(A) Electrical General work in connection with Engg. work "Kurseong-Mahanadi:- Construction of Office-cum-Barrack at DHR-KGN-MHN". (B) Electrical General work in connection with Engg. work "UPGRADATION OF OFFICER REST HOUSE AT DARJEELING IN KATIHAR DIVISION (Old Building)". (C) Electrical General work in connection with Engg. work "UPGRADATION OF OFFICER REST HOUSE AT DARJEELING IN KATIHAR DIVISION (New Building)".
RT22_2026
RT22_2026
Open
10 Months
Darjeeling, West Bengal
₹0
₹1.5 L
21 Jun 2026
21 Jun 2026
1 Jul 2026
DIVISION (New Building))
Item- 1 Please see item breakup for details.
S No. Item Description of Item Unit Qty Rate Amount
KATIHAR DIVISION-ELECTRICAL/N F RLY
1 1 Supply, wiring, testing & commissioning of Numbers 187.00 797.00 149039.00
concealed point wiring by FR PVC insulated and
unsheathed 1.5 sq mm, single core multi strand
copper wire with earth continuity wire by PVC
insulated and unsheathed 1 sq mm , single core
multi strand copper wire concealed on wall
through PVC rigid conduit pipe of dia not less
than 20 mm dia heavy duty including all types
of joints and bends as required, complete with 6
amps flush type controlling modular switch to be
mounted on modular GI inner plate and modular
mounting frame of suitable module as per
requirement complete to be concealed in wall as
per instruction of Engineer Incharge at site.
Existing wall should be cut and re-mended to
original finish by contractor's own material. (a)
FL Point/LED Tube Point/LED Recess Light
Point/LED Decorative Light Fitting Point/LED
Mirror Light Point/LED Reading Light Point with
2 2 (b) Lamp Point with angle holder Numbers 30.00 704.00 21120.00
3 3 (c) Exhaust fan point with c/rose Numbers 6.00 806.00 4836.00
4 4 (d) Plug point 6 amps on board complete Numbers 16.00 361.00 5776.00
5 5 Supply, wiring, testing & commissioning of Numbers 20.00 737.00 14740.00
c o n c e a l e d plug point on separate board
complete with 2 x 6 Amp modular socket and
6/10 amps modular switch to be mounted on
modular GI inner plate 6M and 6M modular
mounting frame with GI box to be concealed in
wall as per instruction of Engineer Incharge at
site. Existing wall should be cut and re-mended
to original finish by contractor's own material.
6 6 Supply, wiring, testing & commissioning of Numbers 30.00 855.00 25650.00
concealed 6/16 amps power plug point on
separate board complete with modular 16 amps
switch (with indicator) and 6/16 amps 3 pin
combined shuttered socket to be mounted on
modular GI inner plate 4M or suitable size with
modular mounting frame to be concealed in wall
as per instruction of Engineer Incharge at Site.
7 7 Supply, wiring, testing & commissioning of Numbers 6.00 395.00 2370.00
concealed call bell point wiring by FR-LSH PVC
insulated and unsheathed 1.5 sq mm, single
core flexible copper wire concealed on wall
through PVC rigid conduit pipe of dia not less
than 20 mm dia with all types of joints and
bends as required complete with 6 amps bell
push controlling switch fitted on half flush MS
board with hylem sheet top and earth continuity
wire by PVC insulated and unsheathed 1 sq mm,
single core multi strand copper wire complete to
be concealed in wall including supply, fixing,
testing & commissioning of call bell "Ding Dong /
Multitune door bell" type.
8 8 Supply, fixing, connection & testing of indoor Numbers 20.00 987.00 19740.00
LED tube batten with 20 watt LED T8 tubular
lamp with extuded aluminium body and PC
diffuser complete with inbuilt driver (System
wattage-20 Watt, System efficacy> 105 lm/W,
Power factor 0.90) with suitable fixing
arrangement as per instruction of Engineer
incharge at site.
9 9 Supply, installation, testing & commissioning of Numbers 100.00 1614.00 161400.00
15 Watt Recess mounted downlighter (Down
Warm Light) with pressure die-cast aluminium
heat sink & PC diffuser with integrated driver as
per instruction of Engineer Incharge at Site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
10 10 Supply and fixing of Hanging type Decorative Numbers 15.00 5000.00 75000.00
light fitting with 1 x E27 9 Watt LED lamp
(Jaguar KCH-CHR-MD150031271B or similar),
Heritage type as per instruction of Engineer
Incharge at Site.
11 11 Supply and fixing of Wall Mount Decorative Light Numbers 30.00 2439.00 73170.00
Fitting with 1 x 7 Watt LED lamp, E27 (Jaguar
JNL-CHR-WLSL55004E27 or similar), Heritage
type as per instruction of Engineer Incharge at
12 12 Supply, fixing, connection, testing & Numbers 6.00 1336.00 8016.00
commissioning of surface mounting sleek LED
mirror light 5 W or 7 W, IP 20, 1 ft version
powder coated CRCA housing, high output
diffuser including suitable fixing arrangement on
surface as per instruction of Engineer incharge
13 13 Supply, installation, connection & tesing & 4 Numbers 12.00 1641.00 19692.00
watt LED spot light, fully rotable to any angle,
warm white color, made of aluminium body,
IP20, Beam angle-50°, with fixing on wall as per
instruction of Engineer incharge at site. (For
14 14 Supply, fixing & testing of LED retrofit lamp 9 Numbers 30.00 146.00 4380.00
watt, B-22 cap as per instruction of Engineer
incharge at site.
15 15 Supply, installation, testing & commissioning of Numbers 6.00 2824.00 16944.00
300 mm sweep (metallic) heavy duty exhaust
fan, 1400 RPM complete with fixing on wall by
suitable size bolts & nuts grouted on wall as per
instruction of Engineer incharge at site.
16 16 Supply, wiring & testing of main wire by 2.5 sq Metre 1200.00 75.00 90000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
concealed in wall through PVC rigid conduit pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
17 17 Supply, wiring & testing of main wire by 4 sq Metre 1000.00 87.00 87000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
concealed in wall through PVC rigid conduit pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
18 18 Supply, wiring & testing of main wire by 6 sq Metre 600.00 100.00 60000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
through PVC rigid conduit pipe/polythene pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
19 19 Supply, wiring & testing of main wire by 10 sq Metre 500.00 110.00 55000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
through PVC rigid conduit pipe/polythene pipe
not less than 25 mm dia as per instruction of
Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
20 20 Supply, installation, testing & commissioning of Numbers 1.00 1193.00 1193.00
modular power unit complete with 32 Amp mini
MCB DP "C" series 3kA , 25 amps starter, 25
Amp Socket and 25 Amp plug to be mounted on
6 module GI box, 6 module combined plate
concealed on wall and wiring by 6 sq mm, Single
Core FR-LSH PVC Insulated Industrial Grade
Copper Conductor (Unsheathed) Flexible Cables,
1100 Volts with earth coninuity wire by 1 sq mm
copper cable Conforming to IS: 694 to be drawn
through Rigid PVC conduit pipe not less than 20
mm dia as per instruction of Engineer incharge
21 21 Supply, Installation, Testing & Commissioning of Numbers 1.00 64659.00 64659.00
2.0 TR All Weather Invertor type Split Air
Conditioner having non-CFC refrigerant, BEE 3
star 2019 rated or above. Make Blue Star,
Voltas, Hitachi, Carrier complete including MS
base frame for outdoor unit, connecting the unit
to refrigerant piping, drain pipe, power cabling &
control cabling complete with all accessories as
per IS & IE rules and as per instruction of
Engineer Incharge at Site.
22 22 Supply, fixing, testing, commissioning of 15 W Numbers 10.00 8096.00 80960.00
LED Bollard light IP 66 complete as per IS & IE
rules and as per instruction of Engineer Incharge
23 23 Supply, fixing & testing of hanging type Mini Numbers 6.00 23882.00 143292.00
Chandelier, Colour-Gold with 5 watt LED Lamp
as per instruction of Engineer Incharge at Site.
24 24 Supply, installation, testing & commissioning of Numbers 20.00 4200.00 84000.00
ILLUMINA PENDANT 1LS E27 MATT GLD Ceiling
Light with an elegant oval-shaped fixture with a
matte gold finish designed to illuminate from it's
center perfectly pairing with Dazzle Shine lamp
as per instruction of Engineer Incharge at Site.
25 25 Supply, installation, testing & commissioning of Numbers 30.00 2589.00 77670.00
4 W BRILLANTE LINEAR WALL WASHER Light
Crafted from Aluminum Die Cast with Bi-
Directional Beam. Its integrated LED ensures
long-lasting and energy-efficient with IP65
Protected as per instruction of Engineer
Incharge at Site.
26 26 Supply, fixing, testing and commissioning of 05 Numbers 10.00 3797.00 37970.00
meter LED strip of wattage less than or equal to
48 watt complete with driver and as per IS & IE
rules, site requirement prior approval of sample.
KATIHAR DIVISION-ELECTRICAL/N F RLY
27 27 Supply, installation, testing and commissioning Numbers 10.00 52751.00 527510.00
of drop down Led decorative light warm white
Cast iron based pole of height 3 meter with 45
watt capacity double arm bracket mild steel
grooved pipe pole made out of cast iron base
390 mm base dia, Top 83mm OD above the
ground level primer coated and painted with
polyurethane paint with die cast aluminum
embellishments, joints/ column's section etc.
The bottom column shall be integral connection
box having mounting arrangement of One No.
MCB, 4 Way heavy duty connector cover the
same etc. as required with medium Led Hanging
light made out of spun aluminium housing,
minimum 4500 lumens with maximum system
wattage 45 watt Led Mounting on aluminum die
casted heat sink with power Led, minimum
efficacy 100 Lumen per watt with external driver
CCT 5700, CRI > 70, PF>0.90, Operating
Voltage 220-240V AC Painted with PU Paint as
matching of above Pole complete. The LED
driver access should be from top for easy
maintenance LEDs should be provided with non-
yellowing modular secondary lens optics. LED
used shall be SMD type, Life of fixture 50000
hrs, THD< 10%, and Operating Temperature
Range 0 deg C to + 50 deg C, IP66. Built in
Surge Protection of SKV & external surge
protection of 10 kV. LED Driver should be of
Constant current driver to have built-in surge,
open & short circuit protection, Over Voltage
Protection @ 300V+5V, Double Phase Protection
(up to 48 hrs.) and as per requirement and as
per instruction of Engineer Incharge at Site.
28 28 Supply, testing & fixing of LED Rope Light 50 Numbers 10.00 7237.00 72370.00
Meters (Red, Yellow, Blue, Green, White as
required) Waterproof, IP 65 or above as per
instruction of Engineer Incharge at Site.
29 29 Supply and fixing of 12 watt LED Picture light Numbers 10.00 2464.00 24640.00
(31402 Muziris or similar) as per instruction of
Engineer incharge at site.
30 30 Supply, installation, testing & commissioning of Numbers 8.00 11309.00 90472.00
Stationary storage type electric water heater
(Geyser), Digital display, Type:-Vertical,
Capacity (Ltrs):25, Power input: 2000 watt,
Class:-I, Star Rating: 5 Star suitable for
operation on 230 Volts, single phase AC, 50 Hz.
Storage electric water heater shall be complete
in all respect with fittings as per general
technical requirements and as per instruction of
Engineer incharge at site.
31 31 Supply, fixing & testing of OIL FILLED RADIATOR Numbers 7.00 15649.00 109543.00
(Room Heater) HESTIO 9 FIN Wave Fin OFR,
Effective Heating, Inclined Control Panel,
Retractable Wheels, 2400 W as per instruction
of Engineer Incharge at Site.
32 32 Supply, installation, testing & commissioning of Numbers 1.00 100011.00 100011.00
Aquaguard Institutional Water cooler-cum-
Purifier with Storage Capacity 120 Ltrs. & Option
for Cold & Normal Purified Water. a) Approx.
Dimensions : 750 mm (W) x 570 mm (D) x 1350
mm (H) b) Power rating : 850 ± 10% watt c)
Water flow capacity : 80 LPH d)Operating power
supply : 170-260 VAC, 1 ph e)No. of stages for
filter-cum-purifier : 3 nos. f) Storage capacity :
120 Ltr g) Nos. of Faucets : 03 nos. h) Body
material: Front SS 304 and the rest in Pre-
coated steel i) Refrigerant used: Freon 22 or
KATIHAR DIVISION-ELECTRICAL/N F RLY
33 33 Supply, installation, testing & commissioning of Set 1.00 66990.00 66990.00
Inverter of 5 kVA/48 VDC, minimum 21600 VAH
with 04 nos x 120 AH SMF VRLA battery and
trolley as per instruction of Engineer Incharge at
34 34 Supply, fixing & testing of STEELIO ELECTRIC Numbers 8.00 1700.00 13600.00
KETTLE 1 Litre, 1250 W Black / Silver as per
instruction of Engineer Incharge at Site.
35 35 Supply, erection & commissioning of earth spike Numbers 10.00 366.00 3660.00
made of 16 mm dia 1.8 mt long GI rod &
connection metal body with the earth spike rod
by 6 SWG GI earth wire with nut, bolt & washer
36 36 Supply, installation, testing & commissioning of Numbers 3.00 12670.00 38010.00
Onload Changeover Switch, 4 Pole, 100 Amp.,
415 V, 50 Hz, with Sheet Steel Enclosure as per
instruction of Engineer Incharge at Site.
37 37 (a) Supply, installation, testing & commissioning Set 8.00 2005.00 16040.00
of 12 way SPN Distribution Board, Flush/Surface
mounting, IP 43 grade protection with copper
bus bar, fully shrouded neutral bar, earth bar,
cable ties, metal double door as per IS 8623 - III
with supply and fixing of following RCBO/MCB's
as per instruction of Engineer Incharge at Site.
module Conforms to IEC 61009-1
Conforms to IS/IEC 60898 - 1:2002
Conforms to IS/IEC 60898 - 1:2002
41 41 (a) Supply, fabrication, erection, testing, Set 1.00 32916.00 32916.00
commissioning & painting of floor mounted
powder coated cubicle panel board (Modular
look) of suitable size (neither big nor small) ),
outdoor type with double door made of suitable
size MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x
6 mm, 14 SWG MS sheet/Powder coated CRCA
sheet with provision of weather proof,rust
proof,dust proof,water proof having internal
rubber gasket with supply and fixing of following
ACB/MCCB/Bus bar/Meter etc. (Connections to
be made by copper strips, glands should be
provided at cable entry and exit, components
should be compartmentalized, Each
compartment will be provided with the door and
pad locking arrangement. The compartment
illumination lamp with door operated switch
shall be provided for each compartment. Panel
board drawing approval must be obtained with
clear indication of make of items of
Conforms to IS/IEC 60898 - 1:2002
electrolytic grade copper consisting of 4 bars ( 3
Ph and Neutral ) ( Bus bar should have
insulation cover)
47 47 (g) Digital voltmeter (0-500) amps and Digital Set 1.00 5581.00 5581.00
ammeter (0-500) amps with s/switch and CTs
KATIHAR DIVISION-ELECTRICAL/N F RLY
49 49 Laying, commissioning & testing of HT/LT Metre 200.00 55.00 11000.00
XLPE/PVC cable of different sizes partly along
the pole and partly through ground in cable
trench by excavation of ground below 1.5 mt
from ground level with suitable fixing
arrangement by MS clamp of size 50x6 mm and
suitable size nut, bolt. Loading, Unloading &
Carrying of cable to actual work site by
contractor's own arrangement. (Aluminium
Crimping Socket should be provided for each
Cable Termination). (Cable will be supplied by
Item Breakup - 1-SCHEDULE-A (Construction of Office-cum-Barrack at DHR-KGN-MHN)
Supply, wiring, testing & commissioning of Numbers 180.00 concealed point wiring by FR PVC insulated and unsheathed 1.5 sq mm, single core multi strand copper wire with earth continuity wire by PVC insulated and unsheathed 1 sq mm, single core multi strand copper wire concealed on wall through PVC rigid conduit pipe of dia not less than 20 mm dia heavy duty including all types of joints and bends as required, complete with 6 amps flush type controlling modular switch to be mounted on modular GI inner plate and modular mounting frame of suitable module as per requirement complete to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material. (a) FL Point/LED Tube Point/Wall Mount Decorative Light Point/Wall Mounted Bracket Fan Point with c/rose
(b) Lamp Point/Inverter Point with angle holder
(c) Exhaust Fan Point with c/rose
(d) Plug Point 6 amps on board complete
Supply, wiring, testing & commissioning of Numbers c o n c e a l e d plug point on separate board complete with 2 x 6 Amp modular socket and 6/10 amps modular switch to be mounted on modular GI inner plate 6M and 6M modular mounting frame with GI box to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material.
Supply, wiring, testing & commissioning of Numbers concealed 6/16 amps power plug point on separate board complete with modular 16 amps switch (with indicator) and 6/16 amps 3 pin combined shuttered socket to be mounted on modular GI inner plate 4M or suitable size with modular mounting frame to be concealed in wall as per instruction of Engineer Incharge at Site.
Supply, wiring, testing & commissioning of Numbers concealed call bell point wiring by FR-LSH PVC insulated and unsheathed 1.5 sq mm, single core flexible copper wire concealed on wall through PVC rigid conduit pipe of dia not less than 20 mm dia with all types of joints and bends as required complete with 6 amps bell push controlling switch fitted on half flush MS board with hylem sheet top and earth continuity wire by PVC insulated and unsheathed 1 sq mm , single core multi strand copper wire complete to be concealed in wall including supply, fixing, testing & commissioning of call bell "Ding Dong / Multitune door bell" type.
Supply, fixing, connection & testing of indoor Numbers 100.00 LED tube batten with 20 watt LED T8 tubular lamp with extuded aluminium body and PC diffuser complete with inbuilt driver (System wattage-20 Watt, System efficacy> 105 lm/W, Power factor >= 0.90) with suitable fixing arrangement as per instruction of Engineer incharge at site.
Supply and fixing of Wall Mount Decorative Light Numbers Fitting with 1 x 7 Watt LED lamp, E27 (Jaguar JNL-CHR-WLSL55004E27 or similar), Heritage type as per instruction of Engineer Incharge at Site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply and testing of wall mounted bracket fan Numbers 400 mm sweep complete with all accessories to be fixed on wall by suitable fixing arrangement including connection by 2 core, 1.5 sqmm PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable
Supply, fixing & testing of LED retrofit lamp 9 Numbers watt, B-22 cap as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Set Inverter of 5 kVA/48 VDC, minimum 21600 VAH with 04 nos x 120 AH SMF VRLA battery and trolley as per instruction of Engineer Incharge at Site.
Supply, installation, testing & commissioning of Numbers 300 mm sweep (metallic) heavy duty exhaust fan, 1400 RPM complete with fixing on wall by suitable size bolts & nuts grouted on wall as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 2.5 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 4 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 6 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 through PVC rigid conduit pipe/polythene pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 10 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 through PVC rigid conduit pipe/polythene pipe not less than 25 mm dia as per instruction of Engineer incharge at site.
Supply, fixing, testing & commissioning of rigid Metre PVC conduit pipe of 32 mm dia, Medium mechanical strength. The pipe should be fixed with ramp/FOB shed structure at regular interval with clamps as per instruction of Engineer Incharge at Site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, installation, testing and commissioning Numbers of drop down Led decorative light warm white Cast iron based pole of height 3 meter with 45 watt capacity double arm bracket mild steel grooved pipe pole made out of cast iron base 390 mm base dia, Top 83mm OD above the ground level primer coated and painted with polyurethane paint with die cast aluminum embellishments, joints/ column's section etc. The bottom column shall be integral connection box having mounting arrangement of One No. MCB, 4 Way heavy duty connector cover the same etc. as required with medium Led Hanging light made out of spun aluminium housing, minimum 4500 lumens with maximum system wattage 45 watt Led Mounting on aluminum die casted heat sink with power Led, minimum efficacy 100 Lumen per watt with external driver CCT 5700, CRI > 70, PF>0.90, Operating Voltage 220-240V AC Painted with PU Paint as matching of above Pole complete. The LED driver access should be from top for easy maintenance LEDs should be provided with non- yellowing modular secondary lens optics. LED used shall be SMD type, Life of fixture 50000 hrs, THD< 10%, and Operating Temperature Range 0 deg C to + 50 deg C, IP66. Built in Surge Protection of SKV & external surge protection of 10 kV. LED Driver should be of Constant current driver to have built-in surge, open & short circuit protection, Over Voltage Protection @ 300V+5V, Double Phase Protection (up to 48 hrs.) and as per requirement and direction of Railway site engineer in-charge.
Supply, installation, commissioning & testing of Square LED indication name board (Length of board will Foot be as per proportion of letter so that all the 4 side of the board will have extra space) with channel letters with 3.75 ft. in lenght with suitable widen and 4 mm projection size which inside ACP board (Brand- ALUDECOR, category- AL 33 series exterior & thikness-3 mm) with acrylic face on front and having Sumsung 5630 LED's (Shape- Lens type, operating voltage- 12 V DC, carring current-80 mA, power Dissipation- 0.96 watt, working hours-50000, case material- ABS, protection-IP68) inside for illumination letters in English, Hindi, Bengali or regional language complete with all materials including provision of erection structure made of MS angle/channel/flat duly painted with aluminium paint over a coat of red oxide primer with CC foundation (1:3:6) of cement, sand and stone chips as required at site and as per instruction of Egnineer incharge at site.
Supply, commissioning of 10 watt LED Bollard fitting (Garden light), IP66, pressure die cast powder coated housing, wiring by 2.5 sq mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts Conforming to IS: 694to be drawn through Rigid PVC conduit pipe not less than 20 mm dia along with 1 sq mm single core FR PVC insulated and unsheathed copper wire for earth continuity as per instruction of Engineer incharge at site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, installation, testing & commissioning of Numbers 100 watt LED flood light luminaires complete with pressure die cast aluminium housing, IP 65, Luminous efficacy 100 lm/watt with heat sink feature, surge protection etc. including wire connection as per instruction of Engineer Incharge at Site.
Supply, installation, testing & commissioning of Numbers Stationary storage type electric water heater (Geyser), Digital display, Type:-Vertical, Capacity (Ltrs):25, Power input: 2000 watt, Class:-I, Star Rating: 5 Star suitable for operation on 230 Volts, single phase AC, 50 Hz. Storage electric water heater shall be complete in all respect with fittings as per general technical requirements and as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers Aquaguard Institutional Water cooler-cum- Purifier with Storage Capacity 120 Ltrs. & Option for Cold & Normal Purified Water. (a) Approx. Dimensions : 750 mm (W) x 570 mm (D) x 1350 mm (H) (b) Power rating : 850 ± 10% watt (c) Water flow capacity : 80 LPH (d)Operating power supply : 170-260 VAC, 1 ph (e)No. of stages for filter-cum-purifier : 3 nos. (f) Storage capacity : 120 Ltr (g) Nos. of Faucets : 03 nos. (h) Body material: Front SS 304 and the rest in Pre- coated steel (i) Refrigerant used: Freon 22 or latest"
Supply, fixing, testing & commissioning of IP Numbers 66/67 thermoplastic cable junction box / loop box of size (210 x 310 x 116) mm with knockouts & 04 nos terminals as per instruction of Engineer incharge at site.
Supply, erection & commissioning of earth spike Numbers made of 16 mm dia 1.8 mt long GI rod & connection metal body with the earth spike rod by 6 SWG GI earth wire with nut, bolt & washer etc. as per instruction of Engineer Incharge at Site.
(a) Supply, installation, testing & commissioning Set of 4 way VTPN MCCB DB (MCCB+12 modules) with IP 43 grade protection, metal door with wire sets, busbar, earth bar, blanking plates, cable ties etc with supply and fixing of following MCCB/MCB as per instruction of Engineer incharge at site.
(b) MCCB FP 125 amps, 36 kA, Ics=100% Icu
(c) MCB DP 63 amps, C-curve, 2 module, 10 kA, Numbers conforms to IS/IEC 60898:2002
(d) MCB DP 40 amps, 2 module, 10 kA, Numbers Conforms to IS/IEC 60898 - 1:2002
(a) Supply, fixing & Commissioning of 8 way SPN Set Distribution Board, Flush/Surface mounting, IP 43 grade protection with copper bus bar, fully shrouded neutral bar, earth bar, cable ties, metal double door as per IS 8623 - III as per instruction of Engineer Incharge at Site.
(b) RCBO DP 63 Amp, 100 mA senstivity, 4 Numbers module Conforms to IEC 61009-1
(c) MCB DP 63 amps, C-curve, 2 module, 10 kA, Numbers conforms to IS/IEC 60898:2002
(d) MCB SP 6-32 amps, 1 module, 10 kA, C-curve Numbers Conforms to IS/IEC 60898 - 1:2002 KATIHAR DIVISION-ELECTRICAL/N F RLY
Laying, commissioning & testing of HT/LT Metre XLPE/PVC cable of different sizes partly along the pole and partly through ground in cable trench by excavation of ground below 1.5 mt from ground level with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt. Loading, Unloading & Carrying of cable to actual work site by contractor's own arrangement. (Aluminium Crimping Socket should be provided for each Cable Termination). (Cable will be supplied by Railway) Total 2178323.00 Schedule 2-SCHEDULE-B (UPGRADATION OF OFFICER REST HOUSE AT DARJEELING IN KATIHAR
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
NITforORHDJ.pdf
ATTACHMENT
GCC 2022 with ACS
ATTACHMENT
GCCApril-2022PDFwithallACS.pdf
ATTACHMENT
Download all tender documents and submit your bid