Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.9 LAccepted-AOC LAXMI BAZAER TEHSIL JOGINDERNAGAR DISTT MANDI HP | MANDI | HIMACHAL PRADESH | 175001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹50.7 L+₹3.1 L (6.44%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹56.2 L+₹8.5 L (17.9%)Rejected-AOC LOWER BAZAR SARKAGHAT DISTT MANDI H P | L3 | Rejected-AOC L3 | |
| 4 | Rejected-Technical VILLAGE BIDDI P O DARWAR TEHSIL DHARMPUR DISTT MANDI H P | - | Rejected-Technical Not fulfill the NIT requirement. | |
| 5 | Rejected-Technical | - | Rejected-Technical Not fulfill the NIT requirement. |
Tender Value
₹52.5 L
EMD Value
₹85,000
Closing Date
29 Dec 2023, 5:00 pmClosed
Executive Engineer Jal Shakti Division Sarkaghat
Executive Engineer Jal Shakti Division Sarkaghat
Replacement of Pumping Machinery to LWSS Baldwara LWSS Karni Darkoul LWSS Harlayan Padhyan Khanot LWSS Rada Manwana LWSS DK Thana
2023_HPIPH_82647_1
12804-60 dt 13.12.2023
Open Tender
Civil Works
Item Rate
90 days
Sarkaghat
Please refer Tender documents.
8 documents required · 8 mandatory
₹800
Executive Engineer Jal Shakti Division Sarkaghat
₹85,000
Yes
Dharampur
19 Mar 2024
15 Dec 2023
30 Dec 2023
15 Dec 2023
29 Dec 2023
15 Dec 2023
22 Dec 2023
Amount
Centrifugal Pump (LWSS Baldwara):- Supply & errection of horizontal spindle horizontal split casing/end suctions (back pull out arrangement) Single/double/multistage centrifugal pumps or combination of pumps in series/parellel of Mather & Platt/KSB/ Kirloskar or JSV approved make conforming to BIS 1520-1980 pump (Latest with up to to date amendments), read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling 3 phase squirrel cage electric induction motor of standard make such as Kirloskar/ NGEF/Cromption or JSV approved make conforming to IS 12615-2018 and should be energy efficient minimum IE2 compliant and totally enclosed fan cooled (TEFC) type ( latest with upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be suitable for operation on the data given below:
SITE CONDITIONS:- Total Head 239.76 mtrs Discharge required 13.26 LPS each set. No. of Pump required. 2.00 No. set (1 Nos. act as Standbye) Length of R/main 4892 mtrs. Dia of R/main 150 mm dia Location of the site of installation of machinery-The site is located near village Matour Tanda & 50 mtr on head load from nearest road head (for the installation of both machinery). Head Load (for the installation of both machinery). The Altitude of :- The Altitude of place is 730 mtrs above MSL Type of Current:- AC three phase supply with Rated Voltage:- 415 +/- 10% Type of water :- Clear water Charactristics of water :- a) Ambient Temperature b) Turbidity NTU < 50.00 NTU c) Hardness 260 Mg/Ltrs -- d) PH Value 7.5 -- e)Total Solid Mg/Lts)PH Value -- No of working hours. 8 Hours. Limit of Pump (-) 15% (+) 10% R.P.M. of Pumping RPM(or to be specified by the tenderer) Test run 8 Hours continueously for 7 days.
Providing ICTP Main Switch 200 Amp with HRC fuses / Side handled operated Change over switch of L&T/Crompton/Standard/Havells or JSV approved make suitable capacity Operational rating as per IS: 4064 (Part - II) 1978 with up to date amendments immediately after the power meter of HPSEB. 1No.
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections.1 No.
O.C.B. 200 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments. 1 No.
E.L.R. 200 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end. 1 No.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition). 1 No.
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating. 1 No.
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating. 1 No.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments. 1 Set
ICTP switches with HRC fuses 200 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments. 2 Nos.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments. 1 Set
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 16 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. 2 Nos.
Providing suitable Star delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. 2 Nos.
Providing Hour run meter of recommended make as per IS: 722 (Latest edition). 2 Nos.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 150 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6) 2 Nos.
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 125 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-300) 2 Nos. .
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 125 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API - 600 (Class ASA-300) . 2 Nos.
Providing double flanged Cast steel 150 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-300) 1 No. . .
Providing 150 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2. 2 Nos.
Providing 150 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury. 2 Nos.
Installation of all the items appearing at Serial No. 3 to 10 complete in all respect as per direction of Engg-inCharge. 1 No.
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.1. 1 Job
The size of the various components to be as under:-
(i)Suction pipe 150 mm dia Min. length = 10 mtr.
(ii) Delivery pipe 125 mm dia -do- = 6 mtr.
(iii) Common Header 150 mm dia -do- = 6 mtr.
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
(i)Motor side: 25 mm2 Min length = 20 mtrs. P/Rmt.
(ii) Supply side: 50 mm2 Min. length = 10 mtrs. P/Rmt.
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25 mm x 5 mm G.I. strips & G.I. wire of 25 x 3mm as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect. 1 Job
Centrifugal Pump (LWSS Karni Darkoul):- Supply & errection of horizontal spindle horizontal split casing/end suctions (back pull out arrangement) Single/double/multistage centrifugal pumps or combination of pumps in series/parellel of Mather & Platt/KSB/ Kirloskar or JSV approved make conforming to BIS 1520-1980 pump (Latest with up to to date amendments), read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling 3 phase squirrel cage electric induction motor of standard make such as Kirloskar/ NGEF/Cromption or JSV approved make conforming to IS 12615-2018 and should be energy efficient minimum IE2 compliant and totally enclosed fan cooled (TEFC) type ( latest with upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be suitable for operation on the data given below:
"SITE CONDITIONS:- Total Head 153.58 mtrs Discharge required 2.85 LPS each set. No. of Pump required. 2.00 No. set (1 Nos. act as Standbye) Length of R/main 825 mtrs. Dia of R/main 65 mm dia Location of the site of installation of machinery-The site is located near village Karni Darkoul & 50 mtr on head load from nearest road head (for the installation of both machinery). Head Load (for the installation of both machinery). The Altitude of :- The Altitude of place is 762 mtrs above MSL Type of Current:- AC three phase supply with Rated Voltage:- 415 +/- 10% Type of water :- Clear water Charactristics of water :- a) Ambient Temperature b) Turbidity NTU < 50.00 NTU c) Hardness 260 Mg/Ltrs -- d) PH Value 7.5 -- e)Total Solid Mg/Lts)PH Value -- No of working hours. 8 Hours. Limit of Pump (-) 15% (+) 10% R.P.M. of Pumping RPM(or to be specified by the tenderer) Test run 8 Hours continueously for 7 days."
Providing ICTP Main Switch 63 Amp with HRC fuses / Side handled operated Change over switch of L&T/Crompton/Standard/Havells or JSV approved make suitable capacity Operational rating as per IS: 4064 (Part - II) 1978 with up to date amendments immediately after the power meter of HPSEB. 1 No.
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections. 1 No.
M.C.B. 63 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments. 1 No.
E.L.C.B. 63 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end. 1 No.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition). 1 No.
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating.1 No.
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating. 1 No.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments. 1 Set
ICTP switches with HRC fuses 60 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments. 2 Nos.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments. 1 Set
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 5 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. 2 Nos.
Providing suitable Star Delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. 2 Nos.
Providing Hour run meter of recommended make as per IS: 722 (Latest edition) . 2 Nos.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 50 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6) 2 Nos.
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 40 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-300) 2 Nos. .
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 40 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API -600 (Class ASA-300) . 2 Nos.
Providing double flanged Cast steel 50 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-300) 1 No. . .
Providing 50 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2. 2 No.
Providing 50 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury. 2 Nos.
Installation of all the items appearing at Serial No. 17 to 24 complete in all respect as per direction of Engg-inCharge. 1 Job
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.1. 1 Job
The size of the various components to be as under:-
(i)Suction pipe 50 mm dia Min. length = 10 mtr.
(ii)Delivery pipe 40 mm dia -do- = 6 mtr.
(iii) Common Header 50 mm dia -do- = 6 mtr.
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
(i)Motor side: 4 mm2 Min length = 20 mtrs. P/Rmt.
(ii)Supply side: 6 mm2 Min. length = 10 mtrs. P/Rmt.
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 20 mm x 3 mm G.I. strips & G.I. wire of 4 SWG as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect. 1 Job
Centrifugal Pump (LWSS Rada Manwana):- Supply & errection of horizontal spindle horizontal split casing/end suctions (back pull out arrangement) Single/double/multistage centrifugal pumps or combination of pumps in series/parellel of Mather & Platt/KSB/ Kirloskar or JSV approved make conforming to BIS 1520-1980 pump (Latest with up to to date amendments), read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling 3 phase squirrel cage electric induction motor of standard make such as Kirloskar/ NGEF/Cromption or JSV approved make conforming to IS 12615-2018 and should be energy efficient minimum IE2 compliant and totally enclosed fan cooled (TEFC) type ( latest with upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be suitable for operation on the data given below:
SITE CONDITIONS:- Total Head 146.02 mtrs Discharge required 3.41 LPS each set. No. of Pump required. 2.00 No. set (1 Nos. act as Standbye) Length of R/main 1250 mtrs. Dia of R/main 65 mm dia Location of the site of installation of machinery-The site is located near village Rada Manwana & 50 mtr on head load from nearest road head (for the installation of both machinery). Head Load (for the installation of both machinery). The Altitude of :- The Altitude of place is 751 mtrs above MSL Type of Current:- AC three phase supply with Rated Voltage:- 415 +/- 10% Type of water :- Clear water Charactristics of water :- a) Ambient Temperature b) Turbidity NTU < 50.00 NTU c) Hardness 260 Mg/Ltrs -- d) PH Value 7.5 -- e)Total Solid Mg/Lts)PH Value -- No of working hours. 8 Hours. Limit of Pump (-) 15% (+) 10% R.P.M. of Pumping RPM(or to be specified by the tenderer) Test run 8 Hours continueously for 7 days.
Providing ICTP Main Switch 63 Amp with HRC fuses / Side handled operated Change over switch of L&T/Crompton/Standard/Havells or JSV approved make suitable capacity Operational rating as per IS: 4064 (Part - II) 1978 with up to date amendments immediately after the power meter of HPSEB. 1 No.
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections. 1 No.
M.C.B. 63 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments. 1No.
E.L.C.B. 63 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end. 1No.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition). 1No.
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating. 1No.
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating. 1No.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments. 1Set
ICTP switches with HRC fuses 60 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments. 2Nos.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments. 1Set
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 5 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. 2 Nos.
Providing suitable Star Delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. 2 Nos.
Providing Hour run meter of recommended make as per IS: 722 (Latest edition) . 2 Nos.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 65 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6) 2 Nos.
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 50 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-300) 2 Nos. .
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 50 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API - 600 (Class ASA-300) 2 Nos .
Providing double flanged Cast steel 65 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-300) 1 No. . .
Providing 65 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2. 2 Nos.
Providing 65 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury. 2 Nos.
Installation of all the items appearing at Serial No. 31 to 38 complete in all respect as per direction of Engg-inCharge. 1 Job
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.1. 1 Job
The size of the various components to be as under:-
(i)Suction pipe 65 mm dia Min. length = 10 mtr.
(ii)Delivery pipe 50 mm dia -do- = 6 mtr.
(iii) Common Header 65 mm dia -do- = 6 mtr.
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
(i)Motor side: 4 mm2 Min length = 20 mtrs. P/Rmt.
(ii) Supply side: 6 mm2 Min. length = 10 mtrs. P/Rmt.
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 20 mm x 3 mm G.I. strips & G.I. wire of 4 SWG as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect. 1 Job
Centrifugal Pump (LWSS DK Thana Stage -First):- Supply & errection of horizontal spindle horizontal split casing/end suctions (back pull out arrangement) Single/double/multistage centrifugal pumps or combination of pumps in series/parellel of Mather & Platt/KSB/ Kirloskar or JSV approved make conforming to BIS 1520-1980 pump (Latest with up to to date amendments), read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling 3 phase squirrel cage electric induction motor of standard make such as Kirloskar/ NGEF/Cromption or JSV approved make conforming to IS 12615-2018 and should be energy efficient minimum IE2 compliant and totally enclosed fan cooled (TEFC) type ( latest with upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be suitable for operation on the data given below:
Total Head 366.62 mtrs Discharge required 4.11 LPS each set. No. of Pump required. 2.00 No. set (1 Nos. act as Standbye) Length of R/main 2620 mtrs. Dia of R/main 80 mm dia Location of the site of installation of machinery-The site is located near village dagraon & 1000 mtr on head load from nearest road head (for the installation of both machinery). Head Load (for the installation of both machinery). The Altitude of :- The Altitude of place is 1015 mtrs above MSL Type of Current:- AC three phase supply with Rated Voltage:- 415 +/- 10% Type of water :- Clear water Charactristics of water :- a) Ambient Temperature b) Turbidity NTU < 50.00 NTU c) Hardness 260 Mg/Ltrs -- d) PH Value 7.5 -- e)Total Solid Mg/Lts)PH Value -- No of working hours. 8 Hours. Limit of Pump (-) 15% (+) 10% R.P.M. of Pumping RPM(or to be specified by the tenderer) Test run 8 Hours continueously for 7 days.
Providing ICTP Main Switch 100 Amp with HRC fuses / Side handled operated Change over switch of L&T/Crompton/Standard/Havells or JSV approved make suitable capacity Operational rating as per IS: 4064 (Part - II) 1978 with up to date amendments immediately after the power meter of HPSEB. 1 No.
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections. 1 No.
M.C.B. /M.C.C.B. 100 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments. 1 No.
E.LR. 100/5 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end. 1 No.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition). 1 No.
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating. 1 No.
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating. 1 No.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments. 1 Set
ICTP switches with HRC fuses 100/5 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments. 2 Nos.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments. 1 Set
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 9 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. 2 Nos.
Providing suitable Star Delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. 2 Nos.
Providing Hour run meter of recommended make as per IS: 722 (Latest edition) . 2 Nos.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 80 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6) 2 Nos.
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 65 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-300) 2 Nos. .
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 65 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API - 600 (Class ASA-300) . 2 Nos.
Providing double flanged Cast steel 80 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-300) 1 No. . .
Providing 80 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2. 2 Nos.
Providing 80 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury. 2 Nos.
Installation of all the items appearing at Serial No. 45 to 52 complete in all respect as per direction of Engg-inCharge. 1 Job
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.1. 1 Job
The size of the various components to be as under:-
(i)Suction pipe 80 mm dia Min. length = 10 mtr.
(ii)Delivery pipe 65 mm dia -do- = 6 mtr.
(iii) Common Header 80 mm dia -do- = 6 mtr.
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
(i)Motor side: 10 mm2 Min length = 20 mtrs. P/Rmt.
(ii) Supply side: 15 mm2 Min. length = 10 mtrs. P/Rmt.
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25 mm x 3 mm G.I. strips & G.I. wire 25x3mm as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect. 1 Job
Centrifugal Pump (LWSS DK Thana Stage - Second):- Supply & errection of horizontal spindle horizontal split casing/end suctions (back pull out arrangement) Single/double/multistage centrifugal pumps or combination of pumps in series/parellel of Mather & Platt/KSB/ Kirloskar or JSV approved make conforming to BIS 1520-1980 pump (Latest with up to to date amendments), read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling 3 phase squirrel cage electric induction motor of standard make such as Kirloskar/ NGEF/Cromption or JSV approved make conforming to IS 12615-2018 and should be energy efficient minimum IE2 compliant and totally enclosed fan cooled (TEFC) type ( latest with upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be suitable for operation on the data given below:
SITE CONDITIONS:- Total Head 208.30 mtrs Discharge required 4.11 LPS each set. No. of Pump required. 2.00 No. set (1 Nos. act as Standbye) Length of R/main 1025 mtrs. Dia of R/main 80 mm dia Location of the site of installation of machinery-The site is located near village Jamthera & 1000 mtr on head load from nearest road head (for the installation of both machinery). Head Load (for the installation of both machinery). The Altitude of :- The Altitude of place is 1371 mtrs above MSL Type of Current:- AC three phase supply with Rated Voltage:- 415 +/- 10% Type of water :- Clear water Charactristics of water :- a) Ambient Temperature b) Turbidity NTU < 50.00 NTU c) Hardness 260 Mg/Ltrs -- d) PH Value 7.5 -- e)Total Solid Mg/Lts)PH Value -- No of working hours. 8 Hours. Limit of Pump (-) 15% (+) 10% R.P.M. of Pumping RPM(or to be specified by the tenderer) Test run 8 Hours continueously for 7 days.
Providing ICTP Main Switch 63 Amp with HRC fuses / Side handled operated Change over switch of L&T/Crompton/Standard/Havells or JSV approved make suitable capacity Operational rating as per IS: 4064 (Part - II) 1978 with up to date amendments immediately after the power meter of HPSEB. 1 No.
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections. 1 No.
M.C.B. 63 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments. 1 No.
E.L.C.B. 63 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end. 1 No.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition). 1 No.
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating. 1 No.
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating. 1 No.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments. 1 Set
ICTP switches with HRC fuses 60 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments. 2 Nos.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments. 1 Set
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 5 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. 2 Nos.
Providing suitable Star Delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. 2 Nos.
Providing Hour run meter of recommended make as per IS: 722 (Latest edition) . 2 Nos.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 65 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6) 2 Nos.
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 50 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-300) 2 Nos. .
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 50 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API - 600 (Class ASA-300) . 2 Nos.
Providing double flanged Cast steel 65 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-300) 1 No. . .
Providing 65 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2. 2 Nos.
Providing 65 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury. 2 Nos.
Installation of all the items appearing at Serial No. 59 to 66 complete in all respect as per direction of Engg-inCharge. 1 Job
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.1. 1 Job
The size of the various components to be as under:-
(i) Suction pipe 65 mm dia Min. length = 10 mtr.
(ii)Delivery pipe 50 mm dia -do- = 6 mtr.
(iii)Common Header 65 mm dia -do- = 6 mtr.
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
(i) Motor side: 4 mm2 Min length = 20 mtrs. P/Rmt.
(ii)Supply side: 6 mm2 Min. length = 10 mtrs. P/Rmt.
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 20 mm x 3 mm G.I. strips & G.I. wire of 4 SWG as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect. 1 Job
dinesh kumar lath
M/S Anil Trading And Engineering Works
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .