Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.0 CrAccepted-AOC | ₹1.0 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹1.0 Cr+₹2.7 L (2.62%)Rejected-AOC KRISHNAKRIPA KOTTARAKARA | ₹1.0 Cr+₹2.7 L (2.62%) | L2 | Rejected-AOC L2 |
| 3 | L3₹1.1 Cr+₹3.9 L (3.78%)Rejected-AOC | ₹1.1 Cr+₹3.9 L (3.78%) | L3 | Rejected-AOC L3 |
| 4 | L4₹1.1 Cr+₹5.3 L (5.22%)Rejected-AOC | ₹1.1 Cr+₹5.3 L (5.22%) | L4 | Rejected-AOC L4 |
| 5 | L5₹1.1 Cr+₹7.3 L (7.15%)Rejected-AOC ERNAKULAM KERALA 682301 INDIA | ERNAKULAM | KERALA | 682301 | ₹1.1 Cr+₹7.3 L (7.15%) | L5 | Rejected-AOC L5 |
Tender Value
₹1.1 Cr
EMD Value
₹50,000
Closing Date
27 Oct 2023, 1:00 pmClosed
Chief Executive Officer
Chief Executive Officer, Park Centre, Technopark Phase-I Campus, Thiruvananthapuram
Electrification works of Plug and Play modules proposed at the rooftop of Nila Building, Technopark Phase-I Campus.
2023_ETPK_610067_1
ETPK/PH-I/023-24/E-07
Open Tender
Electrical Works
Item Rate
70 days
Technopark Phase-I Campus
Please refer Tender Document
8 documents required · 8 mandatory
₹5,900
₹50,000
Park Centre, Technopark Phase-I campus
16 Dec 2023
6 Oct 2023
28 Oct 2023
6 Oct 2023
27 Oct 2023
10 Oct 2023
10 Oct 2023
Amount
INTERIOR ELECTRIFIICATION WORKS(PART-A)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for two light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for three light point controled with one switch with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for four light point controled with one switch with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for five light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required.
2Rx1.5sqmm with 1R 1.5sqmm Green wire for earthing
2Rx2.5sqmm with 1R 1.5sqmm Green wire for earthing
2Rx4sqmm with 1Rx1.5sqmm Green wire for earthing
4Rx4sqmm with 1Rx1.5sqmm Green wire for earthing
2Rx1.5 sqmm
Supplying and drawing of UTP 4 pair CAT 6 LAN cable in the existing surface/ recessed PVC conduit as required.
Cat 6 cable
Supplying and fixing of 20mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of 25mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of 20mm of PVC flexible conduit along with accessories in surface
Supply and Fixing of 20mm ISI medium class PVC casing and capping of following diamensions along with accessories through wall in surface/ceiling
Supply and Fixing of 25mm ISI medium class PVC casing and capping of following diamensions along with accessories through wall in surface/ceiling
Supply and fixing of LED recess mounted (round type) down light with minimum lumen outout of 1200 Lumen, PC defuser, CRI>=80,PF>=0.95 ,CCT >=5700 K ,Efficacy >=100 lm/W
Supply and fixing of LED recessed ceiling fixture 600X600mm with a minimum lumen output of 2880 lumens ,CRI >= 80,PF>=0.95, ,CCT>= 5700K, Efficacy>=110 lm/W
Supply and Installation of Independent plug point with 6A 3 pin plug socket controlled by 6A switch with suitable modular plate, GI box/PVC box in recess/ surface .
Supply and installation of combined modular plug point for 6A, 3 pin plug socket controlled by 6A modular switch in the same switch board with suitable modular plate, GI box/PVC box in recess/ surface
Supply and Installation of Independent plug point with 16A plug socket controlled by 16A switch with suitable modular plate ,GI box/PVC box in recess/ surface .
Supply and Installation of Computer Socket(R-J45 jack) with suitable modular plate , GI box/PVC box in recess/ surface.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 100 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required.
3P 8W VDB Double Door
3P 12W VDB Double Door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections,powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
3P 4W DB Double Door
3P 8W DB Double Door
3P 12W DB Double Door
Supplying and fixing following way, single pole and neutral, IP 43, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
1P 8W DB Double Door
1P 12W DB Double Door
Supplying and fixing following 40 A double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 32A, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required
Supplying and fixing 32A, four pole, 415 V, isolator with metallic enclosure with connections, testing and commissioning etc. as required
Supplying and fixing following rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following pole in the existing MCB DB complete with connections, testing and commisioning.
5A to 32A ,SP MCB
5A to 32A ,DP MCB
MCB Blanking plate
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts,RCBO, having a sensitivity current 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, RCBO, having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supply & laying of Following A2XFY (Aluminium) power cable, conductors of best conductivity aluminium 1.1kV grade of the following sizes in the existing TRAY/RCC/ HUME / STONE WARE/ GI/ DWC pipe / Concrete trench/Clamping on wall etc. as required.
3.5x400 Sqmm A2XFY (Aluminium) Cable
3.5x240 Sqmm A2XFY (Aluminium) Cable
3.5x185 Sqmm A2XFY (Aluminium) Cable
3.5x120 Sqmm A2XFY (Aluminium) Cable
4x70 Sqmm A2XFY (Aluminium) Cable
4x16 Sqmm A2XFY (Aluminium) Cable
4x10 Sqmm A2XFY (Aluminium) Cable
3x4 Sqmm A2XFY (Aluminium) Cable
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5x400 Sqmm A2XFY (Aluminium) Cable
3.5x240 Sqmm A2XFY (Aluminium) Cable
3.5x185 Sqmm A2XFY (Aluminium) Cable
3.5x120 Sqmm A2XFY (Aluminium) Cable
4x70 Sqmm A2XFY (Aluminium) Cable
4x16 Sqmm A2XFY (Aluminium) Cable
4x10 Sqmm A2XFY (Aluminium) Cable
3x4 Sqmm A2XFY (Aluminium) Cable
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5x400 Sqmm
3.5x240 Sqmm
3.5x185 Sqmm
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Supply, laying/fixing of 6 SWG GI for earthing of switchboard and jointing as per IS:3043 / 87 in open trench / walls / pulling through pipes etc as required.
Providing and fixing 32 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required.
SITC of 1.5KVApure sine wave inverter with 200AH Tubular Battery with all accessories.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
PANEL WORKS (PART - B)
Incomer:
630A, 36 kA or above,TM,4P ,Variable settings, MCCB with all accessories including spreader link and extended rotary handle-1No
630/5A,5 VA,Cast resin type ,CL:1 ,CT-3 Nos
Digital Ammeter (Accuracy Cl 1)(0-630A)-3 Nos
Outgoings:
630A,36kA, 4P,Microprocessor type MCCB with all accessories including spreader link and extended rotary handle-1 Nos
160A,25kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-2 Nos
3-phase TOD meter,class 0.5s with RS 485 communication port- 1 No
3Ph Direct kWH meter 10-60A- 1 No
60/5A ,5VA cast resin type,Class 0.5s CT - 3 No
ATS PANEL
630 A , 4P ,ATS automatic and manual changeover with in-built time delay, Primary protection against over voltage, under voltage, single phasing, etc are required- 1 No
Incomer:
630A, 36 kA or above,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-1 Nos
630/5A,5 VA,Cast resin type ,CL:1 ,CT-3 Nos
Digital Ammeter (Accuracy Cl 1)(0-630A)-3 Nos
Outgoings:
400A,36kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-1 Nos
160A,25kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-1 Nos
125A,25kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-1 Nos
DG SET-160kVA
Supply, installation, testing and commissioning of 3phase 415V, 0.8pf 50Hz. DG set of the ratings 128KW/160 KVA, Water cooled Diesel generating set of prime duty comprising of diesel engine alternator, inbuilt fuel tank & Separate not less than 285ltr day tank(Within 3mtr Distance) with necessary fuel line pipe of 25mm MS pipe (heavy duty type) with necessary bends, clamps,supports and valves,painting as required, automatic starting system, battery, battery charger, electronic governor etc with all accessories required for synchronising the DG with another DG. The Generator set shall have a integral type acoustic enclosure as per latest CPCB norms. Diesel engine shall be suitable for continuous operation of generator set and satisfies with BHARAT STAGE-III/EURO-III specifications. Generator set inclusive of fly wheel, flexible coupling, air cleaner, corrossion resistor, fan with guard, fuel pump, fuel filter, electrical starting system( Remote starting) with starter, 24V battery with regulator, instrument panel, rpm indicator, residential silencer, complete with necessary control wiring compatible with SCADA, interconnections etc. including first filling of oil and diesel for commissioning of the DG set. Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary vibration isolation arrangement as per recommendations of manufacturer, which shall be installed on suitable cement concrete foundation as per manufacturers' standards(scope of contractor). Exhaust pipe with suitable specifications with long radius bend from residential silencer with necessary clamps, fixtures, civil works and painted with heat resistant, rust proof, bituminous paint of approved colors to a maximum of 20 m in stages including suitable rain gaurd for top(Scope of contractor). Fixing shall be done with proper clamps, expansion bolts, support angle of size 40 X 40X 6 mm fixed on the wall/ inside the duct as instructed by the Engineer.
DG SYNC PANEL
630 A , 4P ,ATS automatic and manual changeover with in-built time delay, Primary protection against over voltage, under voltage, single phasing, etc are required- 1 No
DG Incomer 1 & 2:
1000A,50kA,3P,uP Based EDO ACBwith O/L,O/C&E/F release- 1 No
250A, 3-pole 36 kA,MCCB, Microprocessor type, variable settings ,extended rotary handle,Spreader Terminals, etc are required- 1 nos
Earth Fault Relay- 1 No
50/5A,15 VA,Cast resin type ,CL: 5P10 ,CT-1 Nos
800/5A,15 VA,Cast resin type ,CL:1 ,CT-3 Nos
225/5A, 15 VA,Cast resin type ,CL:1 ,CT-3 Nos
Digital Multifunction meter (VAF + W/VA/PF/Wh) LED meter Cl 1 with RS485- 2 Nos
500A Neutral Contactor- 1 No 225A Neutral Contactor- 1No
Outgoings:
630A,36kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-2 Nos
DG Synchronization and Load sharing System( with DIEF) of existing 625kVA DG Set with new 160kVA DG set in the proposed DG Sync Panel(BOQ-45)
METERING PANEL-01
Incomer:
100A, 25 kA or above,4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-1No
100/5A,5 VA,Cast resin type ,CL:1 ,CT-3 Nos
Digital Multifunction meter (VAF + W/VA/PF/Wh) LED meter Cl 1 with RS485- 1 No
Outgoings:
32A,16kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-6 Nos
Dual Source Energy meter (CT Operated, Flush mounted type) with RS485 communication- 6 Nos
50/5A,CL- 05,Cast resin type CT,15VA-6 Nos
METERING PANEL-02
Incomer:
100A, 25 kA or above,4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-1No
100/5A,5 VA,Cast resin type ,CL:1 ,CT-3 Nos
Digital Multifunction meter (VAF + W/VA/PF/Wh) LED meter Cl 1 with RS485- 1 No
Outgoings:
32A,16kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-6 Nos
Dual Source Energy meter (CT Operated, Flush mounted type) with RS485 communication- 6 Nos
50/5A,CL- 05,Cast resin type CT,15VA-6 Nos
APFC PANEL- 70kVAR
Design, supply, erection, testing and commissioning of cubicle type floor mounting made out of14SWG, MS sheet enclosure with 250A, 415Volts, 3 phase,not less than 25kA, TP&N,50 Hz Aluminium busbars, single busbar system, cable chamber,Voltmeter,Ammeter, protection relays, with necessary interconnection, painting, earthing,power factor controller-,APFC relay (six stage) & CT with ratio 250/5A-15VA (cast resin) etc.comprising of the following, the board shall be fabricated as per the SLD with IP54
Incomer:
160A, 4-pole 25 kA,MCCB, Microprocessor type, variable settings ,extended rotary handle,Spreader Terminals, etc are required- 1 nos
Outgoings:70kVAR
1 set of 25 KVAR MPP (Metalised Poly Propylene) Capacitor with 63A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 25 KVAR as required.
1 set of 20 KVAR MPP (Metalised Poly Propylene) Capacitor with 63A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 25 KVAR as required.
1 set of 15 KVAR MPP (Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 15 KVAR as required.
1 sets of 5 KVAR MPP (Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 5 KVAR as required.
1 sets of 3 KVAR MPP (Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 5 KVAR as required.
1 sets of 2 KVAR MPP (Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 2 KVAR as required.
With necessary Aluminium busbars, interconnections, providing Digital Voltmeter,Ammeter , RYB and “ON / OFF / TRIP" indicating lamp at incomer, control PT, CTs, MPCBs and MCB and APFC Relay etc. and all other necessary accessories as per the specification/SLD. Each KVAR capacitor in a separate compartment with necessary ventilation arrangemnts or weld mesh arrangements as required by the KSEI guidelines
PANEL DISMANTLING
Dismantling of the existing STATCOM panel located at NILA-SS2A Substation including disconnection of power and control cables, removal of foundation bolts and other supports, moving the panel to the location specified by TP Engineer within a distance not more than 50 metres.
Supply and erection of vertical and horizontal type cable trays and cable supports fabricated out of MS angles (ISA) and MS flats with sufficient width and spacing between successive cross members and supported at adequate spacing. The cable trays and supports shall be painted with two coats of Zinc Chromate primer and two coats of enamel paint. (Size as specified by Technopark as per site conditions)
Supply and providing 2 mm thick sythetic type and 1 m wide electrical grade insulation mat to withstand 3.3 kV dielectric strength conforming to IS 15652 (2006).
Supply of CO2 Extinguisher 4.5Kg, Fire rating of 55B, PESO approved Aluminium cylinders with CCOE certification, IS 15683:2018 standard, Certifications from BIS, EN, CE, ISI and date of manufacture imprinted on cylinder, coated with High Glossy PU Paint, anti corrosive make, Discharge hose with the conductive wires to dissipate the static charge generated during CO2 discharge, Carbon dioxide gas having a purity of 99.5% and conforming to IS15222, “D” handle for ease of carrying and operator safety, Cold impact extrusion can, Used-Unused Mechanism, Squeeze Grip, Gross Weight 11.16 Kg, Empty Weight 6.66Kg, Can Height 860mm, Diameter 140mm, Discharge time minimum 8 Seconds, Controllable discharge mechanism, Range minimum 2m, two piece floating spindle valve with a handwheel to operate, venyl sticker/label with all the details including operational instructions, 10 years warranty
Preparation of all drawings submitting and getting approval and Sanction for Energisation from Kerala State Electrical Inspectorate by a Licensed A Class Electrical Contractor for the electrification of proposed modules, load additions and modification works which include current and past additions in the existing Transformers, existing and newly added DG's , HT & LT panels in substations, submitting of Completion certificates and arranging inspection, getting sanction and energization certificate etc., providing and fixing neatly Laminated Electrical schemes and layout for Nila Substation. The statutory payments made to Kerala State Electrical Inspectorate(KSEI) will be reimbursed on production of original receipts or attested copies of original.
K K Associates
Powertech Electricals and Engineers
SANTHOSH ELECTRO-TECH PVT LTD
IDEAL DATACOM NETWORK AND ELECTRICAL SOLUTIONS PVT LTD
VIJAYA ELE TECHS PRIVATE LTD.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .