CWE, HQ 133 WORKS ENGRS
HQ 133 WORKS ENGRS
REPAIR MAINT OF 33 KV HT LINE AND POWER TRANSFORMER 33 KV STRUCTURE BAY NETWORK VCBS AND ALLIED WORKS REPAIR MAINT OF HT NETWORK INCL TRANSFORMER VCBS AND ALLIED WORKS AND REPAIR REPLACEMENT OF LIGHTING ARRESTER AND EARTHING AT BARAMULLA AND PATAN
2023_MES_615799_2
CWEK-30/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 969 EWS
Class D Category b i AND b ii
7 documents required · 7 mandatory
₹500
GE 969 EWS
₹83,720
HQ 133 WORKS ENGRS
28 Dec 2023
29 Sept 2023
4 Nov 2023
29 Sept 2023
27 Oct 2023
14 Oct 2023
29 Sept 2023 - 9 Oct 2023
9 Oct 2023
Amount
Decarbonising / cleaning complete of HT 11KV 3 phase bus bar & bus bar chamber, all electrical connections complete HT VCBs/OCBs/Bus coupler arrangment after removing the bus bar spout, cleaning with petrol and CRC 226 spray solution and ensure proper de-carbonisation, refixing the same after completion. (Note:- Required spare parts are measured and paid separately) Completed all as specified and directed by Engr-in-Charge.
Calibration and testing of IDMT relays like earth fault, over load relay installed in sub station on HT VCBs/OCBs 11 KV panel and testing through recognised agencies by means of secondary injection method, setting of relay timings and play settings and fixing back the relays in position Completed all as specified and directed by Engr-in-Charge.
S&F Steel tubular swaged poles complete with MS base plate Continuously welded to pole, finial taper plug, bolts, nuts & screws as specified type 410 SP- 55 (11 metres long ) includind two coat of black bituminous paint internally throughout and externally upto embedded portion and including applying two coats of synthetic enamel paint over a coat of red oxide primer with black and white strip of 30 cm each upto 1.5 m height and two coats of aluminium paint over a coat of red oxide primer externally on remaining exposed surface aftereraction in position incl prepration of surface, incl dismantling of existing PCC or steel tubular pole complete all as specified and directed.( earth work ,PCC and copping will be measured and paid for separately under respective item) Completed all as specified and directed by Engr-in-Charge.
S&F Steel tubular swaged poles complete with MS base plate Continuously welded to pole, finial taper plug, bolts, nuts & screws as specified type 410 SP- 31 (09 metres long ) includind two coat of black bituminous paint internally throughout and externally upto embedded portion and including applying two coats of synthetic enamel paint over a coat of red oxide primer with black and white strip of 30 cm each upto 1.5 m height and two coats of aluminium paint over a coat of red oxide primer externally on remaining exposed surface aftereraction in position incl prepration of surface, incl dismantling of existing PCC or steel tubular pole complete all as specified and directed.( earth work ,PCC and copping will be measured and paid for separately under respective item) Completed all as specified and directed by Engr-in-Charge.
S & F Pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut, 150 mm height, 150 mm dia for 33000 volts grade HT over head line and including taking down old Completed all as specified and directed by Engr-in-Charge.
S & F Pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade HT over head line and including taking down old Completed all as specified and directed by Engr-in-Charge.
S & F single Disc type insulator, porcelain, vitreous 145 mm high and 225 mm dia ball and socket type, brown, assembly for tension with tension clamps for conductors, 11000 volts complete all as specified and as directed including taking down old unserviceable one Completed all as specified and directed by Engr-in-Charge.
S & F single Disc type insulator, porcelain, vitreous 145 mm high and 225 mm dia ball and socket type, brown, assembly for tension with tension clamps for conductors, 33000 volts complete all as specified and as directed including taking down old unserviceable one Completed all as specified and directed by Engr-in-Charge.
M&L for shackle type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, 150 mm height, 150 mm dia for 11100 volts grade including dismantling /disconnecting & taking down old broken and unserviceable insulaters of any size & capacity Completed all as specified and directed by Engr-in-Charge.
M&L for Pin type Porcelain, vitreous, white brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mm height, 100 mm dia for 1100 volts grade Completed all as specified and directed by Engr-in-Charge.
Loop type insulator, vitreous porcelain, white, brown or green large size, with overall dimensions 140mm, clearance of hole 25.5mm Completed all as specified and directed by Engr-in-Charge.
M&L for Switch air break, gang operated triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps 11000 volts (12 Insulator) alongwith fuse system Completed all as specified and directed by Engr-in-Charge.
M&L for Switch air break, gang operated triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 400 amps 11000 volts (12 Insulator) alongwith fuse system Completed all as specified and directed by Engr-in-Charge.
M&L for Lighting arresters expulsion type complete with all fittings transmission class, discharge capacity 65KA suitable for 11000volts Completed all as specified and directed by Engr-in-Charge.
M&L for Lighting arresters expulsion type complete with all fittings transmission class, discharge capacity suitable for 33000 volts Completed all as specified and directed by Engr-in-Charge.
M & L for test point terminal block made of gunmetal or phosphorous bronze of size 75x75x25mm drilled & screwed incl 3 Nos 8mm dia 25mm long hex head screws Completed all as specified and directed by Engr-in-Charge.
Supply and Fixing of Galvanised iron strip 32 x 6mm buried in ground Completed all as specified and directed by Engr-in-Charge.
Supply and Fixing of Air termination, single pointed aluminium rod 12mm dia and 300mm long Completed all as specified and directed by Engr-in-Charge.
Material and labour of danger notice plate of 1.6 mm thick as per IS : 2551 of 1982 mild steel sheets vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and inclusive fixed with MS flat clamps 25x3mm 2Nos , bolts , and nuts for HT 11KV 25x20cm including taking down of old one Completed all as specified and directed by Engr-in-Charge.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm Completed all as specified and directed by Engr-in-Charge.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm Completed all as specified and directed by Engr-in-Charge.
M&L for Cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm Completed all as specified and directed by Engr-in-Charge.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm Completed all as specified and directed by Engr-in-Charge.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 Sqmm Completed all as specified and directed by Engr-in-Charge.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm Completed all as specified and directed by Engr-in-Charge.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm Completed all as specified and directed by Engr-in-Charge.
M&L for stay assembly complete with accessories as shown in electrical plate No 1 ( Loop type insulator, stay clamps excavation and concrete measured separately) 20mm dia including dismentling old and unsv stay assy complete comprising of stay clamp, stay wire, stay insulator, stay grip, thimble, bow, stay rod and stay plate etc including breaking of cement conccrete including taking down old one Completed all as specified and directed by Engr-in-Charge.
S & F in repair cross arms bracing supports, clamps and back plate fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat of red oxide zinc chrome, one under coat and one finishing coat of aluminum paint Completed all as specified and directed by Engr-in-Charge.
M & L for cement concrete for foundation fillings and mass conctere type D2 1:4:8 using 40 mm graded aggregate complete Completed all as specified and directed by Engr-in-Charge.
M & for cement concrete for coping of poles using B1 1:2:4, 20 mm graded aggregate, smooth finishing without using extra cement Completed all as specified and directed by Engr-in-Charge.
M & for cement concrete for foundation fillings and mass conctere type C2 1:3:6 using 40 mm graded aggregate Completed all as specified and directed by Engr-in-Charge.
Material and labour for earthing complete with galvanised steel earth plate electrode 60cmX60cmX6.0mm thick, buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5mtr below normal ground level connected to GI earth strip of size 32x6 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron complete earth pit of PCC M-10(Nominal mix) using 20mm graded stone aggregate, 50mm thick earth pit cover of RCC M-15 (Nominal mix) using 20mm graded stone aggregate with MS TMT reinforcement bar of 8mm dia @ 150mm centre to centre both ways, MS handle 10mm dia made to shape, GI funnel, wire mesh and 20mm bore GI water pipe light grade and 40mm bore light grade GI pipe for protection of earth strip from plate to main switch board, common salt, charcoal dust including testing on completion complete all as specified and as directed all as shown in electrical plate No. 3 including testing on completion and making good the disturbed surfaces of wall floors etc without claiming extra cost all as directed by Engr-in-Charge. (Note: GI strip & GI pipe beyond 7.5Mtr length from earth electrode shall be measured and paid separately) Completed all as specified and directed by Engr-in-Charge.
M&L PVC spacer suitable for 3 wire HT OH line including taking down of old one Completed all as specified and directed by Engr-in-Charge.
M&L PVC spacer suitable for 4 wire LT OH line including taking down of old one Completed all as specified and directed by Engr-in-Charge.
Painting to existing steel tubular LT poles, 9m long including cross arms, channels, angle iron support, bracings, clamps etc. with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including preparation of old painted surfaces by scraping etc complete and writing pole numbers. of 2 inches bold letters with black paint after painting, Completed all as specified and directed by Engr-in-Charge.
Painting to existing steel tubular HT poles, 11m long including cross arms, channels, angle iron support, bracings, clamps etc. with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including preparation of old painted surfaces by scraping etc complete and writing pole numbers. of 2 inches bold letters with black paint after painting, Completed all as specified and directed by Engr-in-Charge.
Supply and laying GI pipe 80 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one Completed all as specified and directed by Engr-in-Charge.
Supply and laying GI pipe 50 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one Completed all as specified and directed by Engr-in-Charge.
Supply and laying GI pipe 40 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one Completed all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of lugs or thimbles suitable for 10 Sqmm to 70 sqmm aluminum coductor cable suitable 1100 volts LT Cable Completed all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of lugs or thimbles suitable for 95 Sqmm to 400 sqmm aluminum coductor cable suitable 1100 volts LT Cable Completed all as specified and directed by Engr-in-Charge.
Disconnecting HT/LT cable and earthing connections of burnt/defective transformer of capacity 50 KVA to 500 KVA , 11 KV/433 volts 3 phase from pole/floor mounted, taking from site of installation carefully with the help of Crane and transportation of the same to workshop for repairs, draining out the transformer oil, dismantling complete and taking out the core assembly and removing burnt out windings, dehydrating the core assembly, reassembling transformer after repair, replacement of complete gasket set, refilling the oil duly filtered / dehydrated, topping up with new oil, carrying out routine tests, including transportation back to site, testing and commissioning of the repaired transformer at site on full load after making cable and earthing connections Completed all as specified and directed by Engr-in-Charge.
M&L for Hiring, transportation, installation and testing of serviceable transformer of existing capacity on hired basis in place of unserviceable transformer which is under repair and shifting back to workshop on hire basis for 15 days when ordered complete all as specified and directed by engr in charge. Note:- (1) Repairing of transformer shall not exceed beyond 15 days from the date of dismantling from original site, (2) Contractor shall not be allowed to shift hired transformer untill it is replaced by orginal one. (3) Hired transformer will match with the existing transformer with same voltage, vector group, impendence etc. (4) Incase the defective/unservicable transformer is not repaired with in stipulated period of 15 days a penalty of Rs 1000/- per day will be deducted and no extra cost willl be paid to the contractor un less natural calamidity is occured Completed all as specified and directed by Engr-in-Charge.
Material & labour for rewinding of LT side winding with copper strip/wire of suitable size/gauge, fixing the coil in position in core assembly and making connection as per existing pattern including providing insulation, varnish etc complete all as specified and directed by Engr-in-Charge.
Disconnecting HT/LT cable/busbar and Earthing connections complete of transformer capacity up to 63 KVA, 11 KV/433 Volts 3 phase from pole/floor/transformer shed with the help of Crane to carry out complete maint of transformer comprising of the following:- (i) Draining out oil from chamber. (ii) Opening top cover, disconnecting winding connection from bushings and taking out carefully core assembly complete with winding. (iii) Checking compactness of core & tightening the same where required. (iv) Chemical washing of winding to remove dirt,dust & carbon particles (v) Cleaning of oil tank to remove oil sludge followed by painting of inner surface of tank with zinc chromate base paint (vi) Refixing of core & winding assembly and making connection with HT/LT bushing . (vii Replacement of worn out gaskets & nut/bolts. (Note: Overhauling of transformer should be done on existing installation place on same days) Completed all as specified and directed by Engr-in-Charge.
All as per item No.48 above but transformer capacity from 100 KVA to 200 KVA Completed all as specified and directed by Engr-in-Charge.
All as per item No.48 above but suitable for transformer capacity 250 KVA to 400 KVA Completed all as specified and directed by Engr-in-Charge.
Material and Labour for preparing the surfaces of transformer of capacity up to 63 to 100 KVA by rubbing old paint and applying two coats of spray painting with grey deco paint from outside complete all as specified and as directed. Note. Painting of transformer will be carried out for plinth mounted and pole mounted transformer. Necessary tools and plants shall be arranged by the contractor. Shut down schedule for painting of transformer will be submitted in advance to plan shut down in the station. including writing MES / SM No with enamelled paint complete all as specified and as directed for transformer of rating upto 100 KVA (Indoor/outdoor type) Completed all as specified and directed by Engr-in-Charge.
All as per item No. 51 above but 200KVA to 250KVA (Indoor / outdoor type) Completed all as specified and directed by Engr-in-Charge.
All as per item No. 51 above but 250 KVA to 400 KVA (Indoor / outdoor type) Completed all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of silica gel breather assembly with vent pipe complete with fresh blue coloured, for transformer of capacity 50 KVA to 200 KVA Completed all as specified and directed by Engr-in-Charge.
All as per item No.54 above but suitable for transformer capacity 250 KVA to 400 KVA Completed all as specified and directed by Engr-in-Charge.
Dismantling of old Burnt Tap changer and Supply and fixing new tap changing switch as per existing size including making connection to transformer of various capacities/make Completed all as specified and directed by Engr-in-Charge.
Supply and replacing HT/LT side cable box cover plate made out of MS sheet of 16 SWG complete with nuts, bolts, washers suitable for indoor/outdoor type transformer of capacity 63 KVA to 400 KVA Completed all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement HT bush assembly brass complete with brass spindle, nuts, bolts, washers etc with bushing insulators suitable for transformer of capacity 50 KVA to 63 KVA Completed all as specified and directed by Engr-in-Charge.
All as per item No.58 above but transformer capacity from 100 KVA to 400 KVA Completed all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement LT bush assembly brass complete with brass spindle, nuts, bolts, washers etc with bushing insulators suitable for transformer of capacity 50 KVA to 63 KVA Completed all as specified and directed by Engr-in-Charge.
All as per item No.60 above but transformer capacity from 100 KVA to 400 KVA Completed all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement 11KV porcelain bushing insulators for HT side of out door/indoor type transformerCompleted all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement drain plug of suitable size, Completed all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of rubberized cork sheet gasket 6mm thick for top cover and HT/LT bushes complete all as specified and directed for transformer upto 400 KVA capacity including replacement of Nuts & Bolts where required complete all as Specified and directed by Enge-in-Charge.
Supply and replacement of Oil level indicator complete with glass, gasket, Bolt nuts, washer etc suitable for any make and capacity transformer Completed all as specified and directed by Engr-in-Charge.
M&L loose filling with broken trap stone aggregates of size exceeding 7 cms upto 15 cms in substations, around 4 pole/2 pole structures all as specified and directed by Engineer-in-Charge. (The contractor has to stack the graves/stones near the substation as per directed for necessary measurement and instructions ) Completed all as specified and directed by Engr-in-Charge.
Supply and fixing of D.F. Buchholz Relay Completed all as specified and directed by Engr-in-Charge.
M&L for Insulator suitable for 200A Gang Operating Device Insulator Completed all as specified and directed by Engr-in-Charge.
M&L for Male and Female Blade suitable for 200A Gang Operating Device Completed all as specified and directed by Engr-in-Charge.
S&F MCCB 3 Pole, 415 V, fixed type, 63 Amps with breaking capacity 16 KA all as specified and directed by Engr-in-Charge
S&F MCCB 4 Pole, 415 V, fixed type, 100 Amps with breaking capacity 16 KA all as specified and directed by Engr-in-Charge
S&F MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA all as specified and directed by Engr-in-Charge.
S&F MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA all as specified and directed by Engr-in-Charge.
S&F MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA all as specified and directed by Engr-in-Charge.
M&L for XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete all as specified and directed of following sizes :- (a) 3 ½ core 120 Sqmm Completed all as specified and directed by Engr-in-Charge.
(b) 3 ½ core 95 Sqmm Completed all as specified and directed by Engr-in-Charge.
(c) 3 ½ core 70 sqmm Completed all as specified and directed by Engr-in-Charge.
(f) 2 core 16 Sqmm Completed all as specified and directed by Engr-in-Charge.
(g) 2 core 10 Sqmm Completed all as specified and directed by Engr-in-Charge.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm Completed all as specified and directed by Engr-in-Charge.
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level complete all as specified and directed by Engr-in-charge.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed by Engr-in-charge.
Removing surplus exacavated material from excavation not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point complete all as specified and directed by Engr-in-charge.
Supply and filling dry river sand in trenches including spreading for cushioning of LT UG cablec and punning down complete all as speified and directed by Engr-in-charge. Note : Punned down thickness shall be measured and paid Completed all as specified and directed by Engr-in-Charge.
M&L for well burnt as class ‘B’ bricks as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench complete all as speified and directed by Engr-in-charge.
M&L for Hiring, transportation, installation and testing of serviceable transformer of capacity 2 MVA or higher size on hired basis in place of unserviceable power transformer which is under repair and shifting back to workshop on hire basis for 15 days when ordered complete all as specified and directed by Engr in Charge. Note:- (1) Repairing of transformer shall not exceed beyond 15 days from the date of dismantling from original site, (2) Contractor shall not be allowed to shift hired transformer untill it is replaced by orginal one. (3) Hired transformer will match with the existing transformer with same voltage, vector group, impendence etc. (4) Incase the defective/unservicable transformer is not repaired with in stipulated period of 15 days a penalty of Rs 1000/- per day will be deducted and no extra cost willl be paid to the contractor un less natural calamidity is occured Completed all as specified and directed by Engr-in-Charge.
Material & labour for rewinding of 33/11 KV HT side winding with copper strip/wire of suitable size/gauge of 33/11 KV Power Transformer, fixing the coil in position in core assembly and making connection as per existing pattern including providing insulation, varnish etc complete all as specified and directed by Engr-in-Charge.
Disconnecting all electrical connection of the Power transformer and carryout following works (a) Servicing of all mechanical gear wheels and moving parts, latches and releasing parts, over driven stopping and restarting mechanism complete. (b) Cleaning of complete OLTC control chamber and fault finding. (c) Repairing to control wiring,replacement of burnt wires,lugs etc . (d ) Lubricating,greasing of all mechanical parts. (e) Servicing to electrical auxialary contactors and limit switches and HRC fuses complete. from main line after servicing and routine maintenan re-installation at site complete of all as specified and directed by Engr-in-Charge from pole/floor/transformer shed with the help of Crane to carry out complete maint of transformer. (f) Draining out oil from chamber. (g) Opening top cover, disconnecting winding connection from bushings and taking out carefully core assembly complete with winding. (h) Checking compactness of core & tightening the same where required. (j) Chemical washing of winding to remove dirt,dust & carbon particles (k) Cleaning of oil tank to remove oil sludge followed by painting of inner surface of tank with zinc chromate base paint (l) Refixing of core & winding assembly and making connection with HT/LT bushing . (m) Replacement of worn out gaskets & nut/bolts. (n) Replacing all valves (Note: Overhauling of transformer should be done on existing installation place on same days) Completed all as specified and directed by Engr-in-Charge.
S&F IDMT (as per existing capacity and make) relays earth fault, over load on HT VCBs/OCBs 11 KV panel and testing through recognised agencies by means of secondary injection method, setting of relay timings complete all as directed by Engineer-in-Charge.
S&F Numerical realy (as per existing capacity and make) relays shown earth fault, over load on HT VCBs/OCBs 11 KV panel and testing through recognised agencies by means of secondary injection method, setting of relay timings complete all as directed by Engineer-in-Charge.
S&F Master Trip Relay (as per existing capacity and make) suitable for 33 KV Control and Relay Panel (C&R Panel) for 33 KV HT VCBs and testing through recognised agencies setting of relay timings complete all as directed by Engineer-in-Charge.
S&F Battery Bank of capacity 2V x 18 (36 Volt) Dry type 200 AH with wooden shelf complete all as directed by Engineer-in-Charge.
S&F Battery Charger suitable for charge the battery bank of capacity 2V x 18 (36 Volt) Dry type 200 AH complete all as directed by Engineer-in-Charge.
M&L for restringing HT(33KV/11KV)/LT ACSR conductor complete all as directed by Engineer-in-Charge. Note : All the eqpts required for re-stringing ACSR conductor like vehicle, ladder, rope, manpower etc is deemed to be included in quoted rate Completed all as specified and directed by Engr-in-Charge.
Filtration of transformer oil of transformers installed at Baramulla 33/11 KV Substation for outdoor transformers to achieve di-electric strength of 40 KV for 1 minute at 4mm gap as per relevant IS with portable filtration plant, testing of the oil for the di-electric strength before filtration and after filtration complete all as directed by the Engineer-in-Charge.
Supply and topping up only transformer oil for di-electric strength of 40 KV in to the conservator tank/ body tank of the transformers of various sub stations complete all as directed by the Engineer-in-Charge. (Make: Power Oil/ Transol/ Sabitha Chemicals) Completed all as specified and directed by Engr-in-Charge.
S&F Tripping Coil (Opening/Closing) coil 30V suitable for HT VCB/OCBs 33/11 KV VCB panel and setting of relay timings complete all as directed by Engineer-in-Charge.
S&F Bridge rectifier for AC/DC Motor suitable for HT VCB/OCBs 11 KV panel complete all as directed by Engineer-in-Charge.
S&F Fuse Cartidge suitable for HT VCB/OCBs 11 KV panel complete all as directed by Engineer-in-Charge.
M&L for complete re-wiring with suitable size of copper conductor as per existing size and make for DC supply suitable for HT VCB/OCBs 11 KV panel complete all as directed by Engineer-in-Charge.
S&F LED Indication Lamp suitable size DC/AC supply suitable for HT VCB/OCBs 11 KV panel complete all as directed by Engineer-in-Charge.
S&F PVC Insulated felxible Copper Conductor 25 Sqmm Single Core multistranded all as specified and directed
M&L Trimming of tree branches upto 20 cm girth from the tree near the LT/HT (33 KV/11 KV/1100V) over head line to provide horizantal clearance of 30 cms and verticle clearance of 60 cms and depositing the trimmed branches where dirrected Completed all as specified and directed by Engr-in-Charge. Note : All the eqpts required for trimming like vehicle, ladder, axe, manpower etc is deemed to be included in quoted rate
S&F Electrical rubber Insulating sheet of size 5mm thick, size 1 Mtr x 4 Mtr for used in Electrical Power House 33 KV all as specified and directed by Engr-in-Charge
M/S KULBIR SINGH SODHI AND CO
M/S Khan Hussain & Co.
ALCO ENGINEERSPVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .