Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹44.3 LAdmitted-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | ₹44.3 L | L1 | Admitted-Finance |
| 2 | L2₹49.1 LAdmitted-Finance 12 10 EAST PATEL NAGAR NEW DELHI DELHI 110008 | WEST DELHI | DELHI | 110008 | ₹49.1 L | L2 | Admitted-Finance |
| 3 | L3₹51.4 LAdmitted-Finance | ₹51.4 L | L3 | Admitted-Finance |
| 4 | L4₹56.7 LAdmitted-Finance | ₹56.7 L | L4 | Admitted-Finance |
| 5 | L5₹66.4 LAdmitted-Finance C 2 MADEL INDUSTRIAL ESTATE NEAR VIRWANI INDUSTRIAL ESTATE ROAD NO 2 GOREGAON E MUMBAI 400063 | MUMBAI | MUMBAI | MAHARASHTRA | 400063 | ₹66.4 L | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | TECHNOCRATS SECURITY SYSTEMS PVT LTD L5 | Equip Resource L4 | GLYPTIC L1 | ACS Technologies Limited L3 | VVDN Technologies Private Limited L2 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Fire Alarm Control Panel and associated devices
- EN-54 certified
- Control panel shall be populated with redundant CPU, which shall take over the in case of primary CPU without manual intervention.
- No of Loops per panel: 8; Each loop with redundant circuitary, which shall come in line without manual invervention. same shall be indicated.
- Loop capability: 250 nos. of Multi criteria detectors or equivlant devices.
- Loop Length: 6 loop cards with 1500 mtr cable length capability, 2 loop cards with capacity to drive 2500 mtr cable, using 1.5 sq.mm shielded twisted pair copper cable.
- Ethernet communication: with other panels, and computer for monitoring & configuration.
- Two or more network cards for redundancy. Option to connect fiber patch cable in network card shall be available.
- One Relay output module having Eight or more freely programmable, bistable relays, 230 V AC, / 2A or better rating shall be included.
- One Desktop computers (with latest hardware & software) with GUI, for monitoring, operation & configuration shall be provided with 55” wall mount 4K display. Desktop computer shall be capable of 24x7x365 days operation.
- License with number of installed devices + 100% extra, number of Panels + 3 extra, shall be available for this computer with lifetime validity. The license shall be transferrable in case of failure of native computer.
- Status indication of panel and all loop cards shall be available at front face;
- Auto dialing communicator having facility for fast communication with Security/Police/Fire Services in case of emergency
- Dedicated battery backup for 48 hour (normal operation) & minimum 30 min under alarm condition.
- Triplicate earthing terminals for safety, shield and signal grounding
- Capable to actuate a third party devices (fire dampers etc.) through monitor module
- Storing the logs of alarms, times and action taken report, min 30,000 logs
- In-built buzzer
- Suitable for Class-A type of wiring and work on positive sequence as per NFPA-72
- Facility & equipment shall be provided for simulating the fire condition for testing purpose
- Normal power supply failure shall be annunciated audio-visually
- MS enclosure for the FACP with front door fitted with acrylic sheet.
- Two coat of anticorrosive paint followed by two coat of synthetic enamelled
- Seismic qualification | 1 | Set | 17,69,213.2 ₹17.7 L | 8,84,000 ₹8.8 L | 5,81,950.23 ₹5.8 L | 13,79,000 ₹13.8 L | 13,54,500 ₹13.5 L |
| 2.00 | Fire alarm Repeater panel
- EN-54 Certified
- Active Type, shall be compatible to receive data from FACPs
- Easily readable, bright display
- MMI shall be the same as the main Controller
- Audio & visual Alarms during fire
- Display of Alarm & Fault similar to the Main Panel
- User authentication
- Single point failure in the cable shall not affect the performance and shall intimate the exact location of failure in all Panels
- 24Hrs back up time for normal condition and minimum 30 min back-up time for fault/alarm condition, | 2 | No | 1,02,255 ₹2.0 L | 93,000 ₹1.9 L | 1,09,048.52 ₹2.2 L | 82,800 ₹1.7 L | 79,000 ₹1.6 L |
| 3.00 | Multi criteria detector
- EN 54 certified
- Intelligent, addressable,
- Combination of Smoke detection and heat detection
- Shall be able to identify the fires as per EN-54-29 & VDS
- Thermal sensor shall be able to detect both maximum temperature Pre-defined (as per standards) and the rate of rise temperature
- Inbuilt isolator, Drift compensation facility,
- False alarm immunity and a superior signal to noise ratio, Automatic contamination compensation, Un-authorized detector removal detection, Adaptability with surrounding temperature fluctuations, built-in false alarm filtering provision as per EN54,
- detection of both smouldering fires and open fires
- EN-54-29: type of fires shall be detected
- Operating conditions: 15 to +60oC, 10% to 95% RH (non- condensing) | 408 | No. | 3,783.92 ₹15.4 L | 4,250 ₹17.3 L | 2,769.21 ₹11.3 L | 2,158 ₹8.8 L | 2,278 ₹9.3 L |
| 4.00 | Sounder base smoke detector
- Multi-criteria Detector with Sounder with Base; EN-54 certified
- Specifications for Multi detector are mentioned above,
- Sounder Volume (DIN tone) – (max) 92 dB or more, configurable SPL
- Operating conditions: 15 to +60°C, 10% to 95% RH (non- condensing) | 31 | No | 7,539.62 ₹2.3 L | 12,550 ₹3.9 L | 7,213.44 ₹2.2 L | 5,258 ₹1.6 L | 4,920 ₹1.5 L |
| 5.00 | Manual call points
- EN 54 certified
- Double action, re-usable, addressable, Loop powered
- Shock and vibration resistant, polarity insensitive
- LED status indication, in-built isolator,
- Operating conditions: 15 to +50°C, 10% to 95% RH (non- condensing) | 22 | No | 4,884.17 ₹1.1 L | 7,700 ₹1.7 L | 4,477.46 ₹98,504.12 | 2,898 ₹63,756 | 2,880 ₹63,360 |
| 6.00 | Response Indicator
- EN-54 certified
- shall start flashing when the detector in that particular' area / zone has been activated
- LED status indicator
- Loop powered | 50 | No | 330 ₹16,500 | 300 ₹15,000 | 159.14 ₹7,957 | 250 ₹12,500 | 750 ₹37,500 |
| 7.00 | Duct Detector & indicator
- EN 54
- Shall detect smoke in ventilation ducts
- Air from the ventilation duct is constantly directed through the sample tube and the air sampling housing to the smoke detector
- It shall have separate indication for smoke detection and detector trouble alarm due to accumulation of dust etc
- Air velocity: 1.5 to 20 m/s
- Protection class: IP 54
- Loop powered, in-built isolator
- Detector along with suitable housing shall be suplied
- in-built or additional Relay contact with 60 W rating
- Operating conditions: 15 to +50°C, 10% to 95% RH (non- condensing) | 2 | No | 11,437.84 ₹22,875.68 | 17,500 ₹35,000 | 14,002.53 ₹28,005.06 | 11,050 ₹22,100 | 10,500 ₹21,000 |
| 8.00 | Sounder / Hooter along with Strobe/ Flasher
- Addressable, loop powered sounder along with strobe
- EN 54 certified
- In-built isolator
- SPL should be minimum 96 dB or more, adjustable SPL
- Option of different tones for alarm detection in different floors
- should draw minimum power from loop, at least 20 loop powered sounders in the same loop,
- Sounder shall be combined with a Flasher
- strobe shall be wall/celling mounted with 360 deg. Viewing angle | 14 | No | 8,296 ₹1.2 L | 16,600 ₹2.3 L | 6,700.53 ₹93,807.42 | 6,552 ₹91,728 | 6,280 ₹87,920 |
| 9.00 | Fire Fighter Telephone console
- This system allows firefighters and others to communicate with one another during emergency situations.
- Standalone unit containing the systems master handset & power supply
- Connectivity for 5 or more zones, with status indication of each zone
- Full duplex audio, Conference call facility
- In-built or add -on Power back-up of at least 120 V*A*hr. shall be provided with protectio to Deep discharge, short, high temperature,
- Suitable charging & monitoring system for emergency
- Complying to BS 5839-9 (emergency voice communication systems) or equivalent standard.
- Supports 500 mtr or more cable length per zone
- Monitored handsets, indicate the location of the call and provide an audio visual indication to alert the operator’s attention.
- Master telephone handset with a push to talk button and a Flexible-coiled five (5) foot cord
- minimum size of the wire shall be not less than 0.8 sq.mm for electronic-circuits and 1.5sq.mm for electrical circuits & 14AWG for grounding
- Stainless Steel Flush Mount enclosure.
- 230 V AC mains power supply. | 1 | Set | 2,42,470 ₹2.4 L | 56,000 ₹56,000 | 15,862.13 ₹15,862.13 | 2,04,000 ₹2.0 L | 82,280 ₹82,280 |
| 10.00 | Fireman's Telephone handset
Telephone handset shall have 6.5 / 4.5 mm male jack mm jack for inserting in fireman telephone jack at various field locations.
- The telphone handset shall be rugged & reliable. | 6 | No | 18,210 ₹1.1 L | 4,800 ₹28,800 | 1,528.24 ₹9,169.44 | 11,520 ₹69,120 | 12,000 ₹72,000 |
Tender Value
₹71.1 L
EMD Value
₹1.4 L
Closing Date
10 Nov 2025, 3:00 pmClosed
Chief Engineer,BARC Visakhapatnam
BARC Visakhapatnam, Dosuru post, Gajuwaka Yellamanchili Highway, Near Nagavaram Jn., Visakhapatnam 531011
SITC of Fire Alarm System for TL-3, BARC, Vizag
2025_BARC_879865_1
BARC/ESS(V)/ET/03/2025-2026
Open Tender
Electrical Works
365 days
BARC Mainsite Visakhapatnam
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹1.4 L
27 Feb 2026
6 Oct 2025
17 Nov 2025
6 Oct 2025
10 Nov 2025
9 Oct 2025
6 Oct 2025 - 20 Oct 2025
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.92 MB
TenderDocument032025.pdf
Tender Documents • 2.16 MB
TechSpecs032025.pdf
Tender Documents • 0.46 MB
LETTERTRANSMITTAL032025.pdf
Tender Documents • 0.65 MB
FormOfAgreement032025.pdf
Tender Documents • 0.49 MB
FORMSATOH012025.xls
Tender Documents • 0.06 MB
BOQ_924837.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid