EE-I,WKED,PWDte.
New Secretariat Building, C Block, 4th floor 1, K.S Roy Road, Kolkata-700001
Renovation and remodelling of the existing Sishu Kishor Academy premises on the 2nd fl of Rabindra Sadan, Kolkata for accommodating the new office of the Director of Film under the I and CA Deptt., Govt. of WBFire Detection and Alarm System
2026_WBPWD_5080576_1
WBPWD/EE-WKED/NIQ-102/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Rabindra Sadan
Please refer Tender documents.
6 documents required · 6 mandatory
₹12,831
14 Oct 2026
14 Oct 2026
2 Nov 2026
14 Oct 2026
30 Oct 2026
14 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of
work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. a) Two Loop Panel | 1 | Each | - | - |
| 2 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. | 40 | Each | - | - |
| 3 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. | 20 | Each | - | - |
| 4 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. | 4 | Each | - | - |
| 5 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. | 4 | Each | - | - |
| 6 | Supplying, installation, testing & commissioning of intelligent addressable programmable sounder complete as required. | 2 | Each | - | - |
| 7 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. | 1,200 | Mtr. | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.47 MB
BOQ_5187498.xls
BOQ • 0.28 MB
WBF-2911.pdf
Tender Documents • 0.53 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .