Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹1.4 CrAccepted-AOC KHASRA NO 183 10 SHYAM VIHAR HISAR HISAR HARYANA 125001 | HISAR | HARYANA | 125001 | ₹1.4 Cr | L-1 | Accepted-AOC AOC |
Tender Value
₹1.0 Cr
EMD Value
₹2.0 L
Closing Date
15 Jul 2019, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Division PWD B and R Br., Ambala
Upgradation of Civil Hospital from 200 Bedded to 300 Bedded Ambala City in Ambala Distt. (Pdg. Internal EI only) (Recall).
2019_HRY_80643_2
PWD/Elect-KNL/Elect-AMB/10548
Open Tender
Construction Works
Works
180 days
Ambala
Please refer Tender documents.
3 documents required · 3 mandatory
₹15,000
Executive Engineer, Elect. Division PWD Band R Br.
₹2.0 L
8 Oct 2021
3 Jul 2019
17 Jul 2019
3 Jul 2019
15 Jul 2019
3 Jul 2019
Amount
1 ( c ) Moulded case Circuit breakers. 31.12 Supply and erection of moulded case circuit breakers on wall or on existing pedestal including bonding to earth and necessary connections. 1.1 15 amp.to 60 amp. 415 V ,10 KA 3-phase. 31.12 c (i)
1.2 100 amp.to 220 amp.415 V,10 KA 3-phase. 31.12 c (ii)
1.3 250 amp. To 300 amp. 415 V , 35 KA 3-phase. 31.12 c(iii)
2 Supply and erection of M.S. angle iron frame duly welded for housing M.S. sheet & main switches etc. on it, fixed on wall by means of suiteble size of rag bolts with cement concrete ,duly painted with three coats of approved paint including one coat of red oxide. 31.13 2.1 Size 40 mm x 40 mm x 6 mm. 31.13(ii)
3 M.S.Sheet . 31.14 3.1 Supply and erection of 3 mm thick mild steel sheet duly welded on existing M.S. angle iron frame for fixing the main switches etc. as required, duly painted with three coats of approved paint including one coat of red oxide. ( i )
4 (K) Distrubution board with plug and socket. Supply and erection of sheet steel enclosure 2 pole / 3 pole with earth plug and socket suitable for incorporating single pole / triple pole MCB on wall / on existing pedestal complete with necessary connections etc. 31.15 4.1 S.P.N. enclosure for single pole MCB 20 amp. 31.15 (ii)
5 (L) Miniature Circuit Breaker and Isolator. 31.17 Supply and erection of miniature circuit breaker / isolator 240 /415 V in the existing distribution board including making necessary connections. 5.1 SP MCB of 9 KA breaking capacity 6 amp. to 32 amp. 31.17a) (ii)
5.2 SPN MCB of 9 KA breaking capacity 40 amp. 31.17(a) (ii)
5.3 TPN MCB of 9 KA breaking capacity 40 amp. to 63 amp. 31.17(a) (iii)
6 (M) Supply and erection of Fittings and Accessories. 31.18 6.1 Bakelite angle / straight button holder large size. 31.18 (xi)
6.2 Bakelite sheet including fixing with brass screws and washers. 31.18 (xviii) 6.3 3 mm thick . 31.18 (xviii) (b)
6.4 Ceiling rose flush / surface type . 31.18 (xvii)
6.5 Supply and erection of rectangular bulk head fitting of size 17 cm x 14 cm, aluminium casted with aluminium colour out side and white stove enamelled inside/complete with guard, glass etc. secured by brass screws suitable upto 100 watts lamp with B.C. lamp holder but without lamp. 31.18 (xx)
6.6 Erection only of 1x40 watts or 2x40 watts 1220 mm long / 1x20 watts or 2x20 watts ,610 mm long fluorescent tube fitting directly on wall including necessary connections with 0.75 sqmm ( 24 / 0.20 mm ) PVC copper flexible cable for connecting the tube with the adjecent point. 31.18 (xxiv)
6.7 Supply and erection of hexagonal M.S. box 1.60 mm thick having each side 8 cms , 7.5 cms deep top covered with M.S. lid by means of screws including 10 mm dia 30 cm long mild steel rod made into suitable suspension hook and erected in RCC slab for erection of fan , the bottom covered with 3 mm thick bakelite sheet with suitable holes , painting etc. complete with all labour and material required to complete the job. . 31.18 (xxvi)
7 (O) Erection and carriage of fans.. 31.2 7.1 Erection of ceiling fan complete with necessary earthing of fan and regulator including carriage from local railway station /goods transport /PWD store to the site of work. 31.20 (i)
7.2 Erection of exhaust fan complete with necessary earthing of fan and regulator including carriage from local railway station /goods transport /PWD store to the site of work. 31.20 (iii)
7.3 Making suitable hole in the wall upto 450 mm sweep exhaust fan including finishing the same and fixing of wire mesh duly fixed with Deodar wood frame of section 40 mm x 25 mm thick. 31.20 (v)
7.4 Pdg. and fixing of required size of deodar wood frame of section 50 mm x 32 mm for fixing exhaust fan upto 450 mm sweep. 31.20 (vi)
8 (P) Pipe Laying. 31.21 Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required. 8.1 Heavy guage welded conduit pipe 20 mm dia 1.60 mm thickness flushed. 31.21 (xxi)
8.2 Heavy guage welded conduit pipe 25 mm dia 1.60 mm thickness flushed. 31.21 (xxii)
9 (Q) Earthing 31.22 9.1 Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required. 31.22(iii)
9.2 Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) comlete as equired. 31.22(iv)
9.3 Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode. 31.22(v)
Pdg. and fixing 25 mm x 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required . 31.22(x)
9.4 Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required . 31.22(xi)
9.5 Pdg. and laying earth connections from earth electrode with 4.00 mm dia G.I. wire in 15 mm dia G.I. pipe from earth electrode as required . 31.22(xii)
9.6 Pdg. and fixing 25 mm x 5 mm copper strip on surface or in recess for connections etc. as required with all labour and material. 31.22(xiv)
9.7 Pdg. and fixing 25 mm x 5 mm G.I. Strip on surface or in recess for connections etc. as required with all labour and material. 31.22(xv)
9.8 Pdg. and fixing 4.00 mm dia G.I.wire on surface or in recess for loop earthing as required . 31.22(xvi)
10 (b) Lightning conductor Galvanised iron. 31.24 10.1 Supply and erection of 60 cm. X 60 cm. X 6 mm thick galvanised Iron plate including nacessary bolts and nuts to G.I. tape . 31.24 (iv)
10.2 Pdg. Standard watering tank including down pipe and C.I. cover with locking arrangement etc. 31.24 (v)
10.3 Supply and erection of 20 mm x 3 mm thick lightning conductor G.I. tape fixed with suitable G.I. stapples of same size. 31.24 (vi)
10.4 Supply and erection of G.I. tape 32 mm x 6 mm thick from earth electrode directly in ground and surface , fixed with G.I. stapples of same size. 31.24 (vii)
10.5 Supply and erection of 25 mm dia meter 1.5 metre long lightning G.I. tube rod tapered in to a point at the top with 16 cm. X 16 cm x 3 mm thick G.I. base plate and necessary nuts and bolts with washer. 31.24 (viii)
10.6 Prioviding and fixing , testing joint made of 20mm x 3mm thick G.I. strips 125mm long with 4 Nos. G.I. bolts and nuits, check nuts with washer complete. 31.24 (ix)
11 Supply and erection of under ground cable 1 metre below ground level covered with sand and bricks including necessary connections, digging and refilling of trenches:- 31.25 11.1 35 Sq. mm 3 ½ Core Armoured Cable. (xxvi)
11.2 50 sq mm 3 ½ Core cable (xxvii)
11.3 70 sq mm 3 ½ Core cable (xxviii)
11.4 95 sq mm 3 ½ Core cable (xxix)
11.5 120 Sq. mm 3.5 Core Cable . (xxx) Ard.
11.6 300 Sq. mm 3.5 Core Armoured Cable. (xxxiv)
11.7 400 Sq. mm 3.5 Core Cable . (xxxv) Ard.
12 Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections . 31.26 12.1 35 Sq. mm 3.5 Core Armoured Cable. (xxvi)
12.2 50 sq mm 3 ½ Core cable (xxvii)
12.3 70 sq mm 3 ½ Core cable (xxviii)
12.4 95 sq mm 3 ½ Core cable (xxix)
12.5 120 Sq. mm 3.5 Core Cable . (xxx) Ard.
12.6 300 Sq. mm 3.5 Core Armoured Cable. (xxxiv)
12.7 400 Sq. mm 3.5 Core Cable . (xxxv) Ard.
13 Supply and erection of suitable compression type brass cable glands for underground Cable. 31.28 13.1 10 Sq mm to 16 Sq mm cable 2 to 4 Core (ii)
13.2 25 Sq mm to 50 Sq mm cable 2 to 4 Core (iii)
13.3 70 Sq mm to 95 Sq mm cable 3 to 3 ½ Core (iv)
13.4 300 Sq mm to 400 Sqmm Cable 3 to 3.5 Core . (vii)
14 (X) Miscellaneous . 31.35 14.1 Supply of M.S.pipe (B-Class) for suspension rod of ceiling fan including threading if required. 31.35 (i) 14.2 15 mm dia. 31.35 (i) (a)
14.3 Supply and erection of caution notice plate in three languages. 31.35 (iii)
14.4 Supply and erection of shock restoration chart in glass frame 31.35 (iv)
14.5 Supply and erection of aluminium lugs heavy duty including crimping etc. upto the entire satisfaction of the Engineer-in-charge of the work. 31.35 (ix) 14.6 10 sqmm . 31.35 (ix) (c)
14.7 25 sqmm . 31.35 (ix) (e)
14.8 50 sqmm . 31.35 (ix) (g)
14.9 70 sqmm . 31.35 (ix) (h)
14.1 95 sqmm . 31.35 (ix) (I)
14.11 300 sqmm . 31.35 (ix) (n)
14.12 Supply and erection of cable route marker made of 50 cm long 10 mm dia M.S.rod welded / revitted at the top with 10 cm. Dia 5 mm thick G.I.plate inscribed with `cable' world on it , having a cross arm 30 cm. long of the same dia welded at the bottom , in existing trench 45 cm. below ground level . 31.35 (xi)
15 (A) PVC Insulated wiring in recessed conduit. 31.36 Wiring in 1.5 sq.mm PVC Insulated copper conductor cable in 1.6 mm thick conduit pipe. 15.1 Fan Point - Medium . 31.36
15.2 Fan Point- Long. 31.36
15.3 Light point -Short. 31.36 (ii)
15.4 Light Point - Medium. 31.36
15.5 Light Point- Long. 31.36
15.6 Twin control light point with 2 way 5 amp. single pole switch- Medium point. 31.36 (iii) b
15.7 Twin control light point with 2 way 5 amp. single pole switch-Long point. 31.36 (iii) c
15.8 Call bell point including M.S Box of size 180mmx100mmx60mm deep for call bell - Long point 31.36 (vi) c
15.9 3 pin 5 amp. plug point including earthing the 3rd. pin etc. -Short point. 31.36 (vii) a
15.1 3 pin 5 amp plug point including earthing the 3rd. pin etc. - Medium point. 31.36 (vii) b
15.11 3 pin 5 amp. plug point including earthing the 3rd. pin etc.- Long point. 31.36 (vii) c
15.12 3 pin 15 amp plug point including earthing the 3 rd. pin etc.with 4 sq mm PVC insulated copper conductor cable - Long point. 31.36 (viii) c
16 Supply and erection of PVC unsheathed copper conductor cable single core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe. 31.4 16.1 Size 1.5 sqmm (3 / 0.81mm). 31.40 (i)
16.2 Size 2.50 sqmm (3 / 1.05mm). 31.40 (ii)
16.3 Size 4 sqmm (7 / 0.85mm). 31.40 (iii)
16.4 Size 6 sqmm ( 7 / 1.05mm). 31.40 (iv)
16.5 Size 10 sqmm 31.40 (v)
16.6 Size 16 sqmm 31.40 (vi)
17 Supply and erection of double door sheet steel enclosures distribution boards suitable for MCBs and ELCBs etc. recessed in wall including bonding to earth with all labour and material requared complete the job in all respect upto the entire satisfaction of the Engineer-in Charge of the work. 31.41 17.1 12-way, SP & N (Horizontal) 31.41 (iii)
17.2 4-way, TP & N (Horizontal) (8+12) 31.41 (iv)
17.3 8-way, TP & N (Horizontal) (8+24) 31.41 (v)
17.4 12-way, TP & N (Vertical) (8+36) 31.41 (vii)
18 Supply and erection of PVC conduit pipe ISI marked (Medium) recessed in wall / ceiling etc. including cost of PVC bends, inspection box and all other material required to complete the job in all respect to the entire satisfaction of Engineer-in-Charge of work. 31.44 18.1 25 mm dia 31.44(b)
19 Supply and erection of copper lugs including crimping etc.upto the entire satisfaction of Engineer-in-Charge of work. 31.45 19.1 1.5 sqmm to 2.5 sqmm 31.45 (a)
19.2 4 sqmm to 6 sqmm 31.45 (b)
20 Supply and erection of MS sadles and clamps on wall / RCC parapit for fixing underground cable at distance of 0.60 metre centre to centre fixed by means of rawl plug including the cost of all labour and material required to complete the job in all respect. 31.48
21 Supply and erection of MS box made of 16 gauge MS Sheet recessed in wall, with arrangement of fixing brass screws, 2 Nos. check nuts and one No. PVC bush of required size including all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of work. 31.49 21.1 with 2 coats of primer. 31.49 (i)
21.2 With GI coating (anodized) suitable for modular accessories. 31.49 (ii)
22 Supply and erection of 60 mm dia 1.5 mtr long GI bracket(B class ) making an angle 10 to 15 degree with horizontal plane for mounting street light fitting on GI bracket on wall with 2 nos. 50 mm x 3 mm thick MS flat including cost of cutting welding of GI pipe complete with cement sand mixture nuts and bolts etc. including making necessary connection with all labour and material required to complete the job in all respect upto the entire satisfaction of engineer in charge of work. 31.53
23 Pdg. and fixing modular type accessories of approved make in existing box including fixing and making necessary connection, complete in all respect. 31.56 23.1 10 amp. 1 way switch (i)
23.2 10 amp. 2 way switch ( ii )
23.3 20 amp. switch ( iii )
23.4 10 amp. socket ( iv )
23.5 16 amp. socket ( v )
23.6 Bell push ( vi )
23.7 Fan regulator ( vii )
23.8 Call bell Ding-Dong ( Monitca ) ( viii )
23.9 Blinking Plate ( ix )
24 Pdg. and fixing GI concealed sheet metal boxes inner and outer faceplate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material requiered to complete the job in all respect. 31.57 24.1 1 & 2 module ( i )
24.2 3 Modules ( ii )
24.3 4 Modules ( iii )
24.4 6 Modules ( iv )
24.5 8 Modules ( v )
24.6 12 Modules ( vi )
25 Supply and erection of PVC pipe ISI marked (Medium) recessed in wall/ceiling etc including the cost of PVC bends inspecion boxes, iron hooks and cement concrete etc complete in all respect upto the entire satisfaction of engineer-in-charge of work 31.58 25.1 PVC pipe of 32 mm dia
26 Supply, Installation, Testing and Commissioning of wall / free standing floor mounting dust & vermin proof compartmentalized cubical panel made out of 2 mm thick CRCA sheet, required hardware 3 mm thick bakelite sheet provided all along the bus bar and cable tray separating switches compartment and supporting suitable channel duly painted by 2 coat zinc / red oxide primer followed by 2 coats of powder coating in grey or required shade after rising. the panel having PU / Neoprene rubber gasket of not less than 3 mm thickness separate detachable gland plate MS base channel hinged door with inter locking arrangement for equipments / switch wear. Transport acrylic sheet shall be provided in front of bus bar compartment to prevent direct access to bus bar bakelite sheet 3 mm thick for separately cable alley to BBC from switch chamber extended solid copper bars up to cable alleys shall be provided for outgoing connection which shall be paid as extra items. Side walls and cable alley compartments shall be having bolted type doors with detachable extension type structure. The Panel will be complete with control wiring (Copper) and fuse protection. (Only outer area on all sides shall be measured). 31.63
27 Supply and Fixing of copper bus bar duly tinned by means of SMC / DMC type insulator high tensile nuts and bolts spring washers fixing to same in existing panel including bending, cutting in required shape and size and insulation with color coding heat shrinkable PVC insulation complete in all respect. 31.64
29 Supply and Fixing of rotary handle for ON / OFF operation of existing MCCB in the LT panel including fixing the same in position with all labour and material to required to complete the job in all respect. 31.66 29.1 Rotary Handle up to 125 Amp., MCCB ( i )
29.2 Rotary Handle above 125 Amp., MCCB ( ii )
30 S/E of mark double walled corrugated (DWC) HDPE pipe laid 1 Mtr. Below ground level including digging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer in charge of work. 31.67 30.1 HDPE 63/50 mm outer dia / inner dia ( i )
30.2 HDPE 90/75 mm outer dia / inner dia ( ii )
31 Supply and erection of module case circuit breaker single pole/ 4 pole on wall /on existing pedestal including bounding to earth and making necessary connection required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 31.69 31.1 4 pole MCCB 500 amp viii
33 Supply & erection of cable tray made out of 2 mm thick galavanised perforated sheet steel including erection of the same on wall or ceiling with necessary fixture and other material required to complete the Job in all respect upto the Entire statisfaction of Engineer-in-Charge of the work. 31.81 33.1 40 x 100 mm i
33.2 50 x 150 mm ii
33.3 50 x 300 mm iii
34 Supply & erection of factory manufactureed cable tray cover made of 16g GI Sheet complete with Fastoner Nuts bots and in position including all petty material required to complete the Job in all respect upto the Entire statisfaction of Engineer in Charge of the work 31.82 34.1 Suitable for 40 x 100 mm i
34.2 Suitable for 50 x 150 mm ii
34.3 Suitable for 50 x 300 mm iii
35 Supply, Installation, Testing & Commissioning of Compact Air insulated aluminium TPN rising mains over all dimension should be as per standard size of manufacturer. Powder coated in approved color, fabricated of 1.6 mm thick GI sheet with plug in point provision, IP-54 protection, rise of 55 Degree temperature over an ambeint of 40 Degree temprature, alongwith thrust pad, fire barrier, End cover, suitable for 415 Volt 50 Hz AC and 2 No. aluminium earth strip as per IEC 604391 I & II, complete in all respect upto the entire satisfaction Engineer in charge of work. Make-C&S/Seimens/Legrand/Schneider Electric. NS-1 35.1 250 Amp., 15 KA SC for 1 Second. i)
35.2 400 Amp., 15 KA SC for 1 Second. ii)
36 Supply, Installation, Testing & Commissioning of End feed unit with FPMCCB of following size/capacity suitable for compact bar duct as above, complete in all respect upto the entire satisfaction Engineer in charge of work. Make-C&S/Seimens/Legrand/Schneider Electric. NS-2 36.1 250 Amp., 25 KA, 4 Pole MCCB ii)
36.2 400 Amp., 25 KA, 4 Pole MCCB iii)
37 Supply, instalation Testing and Commissioning of Tap of box with FP MCCB of 25 KA breaking capacity with adjustable thermal and fixed magnetic setting complete in all respect. NS-3 37.1 32/63 Amp. 4 Pole i
37.2 100/125 Amp. 4 Pole ii
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .