21 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, Testing & Commissioning and Maintenance of Medical Gas Pipeline System at Dialysis centre, (Plot no. G-1, Sector- 7, New Panvel) of PMC | |||||
| 1.01 | Supply, Installation, Testing and Commissioning of 2 X10 Cylinder Main Manifold for Oxygen with NRV pipe connection and with middle frame with chain compatible for Control Panel. Wall mounting type gas manifold fabricated with 5/8"x 15 swg. Copper pipe as per BS EN 1057 &brass blocks as per IS 319 equally spaced at 250 mm fitted on duly powder coated MS frame (95 x 45). Hydraulically tested at 300 bar with high pressure non return Valve, 1.25 metre long 5/16" x l6g copper tail pipe tested at 300 bar. With Standards IS/ISO 7396-1:2016 + A1:2017 htm 02-01 Part A:2006, CE. CDSCO. | 1 | Per Set | 1.25 | ₹1.25 |
| 1.02 | Supply, Installation, Testing and Commissioning of 2 X4 Cylinder Main Manifold for Oxygen with NRV pipe connection and with middle frame with chain compatible for Control Panel. Wall mounting type gas Manifold fabricated with 5/8"x 15 swg. Copper pipe as per BS EN 1057 &brass blocks as per IS 319 equally spaced at 250 mm fitted on duly powder coated MS frame (95 x 45). Hydraulically tested at 300 bar with high pressure non return Valve, 1.25 metre long 5/16" x l6g copper tail pipe tested at 300 bar. With Standards IS/ISO 7396-1:2016 + A1:2017 htm 02-01 Part A:2006, CE. CDSCO. | 1 | Per Set | 2.25 | ₹2.25 |
| 1.03 | Supply, Installation, Testing and Commissioning Microprocessor based 2 Source Fully Automatic Control Panel (LCD DISPLAY -TOUCH SCREEN) for Oxygen with 40 micron filters both sides (Left Bank & Right Bank),2100 LPM. It shall be dome loaded fully automatic control panel and shall have touch screen display. The manifold shall consist of two bank regulators (dome bias) used to reduce the cylinder pressure to the two lines regulators which in turn controls the final line pressure. The manifold has an intermediate and line relief valve that is internally connected to a common vent port, terminating into a l/2" FNPT pipe. The header bars shall be equipped with high-pressure shutoff valves outside the cabinet to allow for emergency isolation of the header bars. The header bar shall incorporate integral check valves for each station. The manifold is equipped with pressure transducers, which sends information to the main circuit board for operation of the fail-safe relay which transmits a remote signal to the master alarm or buzzer. The external shut-off valves connecting to the header bars must be ball valves capable of withstanding pressure of 3,000 psi. With Standards IS/ISO 7396-1:2016 + A1:2017 htm 02-01 Part A:2006,IS/ISO 10524-2:2018,IS/ISO 10524-4:2008 CE.CDSCO. Should also be installed with leak measurement device It should be specifically designed for measuring the flow of oxygen, catering to the requirements of hospital where precise oxygen flow control is critical, providing features for easy installation, versatile units election, and comprehensive diagnostic functions., It should incorporate at hermalmass flow sensor designed for measuring oxygen. It should utilizes a calorimetric measuring principle, eliminating the need for additional pressure and temperature measurements. It should supports digital interfaces such as Modbus RTU and RS485, facilitating seamless communication with other systems. Should also provide sanalog (4...20mA) and pulse outputs, ensuring compatibility with different data acquisition and control systems. Anda user- friendly display for unit selection and diagnostic functions. It should be designed to achieve a high level of accuracy, with specified measuring ranges 0-90 Nm/ hand accuracy levels of + 1.5% of measured value and + 0.3% of full - scale value. It should operate effectively in a temperature range of -3Oto80°C and can withstand operating pressure s ranging from-1 to 16 bar. It should be with display degreased or 02 service. The flowmeter should be designed for case of maintenance It should include diagnostic functions that can be read on the display or accessed remotely, facilitating proactive maintenance. | 1 | Nos | 3.25 | ₹3.25 |
| 1.04 | Supply, Installation, Testing and Commissioning Terminal units for Gas of British Standard (METAL) gas outlets with stainless steel probe are CE marked as a Class IIb Medical Device 93/42/EEC with notified body British Standards Institute and stamped CE. With Standards IS/ISO 7396-1:2016 + A1:2017 htm 02-01 Part A:2006,IS/ISO 10524-2:2018,IS/ISO 10524-4:2008 CE.CDSCO.
It should have one-piece chromed fascia plate shall frame the outlet. With the back rough-in mounted, the outlet shall adjust from 3/8" [10 mm] to 1" [25 mm] variation in wall thickness. It should have modular design and include a gas specific 16 ga. [1.6 mm] steel mounting plate designed to permit on-site ganging of multiple outlets, in any order, on 5" [127 mm] spacing. It should be cleaned and degreased for medical gas service, factory assembled and tested. It should be Indexed to eliminate interchangeability of gas services. It should have 360° Swivel Inlet Pipe for easy installation and should have universal rough-in assembly to accept quick disconnects or diss front adaptors or BS Adaptors
Medical Oxygen Gas | 62 | Nos | 4.25 | ₹263.5 |
| 1.05 | Medical Air Gas | 31 | Nos | 5.25 | ₹162.75 |
| 1.06 | Vacuum | 62 | Nos | 6.25 | ₹387.5 |
| 1.07 | Supply, installation, Testing and Commissioning of BPC Flow Meter with Dehumidifier Bottle of Specifications: Flow Range: 0-15 LPM For Adult, Accuracy: ±10% of the scale value or 0.2 LPM, whichever is higher. Material: Brass (chrome plated), float (AISI 316 with mesh), filter (AISI 3 16 wire mesh). Inlet/Outlet Connection: 3/8" BSP RH. Calibration: 50 psig (3.45 bar) at 21°C. Operation Mode: Manual (with a knob to adjust flow). Supply, It shall fully comply and meets with active medical device of class ILA and in compliance with the EN ISO15002:2008 standard. It should be duly CE marked and comply with 93/42/EEC Medical Devices: General. It shall be CE marked with the notified body number specified. It shall be provided with a copy of the certificate of origin. Its Pressure compensated to prevent back pressure build upon flow indicator. Expanded scale providing higher reading accuracy. Durable polycarbonate flow tube with cover. Flowmeter should be placed in the vertical position. lt should be lightweight of 200 g. The flowmeters should be of 0-15 LPM range for oxygen and with inlet pressure 50-60psi. (4.5 bar). The closing of the knob should be without any leakage. Polysulphone 250 cc Humidifier bottle should be unbreakable, reusable to disinfectants and complements. With Standards IS/ISO 15002:2008,IS/ISO 7396-1:2016 + A1:2017 htm 02-01 Part A:2006, CE.CDSCO. | 31 | Nos | 7.25 | ₹224.75 |
| 1.08 | Supply, Installation, Testing and Commissioning of Ward vacuum unit Adult (1000 ml) with vacuum regulator a clear, autoclavable polycarbonate jar with varying capacities a vacuum range of 0 to 760 mmHg, a regulator with an adjustable knob for precise control, and a gauge to measure negative pressure, often with a range of 0 1o -760 mmHg. The jar is designed to be shatterproof and autoclavable, while the regulator typically has an aluminium body, brass inner parts, and a neoprene diaphragm. Conform to relevant standards IS/ISO 10079-3 :2014 for devices .IS/ISO 7396-1:2016 + A1:2017 htm 02-01 Part A:2006, CE. CDSCO. | 31 | Nos | 8.25 | ₹255.75 |
| 1.09 | Supply, Installation, Testing and Commissioning of Medical Grade Copper Pipes BSEN 13348:2016, CE Cerified. Kite Marked. Copper Pipes used should be solid drawn, seamless, Deoxidized phosphorus, non-arsenical, half hard, tempered and degreased. Manufactured as per BSEN 13348:2016 in cither R250 half hard or R290 hard meeting the requirements as per the Medical grade Copper pipe standards. Degreasing of pipe shall be such that there is less than20mg/m2(0.20mg/dm2 of hydrocarbons on the degreased surface when tested by method specified by BSEN13348: 2016. 1t should also have LLOYD third-party inspection of copper pipes. The supplier should provide Manufacturer's Test Certificate of copper Pipes for physical Properties and chemical composition. Copper pipes joined by silver brazing method for copper to brass. Inert gas welding technique should be used by passing Nitrogen gas inside the copper pipes during brazing, in order to avoid carbon deposition inside the copper pipes. All copper pipes and fittings like bends, Tees, reducers and straight couplings should be as per ENI254-1 Copper pipes to be fixed with walls with suitable saddles and supports after erection, All the pipes should be cleaned or purged with the help of dry nitrogen gas & Should be tested with dry Nitrogen
12 mm Thickness 1 mm | 520 | RMTR | 9.25 | ₹4,810 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.46 MB
BOQ_2287955.xls
BOQ • 0.42 MB
New_Panvel_Tender.pdf
Tender Documents • 8.43 MB
PreBidQueries.pdf
PDF • 0.94 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .