Loading…
Loading…
Tender ID
Tender Value
₹19.8 L
EMD Value
₹49,462
Closing Date
13 Mar 2026, 5:00 pmClosed
Executive Engineer,Irrigation Division, Malappuram
Office of Executive Engineer,Irrigation Division, Malappuram
GENERAL RIDF XXIX CSIND Construction of a Lock cum Bridge at Ch 329 .756 km of West Coast Canal near Koottayi RCB in Tirur Ponnanipuzha in Mangalam Grama Panchayat Malappuram District General Electrical Work
2026_Irrig_844183_1
PWD/BLDG/TR/1862/2024_6_1_1/3
Open Tender
Electrical Works
Item Rate
Near Koottayi RCB
Please refer Tender documents.
10 documents required · 10 mandatory
₹2,760
₹49,462
5 Mar 2026
5 Mar 2026
18 Mar 2026
5 Mar 2026
13 Mar 2026
5 Mar 2026
MSB,SSB's and Metering panel
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.7:Supply and providing copper earth bus in the panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
OD55442/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.1.50sq mm wire single run
90.14.10.10:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16A -100A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N
2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
2.1.3:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N
90.14.11.1:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 100A with CBCT.
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
OD226253/2023-2024:Supply and providing LED indicators for all voltage ranges - Blue Colour
OD226254/2023-2024:Supply and providing LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour
OD226256/2023-2024:Supplying and fixing .5 amps to 4 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
90.14.11.17:MCCB AccessoriesSupply and fixing kastel interlock kit up to 250A.
OD193582/2024-2025:Supply ,fixing and installation of Three Phase Voltmeter accuracy class 1-Digitaltype
OD193583/2024-2025:Supply ,fixing and installation of Three Phase Ammeter accuracy class 1-digital type
OD226259/2023-2024:CURRENT TRANSFORMER - 100/5 A, 5 VA, accuracy class 1, Tape wound Metering CT
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.24.2:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.2 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
90.14.24.4:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.4 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Capacitor suitable for direct connection to motors.
90.14.24.5:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor suitable for direct connection to motors.
OD33213/2025-2026:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required in Panel board/DB's- 2.50 cm, 4 cm or 5 cm height.
OD298269/2024-2025:Supply , Conveyance and fitting 100A, HRC Fuse Base with suitable HRC Fuse link in the existing Meter box.
OD298270/2024-2025:Supply , Conveyance and fitting 63 A, 2 Way neutral links in the existing Meter box.
OD33233/2025-2026:Supply and installation reverse forward facility DOL starter up to 7.5 HP Motor with reverse forward facility complete
OD226255/2023-2024:Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour
OD33215/2025-2026:Supply and providing 2mm thick Elastomeric fire retardant insulating sheet as per IS 15652/2006 to withstand 3.3 KV dielectric strength near panel/substation.
Cable laying
90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.7.3:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp
90.12.10.3:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation63/50 mm or nearest size
90.12.9.3:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench63/50 mm or nearest size
90.12.5.28:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 35 sq mm
90.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
OD33234/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size ofglands for the following sizes of cables as required.(25 sq - 95sq mm with 20 mm wide x 1.20 mm thick clip)
OD33235/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required.(4 sq - 16sq mm with 12 mm wide x 1.20 mm thick clip)
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
90.12.24.2:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.4 sq mm
OD56116/2025-2026:Supplying and installation including all manner of supports/ suspenders, anchor bolts etc for cable trays made out of suitable size channel sections, slotted angles,flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colourwashing etc as required.
OD33238/2025-2026:Supplying , threading , laying and jointing of the following sizes of B class GI pipe with all required accessories in ground in the existing trench as protective covering to earth leads.80 mm dia
Earthing
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.1.6:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG)
90.16.3.1:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)20 x 3 mm GI strip
90.16.1.11:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.06 mm GI conductor (8 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
90.16.5.6:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG)
Control room and Watchman room wiring
1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group A
1.14.1:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.3:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
OD226250/2023-2024:Supply and fixing of LED bulb 5/7 w
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
90.15.4.1:Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.17.1:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.32 mm dia GI pipe
OD298527/2024-2025:Supply & Fixing 4 pole power terminal connector for terminating cables
OD34918/2025-2026:Supply and fixing Syntex junction box GSJB 1816 or equivalent with provision for fixing SP/DP MCB for terminating street light cable.
90.15.4.5:Supply Conveyance, installation, testing and commissioning of 40W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
1.21.4:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.40 mm
Diesel Generator
OD34922/2025-2026:Supply and installation of battery charger 12V - 10A of the DG set
OD34923/2025-2026:Supply and providing the following size of B class MS pipe conforming to relevant IS specifications complete with heavy guage specials such as bends,flanges etc welded and fixed at appropriate locations, providing cork sheet in between the flanges at the joints, bolting the flanges together, painting thepipe, flange etc with 2 coats of heat resistant paint suitable for outdoor applications, fixing the pipe firmly with fabricated structure/wall/any othermechanical support etc as required.- 80 mm dia B class MS pipe as extended exhaust pipe.
OD226270/2023-2024:Supply of diesel
OD34925/2025-2026:Provision for liaison works for obtaining statutory approval from the electrical inspectorate / departments.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.05 MB
SBD.pdf
Tender Documents • 1.88 MB
MATERIAL.pdf
Other Document • 0.44 MB
BOQ_1425179.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .