position, grade and alignment as directed by
Engineer-in-charge including hydraulic testing etc. comp.
Item No.7: Lowering, laying and jointing in position following C. I. / D/F Reflux valves, Butterfly valves, Sluice valves and
Air valves including cost of all labour, jointing material, including nut bolts and giving satisfactory hydraulic testing, etc.
complete. Sluice Valve
Temper Proof Air Valve
Item No.8: Providing, supplying and installation of air riser (flanged Tee) on the pipe line at suitable place as per design
& directed by Engineer-in charge. Work including excavation of pit, refilling, levelling of gorund after completion work.
This includes supply, delivery and installation of GI/ M.S. double flanged pipe. MS pipe having flange thickness
8 conforming to IS 3589-2001, R.C.C. foundation block & column in C.C. M-150 as per drg and indicated in minimum BoQ
etc. complete. The length of riser pipe is 3.00 mt from above pipe top -Temper Proof Air Valve
Item No.9: Construction of valves chambers in brick or bela stone masonry, locally available in CM 1:6. Foundation
concrete 150 mm thick in CC 1:4:8 of trap metal size 25 mm to 40mm thick, inside cement plaster in CM 1:3 and cement
pointing outside in CM 1:3 and top cover of precast RCC slab 100 mm thick (with key hole in two parts, each with handles
or MS bar etc. complete as given size) upto 1 mt depth from GL to pipe invert level incl. complete civil works but
9 excluding cost of excavation and refilling, with cast in situ RCC slab in one single piece with fixing of CI MH frame and
cover (excluding cost of CI-MH frame and cover) with 23 mm thick brick masonary wall in CM 1:6 With precast slab in two
(As per rate analysis) for above 1.3 mt size chamber 0.00 -
Item No.10: Extra depth of Valve Chamber beyond 1.00 mt. depth. as per attached calculation sheet
For 1.5 m X 1.5 m Chamber : 0.90 Rmt 10440.00
Item No.11: Thurst Block : Providing and Casting in situ C.C. for Thrust Block in grade M-20 (Proportions as per mix design
or as per table 9 of IS456 2000 in masses by weight batching) using granite, quartzite trap metal of size 6 mm to 20 mm
for RCC work, including scaffolding centering, formwork, needle vibrated consolidation, curing complete up to 6 meter
depth or height etc. complete for Thrust Block work. (excluding cost of reinforcement) 229.70 Cum 6348.00
Item No.12: Reinforcement for Thrust Block : Supplying cutting, bending, binding and placing in position steel as per plan
12 and design and as per ISS 2502 including cost of steel and binding wire for structures only including lift up to 6 meter
height or depth below G.L., Do-Thermo mechanically treated (TMT) bars Fe-415 grade for all diameters. 18376.00 Kg 84.19
Item No.13: Refilling the pipeline trenches incl. ramming, watering, consolidating desposal of surplus stuff as directed
within a radius of 3 km. 2595.72 Cum 25.30
RATE TOTAL AMOUNT
RATE TOTAL AMOUNT
SR. No. ITEM DESCRIPTION QTY UNIT
Item No.14: Asphalt Road Reinstatement : asphalt roads with 150 mm sand, 200 mm spouls, 150 mm black trap metal (25-
40 mm size), 150 mm aggregate (6-12 mm), quarry dust as inert material, watering, ramming with roller, tack coat 1 kg/
sqm, pre-mix carpet 50 mm and seal coat 6 mm of bitumen 80/100 over refilled soil of at least 200-300 mm on top of
pipe (depending upon minimu cover of 0.9 m to 1 m depending upon topography) 722.50 Sq.m. 704.78
RCC Road Reinstatement : Construction of RCC roads including all civil works with labour and material cost. Providing and
laying RCC M20 grade concrete complete work including form work, curing etc. completed 2167.50 Sq.m. 963.16
Item No.15: Road /Canal Crossing : Drilling of following dia horizonal borehole for water main pipeline crossing under the
road incl in all strata with required length incl fixing of following dia MS casing pipe with pusing etc completed various
size of pipe for following dia pipe : with MS Casing Pipe without water main (only Casing pipe)
15 Dia of Drilling of borehole: 1300 mm
Dia of MS Casing pipe : 1200 mm
Dia of Water main pipe line : 600 mm 25.00 Rmt 47367.78
Total for Schedule-B2(Rs.) =
SUMMARY (SCHEDULE-B)
NAMDHA WATER SUPPLY PROJECT (PHASE-2)
NAMDHA WATER SUPPLY SCHEME: WORKING SURVEY, SOIL INVESTIGATION,DESIGN OF WATER SUPPLY SCHEME.WORK INCLUDING DESIGN & CONSTRUCTION,
TESTING & COMMISSIONING OF PROVIDING, SUPPLYING, LOWERING, LAYING AND JOINTING DI PIPELINE FOR RISING MAIN & GRAVITY MAIN, PROVIDING,
SUPPLING, ERECTING & TESTING OF PUMPING MACHINERIES, CONSTRUCTION OF HOUSE CONNECTION & RCC ROAD REINSTATEMENT & SITC WORK OF
INSTRUMENTATION WORK & SCADA SYSTEM AT GRAVITY DISTRIBUTION NETWORK LOCATION ETC. FOR NAMDHA WATER SUPPLY SCHEME (PHASE-2), WORK
INCLUDING 5 YEARS OF OPERATION & MAINTENANCE FOR VAPI MUNICIPAL CORPORATION,DISTRICT: VALSAD.”
SCHEDULE - B3 : SUPPLYING, ERECTING, TESTING & COMMISSIONING OF PUMPING MACHINERIES
ITEM DESCRIPTION QTY UNIT RATE (RS.)
No. AMOUNT (Rs.)
Item No.1: SUBMERSIBLE TYPE PUMPSET: Supply, installation, testing & commissioning of Submerged Submersible pumpsets
with suitable for working on three phase, 50 Hz±3%,415V±10% AC supply, suitable RPM with 3 core flat copper cable from
pump to starter panel with cable end terminations, all supports, clamp, pipe fittings, mechanical seal, bearing bush,
strainer, pump sensors and other protection, pump control unit etc. suitable contruction of foundation/ installation device
1 with cable length from pumps to panels & of following Material of Construction: M.O.C :- Casing : CI, Impeller : SS CF8M,
Wearing ring & bearing bush : Bronze, TC Mechanical seal, CS/SS bearing, SS shaft with sleeve, SS strainer & MS motor body,
Fasteners : SS 316L, Guide Rail : SS 316, Lifting Chain : SS
Capacity of pump - 6299 lpm & 45.5 m. head (75 kW/ 100 HP) - 2 working + 1 standby - WTP (46 MLD) to JN A Zone-1 &
Item No.2: Manufacture, Supply & Delivery of Electric Resistance Welded (Up to 400mm)/Submerged Arc Welded (Above
400mm) M.S.Pipe having beveled ends plate or coil conforming to IS-3589-2001 or its latest revision/ ammendment for
following thickness outside diameter at GWSSB store or site anywhere in Gujarat State including Lowering, laying, jointing
& welding in correct position to correct line & level M.S.Pipe with outside & Inside lining/Epoxy paint on pedestal or chairs
2 upon prepared or prepared bedding in trenches the rates include conveyance from store to site of work loading, unloading
conveyance to Department stores, stacking etc. complete including all taxes, insurance, transportation, freight charges,
octroi, inspection charges, loading, unloading conveyance to Departmental stores, stacking etc. all complete. WTP (46
MLD) to JN A Zone-1 & Zone
273 mm Dia. (5 mm Thick)- Delivery Pipe
2a 610 mm Dia. (6.3 mm Thick)- Header Pipe 7.50 Rmt 7211.05
Item No.3: Butter Fly Valve : SITC of Electrcally Gear operated ISI mark CI D/F Butterfly Valve as per IS 13095, PN
with sleeve of EPDM & disc, shaft & internal parts of SS 410 along with gaskets and all other necessary hardware etc.
of following diameter including all taxes, insurance, transportation, freight charges, Inspection Charges loading unloading,
3 conveyence to pump house stacking, security etc. complete as per IS and Specification. WTP (46 MLD) to JN A Zone-1 &
250 mm dia - On Delivery pipe - PN 1.0 3.00 Nos. 159650.90
3a 600 mm dia - On Header pipe - PN 1.0 1.00 No. 205946.05
Item No.4: Reflux Valve : Providing and supplying ISI mark CI D/F Reflux Valves as per IS:5312 (Latest Edition) of following
class and diameter including Lowering, laying & jointing in position following Reflux Valve including cost of all labour,
jointing material, including nut bolts and giving satisfactory hydraulic testing etc. complete. including all taxes, insurance,
4 transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking
etc. complete. WTP (46 MLD) to JN A Zone-1 & Zone
250 mm dia - On Delivery pipe - PN 1.0 3.00 Nos. 27846.90
Item No.5: Air Cushion Valve with Cast Iron Body : Providing, supplying, lowering & laying C. I. Air cushion valves of
approved make & quality of following class and diameter including Lowering, laying & jointing in position following Air
Valve including cost of all labour, jointing material, including nut bolts and giving satisfactory hydraulic testing etc.
5 complete. including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading,
conveyance to departmental stores, stacking and including cost of all labour, jointing material including nut bolts and
giving satisfactory hydraulic testing etc. complete.
150 mm Dia. : Class-15 - WTP (46 MLD) to JN A Zone-1 & Zone 2 107282.75
Item No.6: Supply, installation, testing & commissioning of flange ends Expansion Bellow as per EJMA standards of overall
length of minimum 300 mm, designed for 15 mm axial compression and 5 mm axial extension with tie rods etc. of following
6 MOC & pressure ratings. MOC: Bellows: SA 240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS
2062 Gr. B (Drilling as per IS 1538 / IS 6392 ) & Limit Rods & Nuts: CS - IS 1367. WTP (46 MLD) to JN A Zone-1 & Zone
Item No.7: MS Specials - Manufacturing, Supply, Delivery of M.S. Specials from MS plate of 5.6 mm thick confirming to
relevent IS including all taxes, duties, insurance, transformation, freight, octoroi, inspection, loading, unloading,convey to
7 site,stacking etc. compete.
Flanged Ended - WTP (46 MLD) to JN A Zone-1 & Zone 2 1300.00 kg 98.00
Item No.8: Design, Supply, Installation, Testing, Commissioing of Bourdon Type Presuure Guage, + 1 & accuracy, Direct
bottom 1/2" NPT (M) process connection, IP 67, Glycerine filled, SS304 case with Bayonel Type Bezel, SS316 L Bourdon
8 Tube, SS316 movement material, Aluminium dial with black graduation on white background, Micro Zero adjustable pointer,
neoprene gasket, Blow out disc, shatter proof glass, SS tag plate as per IS 3624. - 0 to 1 Kg/cm2.
150 mm dia. - WTP (46 MLD) to JN A Zone-1 & Zone 2 4.00 No 1727.00
Item No.9: Full Bore Electromagnetic Flow Meter- Regular Power operated: Design, Supply, Installation, Testing,
Commissioning of Full Bore Electromagnetic flow meter with factory calibrated, Regular Power Operated, flanged
connection, Flow sensor, Indicator, transmitter and totaliser with all accessories viz. surge arrestor, associated cables,
cabinets, hardwares, etc complete as per following specifications: 1. Flow Meter / Sensor : DC pulsed type, IP
Protection, Flanged process connection as per IS 1538 or equivalent standard, SS304/ Metallic Alloy Flow Tube, SS316/ SS
316 L/ Hastelloy Sensor, SS316/ Hastelloy Grounding Ring/ Inbuilt Grounding Electrode, Neoprene/ Polyurethane/ Hard
9 Rubber/ Rilsan lining, SS304/ Die Cast Aluminium/ Carbon steel with Anticorrosive Paint Coil Housing with Junction Box, CS
flanges. 2. Flow Transmitter / Converter (Remote Field Mounted) : Microprocessor based, Modular design, 2 line LCD for
indication of actual flow rate, forward, reverse, sum totaliser display, ±0.5% accuracy at 0.3 to 4 m/sec velocity, 4 to
mA with HART/Modbus output, one scalable pulse, one status output, IP 67 protection, Die cast aluminium/ polycarbonate/
SS316 with Anticorrosive Paint/ PU finish with glass window enclosure, Inbuilt EEPROM and Data Logger, 20 meters cable
length for sensor to transmitter communication etc. alongwith wall mounted/ stand mounted cabinet.
On Header Pipe - 400 mm NB - WTP (46 MLD) to JN A Zone-1 & Zone 2 1.00 No. 211120.00
Item No.10: EOT Crane : Providing & erecting single girder type fully electrically operated E.O.T crane with elecrically
operated hoist, class II duty, geared travelling trolly with seven mts. Lift complete with long travel rail track (40 mm
sq.bar), moving or cross girder, all three motions electrically operated by suitable rating motor IP 54, control panel & down
10 control block, brake, safety device, cables from motor to starter panel & other required accessories & tested as per IS
Specifications. - Span - 9.00 m, travel - 12 m. & Lift - 10 m.
3 Tonnes capacity 1.00 No 534187.50
11 Item No.11: Nuts and Bolts MOC: SS 30.00 Kg 300.00
12 Item No.12: Slab Cutting: Slab to be cut by diamond cutter blade 3.00 Job 15000.00
Item No.13: 11 kV Two Pole Structure Assembly: SITC of 11 kV double pole 9 meter high structure made of 6" X 3" 'I" section
girder, 4" X 2" channels, clamps, nuts, bolts, stay wires including earthing system with following accessories duly connected
with ACSR conductors as per approved drawing & in compliance with requirement of IEC.
(a) 11 kV, 200 A drop out fuses with Synthetic Resin Bonded Paper (SRBP) tubes: 1 Set (01 piece per phase).
(b) 11 kV, 400 A G.O.D. switch complete with earth switch, insulators, operating handle with galvanised pipe, square bar:
(c) 11 kV lightning arrestor with clamps: 3 Nos.
(d) 11 kV Disc Insulators (70KN): 3 Nos.
(e) 11 kV Pin Insulators (5KN): 3 Nos.
(f) 20 mm dia. GI Stay Sets Complete: 2 Set.
Item No.14: Transformer : SITC of outdoor type, three phase, oil immersed, distribution transformer of required KVA &
voltage ratio, copper double wound, vector group - Dyn11, HV delta connected & LV star connected with neutral brought
out connected to provide separate earthing terminals, bushing / cable box on HV side and cable box on LV side suitable for
cables or bus duct as per requirement with standard fittings, conforming to IS: 1180 (Part-1) / 2014 with its latest
amendment including first fill of transformer oil & following accessories. (a) Oil conservator with filling holes with cap and
prismatic oil level gauge. (b) Silica Gel dehydrating breather charged with silica gel (c) Oil drain cum sampling valve with
plug (d) Oil filter valve (e) Lifting Eyes / Hooks / Lugs (f) Two earthing terminal (g) Diagram and rating plate (h) Air release
plug (i) Explosion vent with diaphragm (j) Thermometer pocket (k) Four bi-directional plain roller with base channel with
14 hauling holes (l) Fixed / Separate type radiator banks (m) Off circuit externally operated tapping switch (For rating <
kVA) (n) 100 mm stem type oil temperature indicator (For rating < 500 kVA) (o) Bucholtz relay with shut off valve (For
rating ≥ 500 KVA) (p) 150 mm dial type oil temperature indicator with Alarm / Trip contact (For rating ≥ 500 kVA) (q)
mm dial type winding temperature indicator with Alarm / Tip contact (For rating ≥ 1000 kVA) (r) Marshalling box (For rating
≥ 500 kVA) (s) 150 mm dia. magnetic type oil gauge (For rating ≥ 1600 kVA) (t) Inspection cover & Jacking lugs (For rating ≥
For transformer having oil storage capacity for 2000 liters and higher, nitrogen injection fire protection system (NIFPS) is to
With off circuit tap changer +10% to -10% in steps of 2.5% 1.00 Set. 621411.00
ItemKVA Capacity
No.15: Transformer
Transformer - Eff. Level-2
Foundation : Casting of transformer plinth / foundation including oil soak pit (where required) in
situ reinforced cement concrete in M 20 using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work including
providing of 53 grade cement & Fe 415 grade TMT bars, scaffolding, centering, form work, curing etc. complete.
RCC plinth / foundation for transformer of capacity ≤ 315 KVA.
15 System Voltage (Pri)/Tap Switch: up to 11 kV/OCTC
Transformer Rating (kVA): 250 kVA
Plinth Dimensions (L x W x H): 1250x1250x
Item No.16: Costruction of wire fencing for 11 KV switch yard : Providing and fixing 1.20 Metre high fencing with
Metre long M.S. Angle posts 40mm x 40 mm x6 mm and oil painting 3 coats fixed at 2.5 Mt,C/c. with five Horizontan lines
16 and two diagonals of galvanised steel barbed wire weighting 9.38 Kg. per 100 Metre, strained and fixed to posts with
G.I,staples including fixing the postsin ground with 0.5 M x 0.5.M x 0.5 M. block in C.C1:5:10 etc complete.
17 Item No.17: Providing and Laying best quality gravel bed inside the wire fencing compound as per requirement. 1.60 Cum 2029.00
Item No.18: Providing, Fabricating, Fixing / Installing Mild Steel Wicket Gates of 2 m x 2 m size as per design with
18 operating handle etc. complete
1 No (Approx. 180 Kg of each gate) 1.00 LS 28661.00
Item No.19: LV MCC Panel with DOL / Star Delta / ATS / Micro processor based soft starter: SITC of LV MCC Panel totally
enclosed, dust & bermin proof, indoor type, minimum degree of protection - IP 52 as per IS: 2147, operation on 3-Phase,
Wire, 415V, 50Hz, Neutral effectively grounded, with instrumentation compartments accomodating LED type indicating
lamps, control contactors as per IS: 13947, CT of accuracy class- I as per IS: 2705, relays, meters & control MCBs, air
insulated electrolitic grade Aluminum bus bar for three phase & neutral system with incomming breaker- microprocessor
based Air Circuit Breakers (electrically operated drawout type)/ air break fixed type MCCB with trip free mechanism,
current limiting type as per IS: 8828, Motor Contractor (as per type -2 coordination), Overload Relay with built-in single
phasing prevention feature & auxiliary feeders as per SLD drawings, momentary contact type push buttons, equipment
19 fittings, bus bars, cable boxes, cable gland, incoming & ougoing cable connection for 1100V grade, Aluminium/ Copper
conductor XLPE / PVC insulated & PVC sheathed armoured cable, 10% spare terminals, power wiring using 1100V grade,
FRLS insulated copper conductor wires conforming to IS: 694 & 8130, cable compartments / alleys of minimum 300 mm size,
GI / Al earth bus bar for entire length. MCC shall be fabricated from cold rolled, coled annealed (CRCA) sheet steel &
minimum thickness of various members shall be as follows: Base Frame / Channel / Gland Plate: 3 mm, Load Bearing
Members / Doors: 2 mm and Internal Partitions: 1.6 mm.
Microprocessor based Soft Starter with built-in / External by pass contactor, Semiconductor Fuses, Harmonic Filters, cast
resin type CT, Digital MFM, Analog Ammeter & minimum 10 Channel Temperature Scanner with RS 485 communication port.
75 KW each outer feeder for (2W + 1SB feeder) - WTP (46 MLD) to JN A Zone-1 & Zone 2 3.00 No. 560827.00
Item No.20: Incomer of MCC Panel :
Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed, dust & vermin proof, indoor type,
fabricated from CRCA sheet steel with minimum thickness of 3 mm for base frame / channel / gland plates, 2.0 mm for load
bearing members / doors & 1.6 mm for internal partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for
operation on 3- Phase, 4 Wire, 415 V, 50 Hz, Neutral effectively grounded, with instrumentation compartments accomodating
meters, aux / protective relays, LED type indicating lamps & control MCBs as per IS: 13947, current & voltage transformers as per
IS: 2705, air insulated electrolitic grade Aluminum / Copper bus bar for three phase & neutral system, GI earth bus for entire
length, power / control wiring using 1100 V grade, FRLS insulated copper conductor wires conforming to IS: 694 & 8130, equipment
fittings, horizontally running busbar compartment height of minimum 300 mm, incoming & ougoing cable connections for 1100 V
grade, Aluminium / Copper conductor XLPE / PVC insulated & PVC sheathed armoured cable. LVDB shall have required incomming
20 / bus coupler / outgoing modules of following type & ratings.
-Above 250 A, upto & including 400 A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS / IEC 60947-2 with trip free mechanism,
current limiting type with Thermal-Magnetic / Microprocessor release (O / C, S / C & E / F) with adjustable settings & having
minimum 2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB
module, when used as Incommer / Bus Coupler, shall have enclosure dimensions- 1800(H) x 600(W) x 600 (D) & following technical
4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics =100% of Icu), TM release
Item No.21: SITC of Local Control Station with pendant type Open_Stop_Close pushbutton set and with Open, Close, Trip &
Local / Remote Indicating Lamps complete with Enclouser, necessary mounting/ fixing arrangement on wall / pipe support
etc. to be installed near motors for remote operation, etc. as per IS and specifications (including structural steel) - (For
nos. 75 kW Pump) 3.00 Nos. 6924.00
Item No.22: LV APFC PANEL: Supply, installaton, testing & commissioning LV APFC panel consisting of required capacitor
banks for continuous duty to improve P.F. 0.85 to 0.99 in required steps enclosed in dust & vermin proof compartment,
indoor type, fabricated from CRCA sheet steel with minimum thickness of 3 mm for base frame / channel / gland plates,
2.0 mm for load bearing members / doors & 1.6 mm for internal partitions, minimum degree of protection - IP 42, busbar
chamber, required size of Al bus bar / terminals, minimum 10 stage APFC relay, metering, indicating lamps, push buttons
complete as per IS: 16636-2017 with latest ammendment & detailed technical specification and data sheet as under.
Up to 50 KVAR capacity: APFC panel consisting following items.
22 a) 125 A, 50 kA for 1sec. TP, TM based MCCB with spreader terminals & rotary handle b) 0-125 A range analogue ammeter
of 96 x 96 mm size with selector switch c) 3 nos. 125 / 5A, 10 VA CL-1.0 cast resin type current transformer d) Suitable
rating MCCB / MCB &Contactors for each capacitor bank e) Suitable rating APP type capacitor banks (vacuum impregnated
with non-PCB / non toxic oil, internally delta connected with built in internal fuses complete with discharge resistances &
terminal cover) of approoved make in required steps with well suited detuned reactor is placed in series with each
capacitor step. (e.g. 50 KVAR capacity will be provided in steps of 2 nos x 5 KVAR, 2 nos x 7.5KVAR & 2 nos x12.5 KVAR). f)
Enclosure dimensions: 1600 (H) x 1150 (W) x 600 (D) 2.00 No 138383.00
Item No.23: 11kV(Earthed /Uneartheda) Grade Cable- Aluminium Conductor: Supply, laying, testing & commissioning 11 /
11 kV (UE) grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip / round wire armoured,
extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable
23 trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS: 7098 (Part-
2) & IEC: 60502(Part-2), of following sizes:
3 Core 240 sq mm - For 11 KV DP structure to Trasformer 50.00 m 1261.00
Item No.24: Cable Terminations / Jointing Kits for 11 kV (UE) grade XLPE Cable: Providing & fitting heat shrink cable
termination / jointing kits for 11 kV (UE) grade XLPE insulated cable including necessary earth connectivity connection,
24 material & consummables making the termination/ joint complete ensuring the joint resistance is within the permissble
limit as per IS, of following types & sizes:
Outdoor terimination kit suitable for: 240 to 400 sq mm 3 core 2.00 Each 11487.00
Item No.25: 1.1k Grade cable-Aluminium/Copper Conductor:
Supply, laying , testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat
strip/ round wire armoured, extruded PVC type ST2 sheathed, heavy duty (to be lad on wall surface with necessary
25 clamps/in existing cable trench / cable trays/ conduit/ pipe sleeve at road crossing or floor as per site requirement)
conforming to IS: 7098 (part-1) & IEC: 60502(part-1):
2 Run 3.5 Core 300 sq mm - For Transformer 70.00 m 954.00
25a 1 Run 3.5 Core 50 sq mm - For APFCR Panel 50.00 m 211.00
25b 1 Run 3.5 Core 240 sq mm - Supply Side 50.00 m 784.00
25c 1 Run 3 Core 120 sq mm - Motor Side 45.00 m 355.00
25d 1 Run 4 Core 6 sq mm - For Crane & Misc. 50.00 m 78.00
25e 1 Run 4 Core 4 sq mm - For LDB 25.00 m 70.00
25f 1 Run 4 Core 4 sq mm - For PDB 25.00 m 70.00
Item No.26: Cable Glands: Providing & fitting heavy duty brass cable glands (nickel-plated) with washers & rubber ring
26 conforming to IS, suitable for 3, 3½ & 4 core cables of following type & sizes: Double Compression Brass Cable Glands:
3.5 Core 300 sq mm
26c 3 Core 120 sq mm 2.00 No. 392.00
26d 4 Core 6 sq mm 2.00 No. 107.00
26e 4 Core 4 sq mm 2.00 No. 107.00
26f 4 Core 4 sq mm 2.00 No. 107.00
Item No.27: Cable Terminals (Lugs): Providing and fitting crimping type cable termination (Lugs) conforiming to IS of
27 following types and sizes: Aluminium Tubular Terminals (Long Barrel)
Item No.28: Earthing: Supplying & erecting Funnel type earthing having earth plate of following size burrid in specifically
prepared earth pit 3 m below groung with 40 kg charcol & solt with alternate layers of charcol & solt , 20 mm dia GI pipe
wuth funnel with a wire mesh for watering & brick masonary block CI cover complete as per para 7.3 of IS 3043 with
28 necessary length of double GI/copper earth wirw No.6 SWG bolted with lug to the plate & covered in 12 mm dia GI pipe
mt. long complete connected to the nearest switch gear with ends socket as per direction & duly tested by earth tester
conforming to IS (As per Drawing) with following specifications.
With 45 X 45 X 0.35 cms CI earth plate 2549.78
With 60 X 60 X 0.315 cms Copper earth plate - For Transformer Body, Neutral & 11 KV DP Structure 4.00 Each 7803.78
Item No.29: Cable Tray & Accessories: Supply & laying GI ladder type cable trays with side channels of size - 75 x 15 x
mm / 100 x 15 x 15 mm & rungs of size - 35 x15 x 15 mm spaced at 250 mm apart, fabricated from 2 mm thick sheet steel
in standard length of 2.5 meter, duly hot dipped galvanized after fabrication as per IS 2629-1989/ IS 4759-1984 including
29 accessories such as coupler plates/ fish plates, bends, tees, reducers, elbows, covers and electro-galvanized hardware etc,
erected on existing support as per specification and instruction of Engineer-in-charge.
Item No.30: Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 SWG.
-for earthing of Transformer, LT Pannel board, Motors, etc. using necessary clamps. 330.00 Kg. 77.17
31 Item No.31: Supplying rubber matting of following thickness as per IS:15652/IEC 61111. - 4 mm Thickness. 9.00 Sq.m. 1017.00
Item No.32: Providing and erecting metallic vitrified danger notice board as per language suggested by engineer incharge
for MEDIUM VOLTAGE installation to be erected as per IS-2551. 2.00 No. 69.13
Item No.33: Providing and fixing printed instruction chart both in English and Gujarati and duly framed with front glasses,
for treatment of person suffering from Electric shock with minimum 50" diagonally size. 2.00 No 129.06
Item No.34: Supplying stand first AID box with antiseptic cream, medicine for use on wounds due burn, crepe bandage,
34 gauge bandage, medicated ready to use bandage (Band-aid adhesive tape for medicinal user, Scissors, anti-septic solution
(Savlon or similar) etc. (All above contents shall be of standard makes) 1.00 No 297.00
Item No.35: Supplying FIRE bucket round bottom of 9 litres capacity made out of 24 gauge G.I. sheet with extra handle at
35 bottom duly painted white in side and Red out side with FIRE mark, filled with dry-sand and kept on existing stand provided
or hung on wall hook. 4.00 No 212.00
Item No.36: Supplying and erecting floor mounting stand for keeping four nos. of FIRE buckets comprising 1500 mm in
36 length, 900 mm height frame made out of 30 mm X 30 mm X 4 mm angle iron with cross supports for legs, welded with
hooks and duly painted with one coat of red lead an dtwo coats of approved enamelled silver paint. 1.00 No 933.43
37 Item No.37: Providing pair of rubber hand gloves suitable for working on 11 KV/22 KV supply. 1.00 No 212.00
Item No.38: CCTV Camera Syatem
Supply of high quality images in low light condition IP based PTZ Dome Camera with smart auto tracking ,Optical Zoom,
38 digital zoom, HD CMOS, 120db WDR, camera shall be with 200 Mt IR, seven alarm inputs, 2 outputs, Smart tracking modes:
Manual/ Panorama/ Intrusion trigger/ Line crossing trigger/ Region entrance trigger/ Region rectified with Installation of
necessary accessories with High End Professional Display for 24x7 Operation - 400/500 nits Brightness 110170.00
Item No.39: Ultrasonic type level transmitter with remote display:
Design, Supply, Installation, Testing and Commissioning of Non Contact Ultrasonic Type Level Transmitter with Remote
39 Sensor: The sensor should be non contact type, field mounting type, housing shall have minimum IP65 protection, PP/ PVC
Sensor MOC, with sensor to transmitter cable. Remote Indicator cum Transmitter: Microprocessor based indicator with LED
/ LCD digital display,panel/ wall mounting type, power supply shall be 110-240 Vac or 15 to 36 Vdc, 50 Hz ± 10 %.
Accesories: Mounting bracket, nut, bolts etc as per system requirement and Hook up diagram of the Instruments. Size: 0 to 59436.00
Item No.40: Supply, installation, testing and commissioning of Pressure Transmitter with Micro-processor based integral
LED/LCD display along with, manifold valve, required fittings, tubing (all valves, fittings, tubings, etc. shall be in SS
only) all accessories, hardware, etc. complete in all respects as per specifications and having following measurement
ranges: 2.00 Nos. 29147.00
Item No.41: or o to
Float/ 20 Kg/cm2
Type MainSwitch
Design, Supply, Installation, Testing and Commissioning of Top mounted
Displacer Type level switches with 2 nos SPDT contacts of Micro switch rated 5 A, potential free power supply, Material of
wetted parts shall be SS 316 and the material of accessories shall be SS. IP 65 or equivalent degree of protection for
41 enclosure, suitable for sump, ESR, tank, vessels and underground reservoirs. The top mounted level switches shall be
supplied with still tubes to suit the requirement. . Accessories like name plate, mating flange, gaskets, fasteners, bolts &
nuts, etc. shall be supplied with the Level Switch. Range: 0 to 5 Meter 1.00 No. 12802.00
Item No.42: PLC SCADA SYSTEM
Supply, Installation, Testing & Commissioning of PLC Based Instrument control Panel with Local SCADA system comprising
of min. 21” PC, CPU: i7, 16 GB RAM, 1 TB SSD and monitor to display all the valves in the network and their positions with
colour coding.console with A4 size laser jet printer for report / alarm printing, SCADA run time display software, 4G / 5G
GSM modem, provision of future connectivity at VpMC office SCADA, creation of software to poll between the all Namdha
& Chandor headwork locations and valve, flow meter loactions to SCADA Server, get exact position details, send command
for changing position, received command for position achieved and shutoff etc. Instrument Control Panel (PLC Enclosure /
Panel ) with necessary PLC based logic and wiring , Min 1 nos. flow indicator/totalizer, Min. 1 no. process Indicator, Min
42 no. analog signal multiplier, Min. 1 kVA UPS (with 30 min backup alongwith filter for harmonic, suitable rating SMF batteries
alongwith battery charger, cabling between UPS and battery and all other accessories as per standard), etc. complete in
all respects and as per specs IO list shall include - power supply availability, motor healthy, starter operating, position of
the valve etc. A network switch is required at each of the all all Namdha & Chandor headwork locations and valve, flow
meter loactions. This will ensure that the signal communcation from the remote SCADA System can be done using wireless
communication between central SCADA/PLC to field RTU having gateway with SIM card. Enclosure shall be IP 54 or better
and shall be placed at central location proposed by Department. The PC shall also have back up software for PLC. All
licenced software to be provided. All work shall be carrierd out complete in all respects and as per tender specifications. 1.00 No. 550000.00
PLC/RTU Panel for Field Location
Supply, Installtion, Testing & Commissioning of PLC/RTU panel including PLC, Gateway with SIM Card for remote operation
and monitoring of Flow, Pressure and Valve parameters. Minimum 8DI, 4 DO, 1RS485 communication shall be considered.
42a Real time communication with central SCADA shall be consiered for operation and monitoring from central SCADA.
Panel Shall be IP65 with Local indication and push button for Local operations of valve. UPS with battery backup of
minutes shall be provided in the panel. 20 meter Power Cable from 415 supply nearby shall be considered upto PLC/RTU
Item No.43: INSTRUMENT CABLE & ACCESSORIES
Supply, Laying, Installation, Connection, Termination, Testing & Commissioning of Instrument Cables, along with cable
glands, lugs, cable trays, required junction boxes, fittings and accessores as per specs.
The unit rate shall include
a. Supply, loading & unloading of the cable at site from store.
43 B. Shifitng of cable from site store to place of installation.
c. Fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely.
d. Excavation, back filling and levelling of ground alongwith laying of fine sand, protection bricks and other necessary civil
material for laying cables outside the building.
e. Testing and submission of sketches & reports of all the cables laid.
POWER CABLE- 3C x 4 sq.mm.
43a CONTROL CABLE- 8C x 1.5sq.mm. 30.00 Mtr. 145.00
43b SIGNAL CABLE- 1P x 1.5sq.mm. 30.00 Mtr. 127.00
Item No.44: CABLE END TERMINATION AND CONNECTION
'Supply, fixing, connection, testing and commissioning of double compression brass cable glands and crimping type
Bimetalic lugs / sockets with necessary tools and equipments as specified in specifications and IS complete in all respects.
44 The glands and lugs / sockets shall be suitable for cable size and type mentioned above. The job also includes earthing the
glands and armour of the cable with common earth bar or flexible copper mesh as applicable.
Power Cable -3C x 4 sq.mm. 20.00 Nos. 145.00
44a Control Cable -8C x 1.5 sq.mm. 20.00 Nos. 135.00
44b Signal Cable - 1P x 1.5 sq.mm. 20.00 Nos. 115.00
Item No.45: Instrument Cable Tray: Providing and fixing approved make Perforated C type cable tray. Made from sheet
steel. The cable tray should be single or double bended as per required and as per IS 2062/1079 and shall be coated with
45 hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware like
nut - bolt and washers etc. erection with necessary support(included) as per Specification and as per instruction of
engineer in charge. 50.00 Rmt. 302.30
50 X 1.6 mm Thick
Providing and casting in situ C.C. in grade M-20 (proportions as per mix design or as per table9 of IS456 2000 in
masses by weigh batching ) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work, including scaffolding
46 centering, formwork, needle vibrated consolidation, curing complete up to 6 meter depth or height (excluding cost of
reinforcement and neat finishing) with centering and shuttering/deshuttering etc. complete for structure other than water
retaining (Below G.L) 5.00 Cum 7795.85
Item No.47: Supplying cutting, bending, binding and placing in position steel as per plan and design and as per ISS
including cost of steel and binding wire for reservoirs/structures only including lift up to 6 meter height or depth below 250.00 Kg 84.19
G.L. for all diameters Total for Schedule-B3(Rs.) =
SUMMARY (SCHEDULE-B)
NAMDHA WATER SUPPLY PROJECT (PHASE-2)
NAMDHA WATER SUPPLY SCHEME: WORKING SURVEY, SOIL INVESTIGATION,DESIGN OF WATER SUPPLY SCHEME.WORK INCLUDING DESIGN & CONSTRUCTION, TESTING &
COMMISSIONING OF PROVIDING, SUPPLYING, LOWERING, LAYING AND JOINTING DI PIPELINE FOR RISING MAIN & GRAVITY MAIN, PROVIDING, SUPPLING, ERECTING &
TESTING OF PUMPING MACHINERIES, CONSTRUCTION OF HOUSE CONNECTION & RCC ROAD REINSTATEMENT & SITC WORK OF INSTRUMENTATION WORK & SCADA
SYSTEM AT GRAVITY DISTRIBUTION NETWORK LOCATION ETC. FOR NAMDHA WATER SUPPLY SCHEME (PHASE-2), WORK INCLUDING 5 YEARS OF OPERATION &
MAINTENANCE FOR VAPI MUNICIPAL CORPORATION,DISTRICT: VALSAD.”
SCHEDULE - B4: CONSTRUCTION OF HOUSEHOLD CONNECTIVITY(2013 Nos.)
ITEM DESCRIPTION QTY. UNIT
No. (RS.) AMOUNT (Rs.)
Item No.1: Providing and supplying in true line and level 15mm dia. U.P.V.C. Pipe (SCH-40) for cold water including fittings
1 make PRINCE / SUPREME / ASTRAL / FINOLEX or equivalent as approved by Engineer In Charge.
Item No.2: Providing and supplying in standard length ISI mark rigid unplasticized PVC pipe suitable for portable water with
ring fit joint incl cost of ring, as per IS specification no 4985/1988 incl all local and central taxes, transportation, freight
2 charges, octroi, inspection charges, loading, unloading, conveyance to the departmental store and incl cost of jointing material
etc comp - 6kg/cm2
Item No.3: PVC fittings : Purchasing and supplying at store or site of work G.I./P.V.C. Specials as per requirement incl. Railway
freight, loading, unloading, stacking, and carting from store to site. Sales tax, insurance, octroi, GST & all taxes etc. complete.
3 UPVC Couplers 15 mm dia.
3a UPVC Couplers 90 mm dia. 28.00 No. 78.00
3b Bib Tap 15 mm dia. 1985.00 No. 25.00
3c PVC Flange with pail pieces 90 mm dia 28.00 No. 236.00
3d Service Saddle 15 mm dia. (110/90/75/63/50 mm × 15 mm dia.) 1985.00 No. 50.00
3e Nut bolt 112.00 No. 40.00
3f UPVC Tee (Moulded) 1985.00 No. 20.00
3g UPVC Elbow 15 mm dia. 7940.00 No. 6.00
3h UPVC Elbow 90 mm dia. 28.00 No. 216.00
3i UPVC Clamp 1985.00 No. 10.00
Item No.4: Excavation for pipe line trenches for water supply, sewerage line, manhole etc. all with shoring and strutting if
required as per required gradient and line including safety provisions using site rails and stacking excavated stuff including up
4 to all required lead cleaning the site etc. complete for all lifts and strata as specified.
Upton 0 to 1.5 Mt. Depth
In all sorts of soil and soft murrum 714.60 Cu.m 102.35
4a In hard murrum, boulders incl. macadam road. 2721.75 Cu.m 155.25
Item No.5: Lowering, laying, fixing and jointing PVC/UPVC/CPVC pipes and specials of following class and diameter including
cost of conveyance from stores to site of works including cost of labour, material, cement solvent, giving satisfactory hydraulic
testing as per ISI code. Rate is taken for 63 mm and prorated for 15 mm
5a 90 mm Dia 140.00 Rmt 19.55
Item No.6: Refilling the pipeline trenches incl. ramming, watering, consolidating disposal of surplus stuff as directed within a
radius of 3 km. 3416.23 Cu.m 25.30
7 Item No.7: Cutting of Road : C.C 1:2:4 or RCC 146.59 Cu.m 427.80
7a IPS Cutting 89.33 Cu.m 427.80
Item No.8: Providing and casting in situ mass cement concrete in 1:4:8 proportion using granite quartzite trap metal of size
8 mm to 40 mm including consolidation curing etc. complete. 235.91 Cu.m 3901.95
Item No.9: Making hole for Fitting saddle in to Existing pipe (110/90/63/50 mm) or New laying pipe. Lowering, laying and
9 jointing 110/90/63/50 mm × 15 mm dia. Service Saddle including cost of labour, material, with cement solvent, giving
satisfactory hydraulic testing as per ISI code. 1985.00 No. 100.00
Total for Schedule-B4(Rs.)
SUMMARY (SCHEDULE-B)
NAMDHA WATER SUPPLY PROJECT (PHASE-2)
NAMDHA WATER SUPPLY SCHEME: WORKING SURVEY, SOIL INVESTIGATION,DESIGN OF WATER SUPPLY SCHEME.WORK INCLUDING DESIGN & CONSTRUCTION, TESTING
& COMMISSIONING OF PROVIDING, SUPPLYING, LOWERING, LAYING AND JOINTING DI PIPELINE FOR RISING MAIN & GRAVITY MAIN, PROVIDING, SUPPLING, ERECTING &
TESTING OF PUMPING MACHINERIES, CONSTRUCTION OF HOUSE CONNECTION & RCC ROAD REINSTATEMENT & SITC WORK OF INSTRUMENTATION WORK & SCADA
SYSTEM AT GRAVITY DISTRIBUTION NETWORK LOCATION ETC. FOR NAMDHA WATER SUPPLY SCHEME (PHASE-2), WORK INCLUDING 5 YEARS OF OPERATION &
MAINTENANCE FOR VAPI MUNICIPAL CORPORATION,DISTRICT: VALSAD.”
SCHEDULE -B5: SITC WORK OF INSTRUMENTATION WORK & SCADA SYSTEM AT GRAVITY DISTRIBUTION NETWORK LOCATION FOR NAMDHA WATER SUPPLY
SR. TOTAL AMOUNT
SR. TOTAL AMOUNT
ITEM DESCRIPTION QTY. UNIT RATE (RS.)
Item No.1: Supply, Installation, Testing and Commissioning of ISI mark CI D/F Sluice Valve as per IS 14846 PN 1.0 with
Electrically / Manually operated including non-modulating type (ON/OFF operation only), Motorised valve shall be suitable for
underwater operation in case of flooding in the chamber(Min IP68 rated).Type of valve, pressure of water, location and
interface to be provided for correct valve operation. valves can be modulating also, you can use for flow control. Non -
modulating are ON / OFF type only (Open / Close type) of following sizes with Integral Starter, SS 304 seat rings, SS rising
spindle with all hot dipped galvanised hardware's, bolts, nuts & washers, gaskets and handwheel including all taxes, insurance,
transportation, freight charges, Inspection Charges, loading unloading, conveyance to pump house, stacking, security etc.
complete as per IS and Specification.
Lowering, laying and jointing C.I./D/F Reflux valves, Butterfly valves, Sluice valves and Air valves including cost of all labour,
jointing material, including nut bolts and giving satisfactory hydraulic testing, etc. complete.
200 mm NB (Electrically Operated)
1a 250 mm NB (Electrically Operated) 2.00 No. 472212.90
1b 300 mm NB (Electrically Operated) 1.00 No. 478348.15
1c 350 mm NB (Electrically Operated) 2.00 No. 491601.30
1d 400 mm NB (Electrically Operated) 1.00 No. 509248.65
1e 450 mm NB (Electrically Operated) 1.00 No. 522710.00
1f 500 mm NB (Electrically Operated) 1.00 No. 570394.75
Item No.2: Electromagnetic Flow Meter- Regular Power Operated- PN 10 :
Supply, installation, testing and commissioning of remote type Full Bore Electromagnetic flow meter comprising of IP-68
Sensor SS304/ Metallic Alloy Flow Tube, SS316/ SS 316 L/ Hastelloy Sensor, SS316/ Hastelloy Grounding Ring/ Inbuilt
Grounding Electrode, Neoprene/ Polyurethane/ Hard Rubber/ Rilsan lining, SS304/ Die Cast Aluminium/ Carbon steel with
Anticorrosive Paint Coil Housing with Junction Box, CS flanges.
Flow Transmitter: Microprocessor based, Modular design, 2 line LCD for indication of actual flow rate, forward, reverse, sum
totaliser display, ±0.5% accuracy at 0.3 to 4 m/sec velocity, 4 to 20 mA with HART/Modbus output, one scalable pulse, one
2 status output, IP 67 protection, Die cast aluminium/ polycarbonate/ SS316 with Anticorrosive Paint/ PU finish with glass
window enclosure, Inbuilt EEPROM and Data Logger, 20 meters cable length for sensor to transmitter communication etc.
along with wall mounted/ stand mounted cabinet.
Panel mounted flow indicator cum Totalizer along with all mounting accessories, hardware, etc. complete in all respect and as
per specs and shall have following size measurement range. The scope also includes necessary connection with header pipe.
200 mm Nominal Bore
2a 250 mm Nominal Bore 2.00 No. 117201.00
2b 300 mm Nominal Bore 1.00 No. 134422.00
2c 350 mm Nominal Bore 2.00 No. 185900.00
2d 400 mm Nominal Bore 1.00 No. 211120.00
2e 450 mm Nominal Bore 1.00 No. 226181.00
2f 500 mm Nominal Bore 1.00 No. 263124.00
SR. TOTAL AMOUNT
SR. TOTAL AMOUNT
ITEM DESCRIPTION QTY. UNIT RATE (RS.)
Item No.3: Design , Supply, Installation, Testing, Commissioning of Bourdon Type Pressure Guage, +1& accuracy, Direct
bottom 1/2" NPT (M) process connection, IP 67, Glycerine filled, SS304 case with Bayonet Type Bezel, SS316 L Bourdon Tube,
3 SS316 movement material, Aluminium dial with black graduation on white background, Micro Zero adjustable pointer,
neoprene gasket, Blow out disc, shatter proof glass, SS tag plate as per IS 3624. - 0 to 10 Kg/cm2.
100 mm Dial Size 12.00 No. 1686.00
Item No.4: Supply, installation, testing and commissioning of Pressure Transmitter with Micro-processor based integral LED/
LCD display along with, manifold valve, required fittings, tubing (all valves, fittings, tubing's, etc. shall be in SS 316 only) all
4 accessories, hardware, etc. complete in all respects as per specifications and having following measurement ranges:
Range : 0 to 10 or o to 20 Kg/cm2
Item No.5: Construction of RCC Valve Chamber including dewatering required. Damage to existing pipe shall be made good as
per original. Slope of chamber shall be such that excess water shall be drained and taken to a local drain. Space for
5 maintenance shall be provided. (Chamber can be bigger. ensure rung ladders or similar is provided for person to access the
Item No.6: Providing and casting in situ C.C. in grade M-15 (approx. corresp. to prop. 1:2:4) (proportions as per mix design or
as per Table 9 of IS456 2000 in masses by weigh batching) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC
work, including scaffolding centring, form work, needle vibrated consolidation, curing comp. up to 6 meter depth or height
6 (excluding cost of reinforcement and neat finishing) with centring and shuttering/DE shuttering etc. comp. for structure for
other than water retaining. Footing for column or foundation (with form work)
Panel Foundation for Field PLC/RTU Panel
Size : 1.8 m L X 0.8 m W X 0.5 m H (12 Locations)
Item No.7: PLC/RTU Panel for Field Location
Supply, Installation, Testing & Commissioning of PLC/RTU panel including PLC, Gateway with SIM Card for remote operation
and monitoring of Flow, Pressure and Valve parameters.
Minimum 8DI, 4 DO, 2AI, 1RS485 communication shall be considered.
7 Real time communication with central SCADA shall be considered for operation and monitoring from central SCADA.
Panel Shall be IP65 with Local indication and push button for Local operations of valve. UPS with battery backup of 30 minutes
shall be provided in the panel.
20 meter Power Cable from 415 supply nearby shall be considered up to PLC/RTU panel.
Item No.8: POWER AND INSTRUMENT CABLE & ACCESSORIES
Supply, Laying, Installation, Connection, Termination, Testing & Commissioning of Instrument Cables, along with cable glands,
lugs, cable trays, required junction boxes, fittings and accessors as per specs.
The unit rate shall include
a. Supply, loading & unloading of the cable at site from store.
8 b. Shifting of cable from site store to place of installation.
c. Fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely.
d. Excavation, back filling and levelling of ground along with laying of fine sand, protection bricks and other necessary civil
material for laying cables outside the building.
e. Testing and submission of sketches & reports of all the cables laid.
Power Cable -3C x 4 sq.mm.
8a Control Cable -8C x 1.5 sq.mm. 600.00 m 145.00
8b Signal Cable - 1P x 1.5 sq.mm. 720.00 m 127.00
SR. TOTAL AMOUNT
SR. TOTAL AMOUNT
ITEM DESCRIPTION QTY. UNIT RATE (RS.)
Item No.9: CABLE END TERMINATION AND CONNECTION
'Supply, fixing, connection, testing and commissioning of double compression brass cable glands and crimping type Bimetallic
lugs / sockets with necessary tools and equipment's as specified in specifications and IS complete in all respects. The glands
9 and lugs / sockets shall be suitable for cable size and type mentioned above. The job also includes earthing the glands and
armour of the cable with common earth bar or flexible copper mesh as applicable.
Power Cable -3C x 4 sq.mm. 120.00 No. 145.00
9a Control Cable -8C x 1.5 sq.mm. 120.00 No. 135.00
9b Signal Cable - 1P x 1.5 sq.mm. 180.00 No. 115.00
Item No.10: Instrument Cable Tray
Providing and fixing approved make Perforated C type cable tray. Made from sheet steel. The cable tray should be single or
double bended as per required and as per IS 2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759. with
max 17.5% perforation with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erection with
necessary support (included) as per Specification and as per instruction of engineer in charge.
50 X 50 X 1.6 mm Thick
Item No.11: Earthing: Supplying & erecting Funnel type earthing having earth plate of following size burred in specifically
prepared earth pit 3 m below ground with 40 kg charcoal & slot with alternate layers of charcoal & slot , 20 mm dia GI pipe
with funnel with a wire mesh for watering & brick masonry block CI cover complete as per para 7.3 of IS 3043 with necessary
11 length of double GI/copper earth wire No.6 SWG bolted with lug to the plate & covered in 12 mm dia GI pipe 2.5 mt. long
complete connected to the nearest switch gear with ends socket as per direction & duly tested by earth tester conforming to
IS (As per Drawing) with following specifications.
With 30 x 30 x 0.35 cms: C.I. earth plate.
Item No.12: Supply, erection, testing & commissioning of Cast Alu. Junction Boxes along with all required hardware in GI,
12 supporting structure, etc. complete in all respects as per following:
10 Terminal Junction box (suitable for cable) 12.00 No. 3500.00
12a 25 Terminal Junction box (suitable for cable) 12.00 No. 5000.00
Item No.13: Cable Trench, Laying & Installation of Cable; Making cable trench in soft soil of suitable width of 90cms deep for
laying cable all over the run and back filling the same and making the surface as normal ground as per IS & Specification.
13 (For laying cable in ground)
Item No.14: Cable Covering in Trench: Cable Covering with second class bricks or cement tiles laid cover the cable crosswise
& also on both side with covering of 7.5cms. Layer of sand above & below cable (16 bricks per meter.) as per IS &
14 Specification.
(For cable in ground) 120.00 m 139.37
Item No.15: Supplying rubber matting of following thicknesses per IS:15652/IEC
4 mm Thickness. 24.00 Sq.m 1017.00
Item No.16: Providing and erecting metallic vitrified danger notice board as per language suggested by engineer in charge for
MEDIUM VOLTAGE installation to be erected as per IS-2551. 12.00 No. 69.13
Item No.17: Providing and fixing printed instruction chart both in English and Gujarati and duly framed with front glasses, for
treatment of person suffering from Electric shock with minimum 50" diagonally size. 12.00 No. 129.06
Item No.18: Supplying stand first AID box with antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge
18 bandage, medicated ready to use bandage (Band-aid adhesive tape for medicinal user, Scissors, anti-septic solution (Savlon or
similar) etc. (All above contents shall be of standard makes) 12.00 No. 297.00
Item No.19: Supplying & erecting D.C.P. type fire extinguisher for following capacity cartridge type with gun metal cap
19 gram CO2 gas cartridge, powder and brackets confirming to IS 2171 1985 and complete erected with necessary clamps made
from 50 x 6 mm M S Flat with nuts and bolts grouted in wall complete. [A] For 5 Kg Capacity 12.00 No. 1696.26
Total for Schedule-B5(Rs.) =
SUMMARY (SCHEDULE-B)NAMDHA WATER SUPPLY PROJECT (PHASE-2)
NAMDHA WATER SUPPLY SCHEME: WORKING SURVEY, SOIL INVESTIGATION,DESIGN OF WATER SUPPLY SCHEME.WORK INCLUDING DESIGN & CONSTRUCTION, TESTING &
COMMISSIONING OF PROVIDING, SUPPLYING, LOWERING, LAYING AND JOINTING DI PIPELINE FOR RISING MAIN & GRAVITY MAIN, PROVIDING, SUPPLING, ERECTING &
TESTING OF PUMPING MACHINERIES, CONSTRUCTION OF HOUSE CONNECTION & RCC ROAD REINSTATEMENT & SITC WORK OF INSTRUMENTATION WORK & SCADA
SYSTEM AT GRAVITY DISTRIBUTION NETWORK LOCATION ETC. FOR NAMDHA WATER SUPPLY SCHEME (PHASE-2), WORK INCLUDING 5 YEARS OF OPERATION &
MAINTENANCE FOR VAPI MUNICIPAL CORPORATION,DISTRICT: VALSAD.”
SCHEDULE-C1: OPERATION & MAINTANANCE (FOR 5 YEARS)
Description Qty Unit Rate Amount
ITEM NO.1: Comprehensive Operation and Maintenance of Rising Main and Gravity Main distribution
pipeline network. This system includes House Connectivity, SITC work of Instrumentation work & Scada
System at Gravity Distribution Network to ensure reliable water distribution and other allied works. This
also involves the integration of essential mechanical, instrumentation, and electrical components,
alongside headwork to enhance water management efficiency including
1) Breakdown Maintenance or Emergency Maintenance,
2) Day to day Maintenance
1 3) Preventive or Periodic Maintenance, 1 Per Year 28,71,486.30
4) Major Maintenance (or Special repairs and replacement including Training to O & M staff of Municipality.
The rate shall also include all consumables and deployment of Manpower but excluding electric power (The
electrical bill for power shall be paid by the municipality) . The O & M work shall be carried out as per
detailed specifications in the tender & maintaining the record for the same.
Comprehensive Operation and Maintenance of Rising Main and Gravity Main distribution pipeline network.
This system includes House Connectivity, SITC work of Instrumentation work & Scada System at Gravity
Distribution Network to ensure reliable water distribution and other allied works. This also involves the
integration of essential mechanical, instrumentation, and electrical components, alongside headwork to
enhance water management efficiency including
1) Breakdown Maintenance or Emergency Maintenance,
2) Day to day Maintenance
1a 3) Preventive or Periodic Maintenance, 1 Per Year 34,45,783.56
4) Major Maintenance (or Special repairs and replacement including Training to O & M staff of Municipality.
The rate shall also include all consumables and deployment of Manpower but excluding electric power (The
electrical bill for power shall be paid by the municipality) . The O & M work shall be carried out as per
detailed specifications in the tender & maintaining the record for the same.
SCHEDULE-C1: OPERATION & MAINTANANCE (FOR 5 YEARS)
Description Qty Unit Rate Amount
Comprehensive Operation and Maintenance of Rising Main and Gravity Main distribution pipeline network.
This system includes House Connectivity, SITC work of Instrumentation work & Scada System at Gravity
Distribution Network to ensure reliable water distribution and other allied works. This also involves the
integration of essential mechanical, instrumentation, and electrical components, alongside headwork to
enhance water management efficiency including
1) Breakdown Maintenance or Emergency Maintenance,
2) Day to day Maintenance
1b 3) Preventive or Periodic Maintenance, 1 Per Year 38,28,648.40
4) Major Maintenance (or Special repairs and replacement including Training to O & M staff of Municipality.
The rate shall also include all consumables and deployment of Manpower but excluding electric power (The
electrical bill for power shall be paid by the municipality) . The O & M work shall be carried out as per
detailed specifications in the tender & maintaining the record for the same.
Comprehensive Operation and Maintenance of Rising Main and Gravity Main distribution pipeline network.
This system includes House Connectivity, SITC work of Instrumentation work & Scada System at Gravity
Distribution Network to ensure reliable water distribution and other allied works. This also involves the
integration of essential mechanical, instrumentation, and electrical components, alongside headwork to
enhance water management efficiency including
1) Breakdown Maintenance or Emergency Maintenance,
2) Day to day Maintenance
1c 3) Preventive or Periodic Maintenance, 1 Per Year 42,11,513.24
4) Major Maintenance (or Special repairs and replacement including Training to O & M staff of Municipality.
The rate shall also include all consumables and deployment of Manpower but excluding electric power (The
electrical bill for power shall be paid by the municipality) . The O & M work shall be carried out as per
detailed specifications in the tender & maintaining the record for the same.
SCHEDULE-C1: OPERATION & MAINTANANCE (FOR 5 YEARS)
Description Qty Unit Rate Amount
Comprehensive Operation and Maintenance of Rising Main and Gravity Main distribution pipeline network.
This system includes House Connectivity, SITC work of Instrumentation work & Scada System at Gravity
Distribution Network to ensure reliable water distribution and other allied works. This also involves the
integration of essential mechanical, instrumentation, and electrical components, alongside headwork to
enhance water management efficiency including
1) Breakdown Maintenance or Emergency Maintenance,
2) Day to day Maintenance
1d 3) Preventive or Periodic Maintenance, 1 Per Year 47,85,810.50
4) Major Maintenance (or Special repairs and replacement including Training to O & M staff of Municipality.
The rate shall also include all consumables and deployment of Manpower but excluding electric power (The
electrical bill for power shall be paid by the municipality) . The O & M work shall be carried out as per
detailed specifications in the tender & maintaining the record for the same.
Total for Schedule-C1 (Rs.)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
004 Annexure -2 (Schedule B) Namdha WS- Without Ref.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .