| Sl No | Description | Qty | Unit | u and v engineers and consultants L1 | R D Bansal L2 | Raman Electric Trading Co L4 | MM Engineers L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep in loose / soft soil and getting out for under ground cable / errection of poles, stays etc complete all as specified and directed. | 213 | CUBIC METRE | 80 ₹17,040 | 100 ₹21,300 | 90 ₹19,170 | 125 ₹26,625 |
| 2.00 | Excavation in trenches not exceeding 1.5 metre wide and exceeding 1.5 metre deep but not exceeding 3.0metre deep in loose / soft soil and getting out for under ground cable / errection of poles stays etc complete all as specified and directed. | 2.5 | CUBIC METRE | 400 ₹1,000 | 200 ₹500 | 100 ₹250 | 200 ₹500 |
| 3.00 | Returning filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed. | 126 | CUBIC METRE | 40 ₹5,040 | 20 ₹2,520 | 20 ₹2,520 | 5 ₹630 |
| 4.00 | Removal of excavated soil to a distance not exceeding 50 Mtr depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and directed by Engineer-in-Charge | 89.5 | CUBIC METRE | 20 ₹1,790 | 30 ₹2,685 | 20 ₹1,790 | 5 ₹447.5 |
| 5.00 | Material and labour for Sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and as directed.
Note:- Punned thickness 18cm shall be measured for payment purposes. | 61 | CUBIC METRE | 220 ₹13,420 | 300 ₹18,300 | 300 ₹18,300 | 400 ₹24,400 |
| 6.00 | Supply and laying of un-reinforced precast concrete cable cover ,class HV, type-1 size 300X180X40mm complete all as specified and directed. | 700 | EACH | 18 ₹12,600 | 18 ₹12,600 | 18 ₹12,600 | 22 ₹15,400 |
| 7.00 | Supply and lay bricks, common burnt clay, sub class "B', old size, laid in vertical direction to cable as cable protection complete all as specified and as directed. | 6 | PER 1000 NOS | 3,500 ₹21,000 | 3,500 ₹21,000 | 3,500 ₹21,000 | 4,500 ₹27,000 |
| 8.00 | Material and labour of PCC 1:4:8 Type D-2 using 40 mm graded aggregate for bottom of Pit for bed concrete below base plat of steel tubular poles including necessary frame work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site by Engr-in-Charge. | 1.5 | CUBIC METRE | 1,800 ₹2,700 | 2,000 ₹3,000 | 1,000 ₹1,500 | 2,000 ₹3,000 |
| 9.00 | Material and labour of PCC 1:3:6 (nominal mix) type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed. | 5.5 | CUBIC METRE | 1,800 ₹9,900 | 2,200 ₹12,100 | 1,000 ₹5,500 | 2,200 ₹12,100 |
| 10.00 | Material and labour of PCC 1:2:4 Type B-1 using 20 mm graded aggregate for coping of poles including necessary farm work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site. | 0.8 | CUBIC METRE | 2,500 ₹2,000 | 2,500 ₹2,000 | 1,000 ₹800 | 2,400 ₹1,920 |
Tender Value
₹25.9 L
EMD Value
₹52,000
Closing Date
6 Apr 2026, 6:00 pmClosed
CWE Ambala
Headquarter Commander Works Engineer Ambala Mansfield Road Ambala Cantt
CA NO CWE/AMB/UTILITY-82 OF 2025-26 PROVN OF INDEPENDENT FEEDER EXTERNAL SUPPLY ALONGWITH CONNECTED ITEMS FOR ECHS POLYCLINIC AMBALA UNDER GE(UTILITY) AMBALA CANTT
2026_MES_755256_1
CWE/AMB/UTILITY-82 OF 2025-26
Open Tender
Electrical and Maintenance Works
150 days
Ambala Cantt
All as per tender documents
9 documents required · 9 mandatory
₹500
Yes
GE(Utility) Ambala
₹52,000
Yes
12 May 2026
9 Mar 2026
8 Apr 2026
9 Mar 2026
6 Apr 2026
24 Mar 2026
9 Mar 2026 - 19 Mar 2026
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep in loose / soft soil and getting out for under ground cable / errection of poles, stays etc complete all as specified and directed.
Excavation in trenches not exceeding 1.5 metre wide and exceeding 1.5 metre deep but not exceeding 3.0metre deep in loose / soft soil and getting out for under ground cable / errection of poles stays etc complete all as specified and directed.
Returning filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed.
Removal of excavated soil to a distance not exceeding 50 Mtr depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and directed by Engineer-in-Charge
Material and labour for Sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and as directed. Note:- Punned thickness 18cm shall be measured for payment purposes.
Supply and laying of un-reinforced precast concrete cable cover ,class HV, type-1 size 300X180X40mm complete all as specified and directed.
Supply and lay bricks, common burnt clay, sub class "B', old size, laid in vertical direction to cable as cable protection complete all as specified and as directed.
Material and labour of PCC 1:4:8 Type D-2 using 40 mm graded aggregate for bottom of Pit for bed concrete below base plat of steel tubular poles including necessary frame work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site by Engr-in-Charge.
Material and labour of PCC 1:3:6 (nominal mix) type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed.
Material and labour of PCC 1:2:4 Type B-1 using 20 mm graded aggregate for coping of poles including necessary farm work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site.
Supply, fix and erection of steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31, 09 meter long, providing synthetic enamel aluminium paint over one coat of red oxide and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr including 2 bands of radium tape of 2' width green & red colour above the coping of pole starting with black strip complete all as specified and directed by Engr-in-charge. Note (i) Earth work and PCC shall be measured and paid seperately. (ii) Street light pole No 1 to 06 will be printed on each pole without any extra cost with hole in poles for passing 3 core PVC cable for Street lights
Supply, fixing and transportation upto site of work and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 metres long) and including marking alternate 05 Nos white and black strip 30cm height with two coats of synthetic enamel paint and 2 bands of radium tape of 2" width green & red colour complete all as specified and directed by Engr-in-charge. Note Earth work and PCC shall be measured and paid seperately
Supplying and laying, connecting & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 11000 Volts grade, cross sectional area 95 Sqmm 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part - 2 for insulation and for conductors Class 2 to IS 8130 - 84, in trenches, floors, ducts passing through pipe for road crossing etc, complete all as specified and directed. (Note : Excavation, earth work, brick protection, sand cushioning and GI pipe etc shall be measured & paid for separately).
Supply and fixing, laying, connecting and testing in XPLE armoured cable underground insulated and overall sheathed with aluminium conductor of size 150 Sqmm 3.5 core heavy duty 1100 volts grade laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on wall etc. Note : (i) Earth work, sand, brick, removing, returning filling will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments , machinery or tools if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per item ser No 14 here-in-before but for 95 Sqmm 3.5 core complete all as specified and directed.
All as per Item ser No 14 here-in-before but of size 50 Sqmm 3.5 core complete all as specified and directed.
All as per Item ser No 14 here-in-before but of size 35 Sqmm 3.5 core complete all as specified and directed.
All as per item ser No 14 here-in-before but of size 25 Sqmm 4 core complete all as specified and directed.
All as per item ser No 14 here-in-before but of size 10 Sqmm 4 core complete all as specified and directed.
Supplying and fixing of light grade galvanised mild steel pipe 100mm bore with all fittings, laid under roads, drain, paths, fixed to poles/walls with suitable mild steel clamps , bolts , nuts and washers complete all as specified and directed. Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule
All as per Item No 20 here-in-before but of size 50 mm bore complete all as specified and directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique or manual boring and necessary machine including HDPE pipe of 50mm to 150 mm dia suitable for 0.4 mpa working pressure.
Supply and fixing of cable end jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
Supply and fixing for outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 35-50 Sqmm 3.5 core complete all as specified and directed.
All as per Item No 24 here-in-before but for cable of size 95-150 sq mm 3.5 core complete all as specified and directed.
Supply, installation, testing and commissioning of step down transformer out door type complete with standard fittings and accessories, HT 11 KV 3 Phase, LT 433 Volt, 3 Phase 4 wire with off load tap changer on primary side to carry secondary voltage tapping range + 7.5% with tappings at every steps 2.5 % all as per IS 1180 Part-I (2014) , With Latest Amendment No 1, 2, 3 & 4 of Energy Efficiency Level -2) EEL-2, for Transformer manufacturing of capacity 200 KVA, copper wound, oil cooling with fins, vector group : DYn 11, including initial oil filling (oil confirming to IS 335 and ISI Mark) complete all as specified including the following accessories :- (a) Three Nos porcelain bushing HT 11 KV with brass bushing rods, nuts, bolts & washers etc inside cable end box. (b) One cable box LV side consisting of 4 Nos porcelain with brass bushing rods complete with nuts and washers suitable for runs of 3.5 core LT UG cable. (c) Oil conservator with filler type drain valve and oil level gauge. (d) Dehydrating breather with first fill of dehydrating agent. (e) Explosion vents. (f) Thermometer pocket on tank cover.(g) One No 100mm dia, dial type thermometer vapour pressure type having range 0 to 120 degree centigrade. (h) Rating plate and terminal marking plate. (j) Earthing arrangement. (k) Oil level gauge. (l) Oil drain filter valve. (m) Oil drain valve. (n) Lifting hook. (o) Oil conservator with filling hole and cap. (p) Air relief valve plug. (q) Four plate solid cast steel detachable rollers. (r) Earth bushing for neutral outside the cable box for providing independent earthing for neutral. (s) Necessary channel on foundation for fixing the transformer with joint and stopper. (t) Danger notice plate provide to transformer. Note :- The transformer should be Energy Efficiency Level -2 (Energy conservation Binary Corps) for which necessasry test certificate to be produced by contractor from manufacturer of the trasformer."
Supply, installation and testing of LT Panel of size (1.5m X1.2m X0.55m) , weather proof, outdoor type,degree of protection IP-56, having thickness of 3.15mm and inner shell made out of 2mm thick CRCA sheet and MS angle size 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front openable double door system and cable alley (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction of LT panel shall be tested from CPRI type test for 4000 Amp with breaking capacity not less than 65 KA and IP 56 as confirming to IS:61439/2011 Part-1 and part -2 type test certificate with switchgears with not less than IP-65 and short circuit test 4000 Amps 65 KA comprising of the following - (a) Al busbar of capacity 500 Amps - Set of four. (b) ON Load Change over Switch 200 A , 415 volts - 01 No (Incoming) and common connected with busbar of O/G MCCBs. Make: Havells / Indo Asian / L&T/ Siemens or equivalent (c) Incoming MCCB 315 Amps, 4P, 415V, 36 KA - 01 No. with magnetic thermal release, adjustable type. (d) Outgoing MCCB 250 Amps, 4P, 415V, 25 KA - 01 Nos. (e) Outgoing MCCB 200 Amps, 4P, 415V, 25 KA - 01 Nos. (f) Outgoing MCCB 63 Amps, 4P, 415V,16 KA - 02 Nos. (one standby) (g) Indicator lamps RYB LED type - 01 Set of three. (h) Multi function meter Make: AE for measuring KWH, PF, Voltage, Ampere, Freq incl CT coils as reqd 03 Nos. (j) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves etc complete are included in quoted rates.
Supply, installing, testing & commissioning of outdoor type cubical panel board of size 1.2mX1.2mX.5m, outer shell made out of 3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able with arrangement of pad locking on both doors incl 2 no. of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, incl Al bus bar of 500 A , tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general constructionconfirming to IS:61439/2011 Part-1 and part -2 type test certificate with switchgears with not less than IP-65 and short circuit test 4000 Amps 65 KA comprising of the following - (a) Aluminium bus bar of capacity 300 Amps for 3 phase with neutral - one job (b) Incoming MCCB 415 V, 200A 4 pole, breaking capacity 25 KA adjustable type - 01 Nos. (c) ON Load Change over Switch 100 A , 415 volts - 01 No (out going) and common connected with busbar of O/G MCCBs. Make: Havells / Indo Asian / L&T/ Siemens or equivalent. (d) Outgoing MCCB 415 V, 100A 4 pole, breaking capacity 25 KA adjustable type - 02 Nos. (one standby) (e) Outgoing MCCB 415 V, 63A 4 pole, breaking capacity 16 KA -03 Nos (one standby) (f) Indicator lamps RYB LED type - 01 Set of three. (g) Multi function meter Make: AE for measuring KWH, PF, Voltage, Ampere, Freq incl CT coils as reqd 03 Nos. (h) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, sleeves etc complete are included in quoted rates.
Note for Ser No 27 & 28 :- (i) The quoted rate shall include minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLSH cable conforming to IS-694. (iii) Panel drawing shall be got approved from Engr-in-Charge/GE before placing of order. (iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) Cable will be entered in panels through gland. (v) Cost of marking description incl CA No & year of manufacture and matter on the front door as specified and directed by Engr-in-Charge is incl in quoted rate.
Supply & fixing stay assembly complete with all accessories such as stay plate 300mmx300mmx6mm, stay rod 20 mm dia and 215cm long threaded end with nut with nuts including 14mm dia GI stay bow. turn buckle, etc. complete, all as shown in Electrical plate No 1 of SSR part I 2009 complete all as specified and as directed. Note- (i) loop type insulator, stay clamps, excavation and concrete measured separately.
Material and labour of Loop insulator porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mm x 140mm, clearance of hole 25.5 mm, Complete all as specified and directed.
Material and labour of danger notice plate 1.60 mm thick of size 25x20 cm , mild steel sheet, vitreous enameled red coulor with letters, figures and conventional skull and bones in signal white colour and fixed with M.S. clamps, bolts and nuts of approved size for HT, complete, all as specified and as directed.
Material and labour of cross arms, clamps, bracing, etc. of any section from pole including nuts, bolts, washers, including cutting of bolts (slag bolts) if required complete and material and labour for cross arm bracing supports, clamp and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling hole for bolts in any shape or size as indicated or directed including two coats of aluminium paint over a coat of red oxide, complete, all as specified and as directed.
Material and labour for anti climbing device, spikes type fabricated out of MS bars (round,square and flat) including nuts, bolts, washers and welding in two halves, made to shape to suit the cross section of the pole complete all as specified and directed.
Supply and fixing pin type, porcelain, vitreous, white or brown or green insulators,11000 volts grade of 150 mm dia ,150 mm height including one galvanized mild steel spindle, two galvanised iron washers and one galvanized iron nuts complete all as specified and as directed.
Material and labour for disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified and directed.
Supply, Installationg, testing and commissioning of air breaker gang operated device triple pole switch ( GOD) outdoor type, vertical mounting type of capacity 200 Amp with drop out fuse consisting 12 insulators ISI marked mechanically operated mounted on insulator and frame work with operating GI rods and mechanical work from ground level with 02 Nos clamp hook for protection of operating GI pipe including locking arrangement including Godrej pad lock with two keys complete with fuse carried and HT fuse element having upto 200 Amp rating suitable for HT 11 KV 50 HZ AC supply including necessary electric connection complete all as specified and directed .
Supply and fixing of lightning arrester, expulsion type, suitable for HT 11000 volts, with all fittings, trasmission class, discharge capacity 65 KA, including connecting with HT line complete all as specified and as directed.
Material and labour for earthing complete with galvanised earth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 32x6 mm GI strip earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore (medium grade) and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe (medium grade) for watering and 40mm bore GI protection pipe medium grade, funnel, wire mesh, cast iron cover and frame etc, complete, all as specified or indicated and as directed including testing on completion complete all as specified and directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2 Ώ the earthing will be redone at no extra cost
All as per item ser No 39 here in before but for connected to galvanised earth lead wire of 4.0 mm dia by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn through 15 mm bore GI pipe medium grade for protection of GI earth lead wire including 20mm bore GI pipe medium grade for watering GI funnel complete all as specified and directed.
Supply, fixing or passing through PVC conduit pipe of 1100 volts grade heavy duty, PVC insulated round 3 core 1.5 sqmm copper cable with PVC conduit pipe fixed with clamp & nuts bolts including electrical connection suitable size of lugs, complete all as specified and as directed.
Supply & fixing of LED street light fitting 60 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover/ toughened glass having TOP Opening separate driver compartment with IP 66 protection and impact resistance of IK07 consisting of 10-15 numbers of LEDs with sealed toughened glass cover, 5700K, LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distribution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirming the safety test as per IS 15885 part-2 from auth labs : LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl make proper connection of light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified and as directed.
Supply and fixing of fabrication of Kiosk box made out of fibre material complete with TPN ,aluminium bus and suitable for one number MCB (SP) including one No MCB (SP) 6 Amps 240 volts with glands for incoming & out going cable including fixing of flat iron clamps of size 20x4mm on PCC/Steel tubular pole complete all as specified and as directed.
Supply & Fixing of bracket made out of GI tubing single piece bended at proper angle of size 40mm dia, light grade 1.5 mtr long including painting with aluminium paint over one coat of red oxide primer to the bracket of street light fitting all as specified and as directed.
Supply & Fixing of MS clamp suitable for holding street light bracket on steel/PCC pole made out of 40 mm x6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia -3 Nos with flat washer 3mm thick -02 No for each including painting with aluminium paint over one coat of red oxide primer to the M.S clamps complete all as specified and as directed.
Supply & fixing of Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). Three phase, 25 Amps per phase, MCB rating 32Amp, max load 8-12 kw incl circuit copper wire 10 sq.mm. Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS). Madel : Swadeep-02EC-8kW3P-VMS complete all as specified and directed. Note (i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 yers . (iii) The test certificate and warranty cirtificate must be provided by supplier.(iv) Cost of marking description on the box is incl quoted rate.
Supply and fixing of off load change over switch with sheet steel Enclosure 415 V, 4 pole, 160 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and as directed.
supply and fixing of Retro reflective sign board print both side of size 600 mm x 750 mm made of ACP sheet of 3mm thick ACP sheet shall be fixed on MS frame with legs of MS angle section 35mm X 35mm X 5mm grouted in PCC 1:3:6 type C-1, 800mm above the ground level and 600mm below the ground level. The background of board to be provided with red colour, letters and border with white retro reflective tape. Same description shall be mentioned on both sides of ACP sheet complete all as specified and directed. NOTE:- (i) Excavation, earth work, PCC, nuts, bolts, fasners, paint on MS frame and legs shall be included in quoted rates by contractor. (ii) The size of letters and description shall be all as per sample approved by Engr-in-Charge.
Supply and fixing of cable gland as per cable size in the LT panels complete all as specified and as directed.
Supply and fix of sheet metal enclosure Vertical triple pole & neutral (VTPN) with MCCB TPN 125 Amp for 415 volts 4 way with 200 Amp rated bus bar flush /surface mounting double door duly grouted in solid block wall or on wooden board in and including lugs/thimbles duly crimped for connection including making smooth the disturbed surface with PCC 1:3:6 complete all as specified and directed.
Supply and fix of MCB SP 6-32 Amps, 240 volt,10 KA 'C' curve complete all as specified and directed.
Supply and fixing single pole and neutral enclosure with a two pin and earth plug and socket 20 Amp complete with and including one single pole MCB. 20 Amp complete all as specified and directed.
Supply and fixing of sub main wiring with two run of 6 sqmm PVC insulated , unsheathed cable FRLS-H,1100 volt grade ISI marked multi stranded copper conductor with one run of 6 sqmm PVC insulated , unsheathed cable FRLS-H, 1100 volt grade ISI marked multi stranded copper conductor connected to common earth dolly including capping & casing or concealed on wall/ceiling in PVC conduit medium grade not less than 25 mm dia ISI marked of adequate size for housing the wires complete all as specified . Note: (i) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB (ii) For the purpose of payment two runs of 6 sqmm conductors and one run of 6 sqmm conductor with conduit shall be measured as one length.
Supply and fixing of sub main wiring with two run of 4 sqmm PVC insulated , unsheathed cable FRLS-H,1100 volt grade ISI marked multi stranded copper conductor with one run of 4 sqmm PVC insulated , unsheathed cable FRLS-H, 1100 volt grade ISI marked multi stranded copper conductor connected to common earth dolly including capping & casing or concealed on wall/ceiling in PVC conduit medium grade not less than 25 mm dia ISI marked of adequate size for housing the wires complete all as specified . Note: (i) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB (ii) For the purpose of payment two runs of 4 sqmm conductors and one run of 4 sqmm conductor with conduit shall be measured as one length.
Material and labour for hardcore broken stone or boulders filling of gauge not exceeding 63 mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and as directed.
Excavating in post holes each n.exc 0.5 cum getting out, in soft/loose soil complete all as specified and directed.
Material and labour for cement concrete 1:3:6 type c-2 (40mm graded aggregate) as in post holes complete all as specified and directed.
Supply and fixing mild; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe 290 Gde E-165. complete all as specified and directed.
Material and labour for mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, but lenth of bolt exc 5cm and n exc 10 cm long and diameter of neck 10mm complete all as specified and directed.
Supply and fixing chain link fencing size 100mm x 100mm (3.8mm thick dia wire) including line wires, any mesh, any type of standards, rails, straining bolts, etc. including provision of binding wire complete all as specified and directed.
Supply and fixing mild steel rounded bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
Material and labour for two coats of synthetic enemel paints on new steel Surfaces exc 10cm girth over a coat of red oxide when unconnected with other painting or when painted in a different tint complete all as specified and directed.
Material and labour for two coats of synthetic enemel paints on steel Surfaces exc 10cm girth over a coat of red oxide complete all as specified and directed.
Material and labour for Brick work with subclass 'B' bricks, straight or curved on plan exc 6m mean radiusbuilt in CM 1:6 complete all as specified and directed.
Material and labour for PCC 1:2:4 type B0(12.50mm aggraded aggregate ) as in coping etc incl form work complete all as specified and directed.
Material and labour for rendering 15mm thick on fair faces of brick work or concrete surfaces in CM 1:4 finishing the surface fair and even smooth without using extra cement all as specified as directed.
Material and labour for for preparation and applying three coats of white wash on new plastered surface of wall complete all as specified and directed.
Material and labour for hardcore broken stone boulder hand packing (any thickness) at back of walls over arches etc. and raising (or lowering) to the required level all as specified as directed.
Material and labour for 100 mm thick PCC 1:2:4 type B1(20mm aggraded aggregate ) finishing cement concrete surface even and smooth with using extra cement all as specified as directed.
Material and labour for mild steel TMT bars 10mm dia and over, cut to length, bent to shape required, including cranking bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.13 MB
BOQ_846400.xls
BOQ • 0.40 MB
TenderU82.pdf
Tender Documents • 0.52 MB
TenderU82Rev.pdf
PDF • 0.53 MB
Download all tender documents and submit your bid