Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.4 LAccepted-AOC HOSUE NO 202 NEW RAM VIHAR COLONY PINTO PARK MORAR GWALIOR 474005 MP | GWALIOR | MADHYA PRADESH | 474005 | L1 | Accepted-AOC Being L1 and reasonable | |
| 2 | L2₹34.3 L+₹2.4 L (7.63%)Rejected-Finance | L2 | Rejected-Finance Being other than L1 | |
| 3 | L3₹41.8 L+₹9.9 L (30.9%)Rejected-Finance | L3 | Rejected-Finance Being other than L1 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
29 Jul 2023, 6:00 pmClosed
GE Pithoragarh
GE Pithoragarh Post - Bharkatiya Pithoragarh - 262520
REPAIR/MAINT OF LT SWITCHGEAR, SERVO VOLTAGE STABILIZERS, EM INSTALLATIONS AND CONNECTED ITEMS OF WORKS AT MIL STN PITHORAGARH
2023_MES_607304_1
8533/PGH/E8
Open Tender
Civil Works
Item Rate
240 days
Pithoragarh
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE Pithoragarh
₹90,000
Yes
17 Jan 2024
30 Jun 2023
5 Aug 2023
30 Jun 2023
29 Jul 2023
15 Jul 2023
1 Jul 2023 - 7 Jul 2023
Amount
DESCRIPTION OF ITEMS
M&L for Repairs & overhauling to LT ACBs of capacity (400 A to 800 A) of any make by removing out the breaker from the respective panels after taking proper electric shut down & disconnecting the breaker, checking it thoroughly for the defects & tripping system of the ACB and rectifying them, lubrication of moving contacts, overhauling of the ACB, replacement of wornout minor spares like springs, washers, levers, nuts & bolts etc reassembling , re-installation ,testing & commissioning of ACB complete and replacement of unserviceable parts all as directed. Note :(i) Cost of lubricants, cleaning agents, testing tools and minor spares shall be deemed to be including in quoted rates
Supply only in replacement of Moving Arcing contacts and adjust the contact pressure of LT ACB of any make capacity (400 A to 800 A) complete all as specified and directed.
Supply only in replacement of fixed Arcing contact and adjust the contact pressure of LT ACB of any make capacity (400 A to 800 A) complete all as specified and directed.
Supply only in replacement of main shaft assembly with crank & cam spacer of existing capacity (630/800 Amp) LT ACB of existing make & model and testing for proper operation complete all as directed.
Supply only in replacement of Trip coil of LT ACB of capacity (400 A to 800 A) complete all as specified and directed.
M&L for grouting of LT/APFC Panel by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type B-1 with 20mm graded stone aggregate.including shifting of existing LT/APFC panel with disconeection of existing cables and reconnecting it after grouting of panel complete all as specified and directed.
M&L for Repairs & overhauling to LT APFC Panel of capacity 30 KVAr to 200 KVAr of any make by checking all the parts & accessories of respective panels & after taking proper electric shut down & disconnecting the APFC Panel from mains, checking it thoroughly for the defects & tripping system and serviceability of all MPP capacitors 6/8/10 stage relay settings of the APFC panels and rectifing them, replacement of U/s capacitors ,wornout minor spares like springs, washers, levers, nuts & bolts etc reassembling , re-installation ,testing & commissioning of APFC apnels complete and replacement of unserviceable parts all as directed. Note :(i) Cost of capacitors , Relay , MCBs,contactors,will be measured & paid separatley under relevant items. (ii) Cost of lubricants, cleaning agents, testing tools and minor spares shall be deemed to be including in quoted rates.
S & F in replacement MCB Tripple pole of capacity 20 Amp for suitable for existing APFC Panel contactor/capacitor complete all as specified and directed. Note : Necessary addition /altration required to adjust MCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.
S & F in replacement APFC Panel Relay micro processor based of 6/8/10 stage suitable for switching of APFC Panel contactor/capacitor complete all as specified and directed. Note : Necessary addition /alteration required to adjust MCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.
S & F in replacement standard duty resin filled capacitor MPP type 440 V, 3 phase 5 KVAr complete all as specified and directed. Note : Necessary addition /alteration required to adjust Capacitors in the panel shall be done by the contractor and no extra payment will be made to the contractor.
All as per Item No.6 above but of 7.5 KVAr complete all as specified and directed.
All as per Item No.6 above but of 8.5 KVAr complete all as specified and directed.
All as per Item No.6 above but of 10 KVAr complete all as specified and directed.
All as per Item No.6 above but of 15 KVAr complete all as specified and directed.
All as per Item No.6 above but of 20 KVAr complete all as specified and directed.
All as per Item No.6 above but of 30 KVAr complete all as specified and directed.
S & F in replacement contactor 440 V, 3 phase suitable for capacitor upto 8.5 KVAR complete all as specified and directed. Note : Necessary addition /altration required to adjust Contactors in the panel shall be done by the contractor and no extra payment will be made to the contractor.
All as per Item No.13 above but of 10 KVAr complete all as specified and directed.
All as per Item No.13 above but of 15 KVAr complete all as specified and directed.
Supply and fix in replacement copper bus bar in the panel of exsiting size and capacity for phase and neutral with heat shrinkable including PVC sleeves in different colour codes for phase indication all as per directed.
All as per item No 16.00 above but aluminium bus bar complete all as specified and directed.
S & F in replacement LED type phase indication lamp of Red /blue/Green colour for phase indication in existing panels complete all as specified and directed.
All as per item No 19 Above but (VSS) for checking of line voltage in RY, YB, BR complete all as specified and directed.
S& F in replacement Digital volt meter 0 to 500 volt complete all as specified and directed.
S& F in replacement Digital Ammeter 0 to 800 Amp with CT of suitable ratio complete all as specified and directed.
S& F in replacement Digital Multi function meter complete all as specified and as directed.
S&F in replacement of Aluminium Lugs/connectors of size 16 sqmm complete all as specified and directed.
S&F in replacement of Aluminium Lugs/connectors of size 25 sqmm complete all as specified and directed.
S&F in replacement of Aluminium Lugs/connectors of size 35 sqmm complete all as specified and directed.
S&F in replacement of Aluminium Lugs/connectors of size 50 sqmm complete all as specified and directed.
S&F in replacement of Aluminium Lugs/connectors of size 70 sqmm complete all as specified and directed.
S&F in replacement of Aluminium Lugs/connectors of size 95 sqmm complete all as specified and directed.
S&F in replacement of Aluminium Lugs/connectors of size 120 sqmm complete all as specified and directed.
S&F in replacement of Aluminium Lugs/connectors of size 150 sqmm complete all as specified and directed.
M&L for preparing old painted surface of panel board by cleaning removing of the old paint by scracthing with wire bursh/sand paper etc and including denting/patching of broken/rusted surfaces etc and apply one coat of synthetic enamel paint by spray painting on inside/outside surface of panel,all as specified and directed.
S&f in repairs micro prismatic reflective sheet, min 2.5 cm wide, with adhesive base for direct fixing on steel tubular/PCC pole without nail or any other fixing material at suitable height, in Red/ White/Yellow colour complete all as directed.
S&F of PVC insulating tape roll of 10 mtr length and 15 mm wide for cable insulation and joints of cable & connectors complete all as directed.
M&L in replacement for fabrication of door/surfaces of LT panel indoor/outdoor as per existing size / thickness/shape and fitted in the panel with door handle, formed gasket around doors, lock insets, earthing strips, door stay, hinges,rivets etc. including two coat of synthetic enamel paint by spray painting on inside/outside surface of panel,all as specified and directed
S & F in replacement MCCB 415 Volts 4 pole 400 Amps 50 Hz 50 KA of existing make model and type alonwith spreader terminal with adjustable thermal setting including lugs/thimbles of suitable size in existing panels complete all as specified and directed.Note : Necessary addition /alteration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.
All as per Item No.36 above but of MCCB 315 Amps 4 pole 50 Hz 415 V with rupturing capacity 36 KA complete all as specified and directed.
All as per Item No.36 above but of MCCB 250 Amps 4 pole 50 Hz 415 V with rupturing capacity 36 KA complete all as specified and directed.
All as per Item No.36 above but of MCCB 200 Amps 4 pole 50 Hz 415 V with rupturing capacity 36 KA complete all as specified and directed.
All as per Item No.36 above but of MCCB 100 Amps 4 pole 50 Hz 415 V with rupturing capacity 25 KA complete all as specified and directed.
All as per Item No.36 above but of MCCB 63 Amps 3 pole 50 Hz 415 V with rupturing capacity 16 KA complete all as specified and directed.
S & F in replacement of MCB TPN 63 Amps 50 Hz 415 V complete all as directed.
M & L in replacement for fabrication of MS busbar chamber of nominal dimension 900 mm x 600 mm x 300 mm duly provided with aluminimum busbar of size 50 mm x 6mm fixed on porcelain insulators TPN type out door weather/vermin proof with both way opening duly provided with neoprene rubber gasket along the doors openings pedestal type duly painted powder coated on CRCA steel sheet encloser with one No incommer MCCB 200 Amp 25 KA complete with grouting of bus bar chamber in ground by using angle iron frame of size 40mm x 40mm x 5mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate. all as sepcified and directed incl making connection /thimbles etc complete.
All as per srl item No 43 here-in-before but of size 600 mm x 600 mm x 300 mm and without MCCB complete all as specified and directed.
S&F in replacement of OFFLOAD Change over switch enclosed in sheet metal enclosure box complete with all accessories like nut bolts,connector etc of capacity 200 Amp 4 pole 3 phase 415 Volts supply with side handle operated all as directed
All as per Item No.45 above but of capacity 100 Amps 4 pole 50 Hz 415 V all as directed.
M& L in replacement for Panel Wiring in relacement with suitable size PVC insulated PVC sheathed 1100 volts grade FRLS type with copper conductor multistranded cable with lugs on both ends of cable and proper insulation from PVC insulating tape on open joints on incoming / outgoing XLPE UG cable complete all as specified & directed.
S&F in replacement for contactor MNX 40 of existing make/model suitable for street light timer including dismantling existing un serviceable from the timer assembly and making reconnection connection all as specified and directed.
M& L for ,servicing and complete overhauling of servo stablizer of capacity 160 KVA to 200 KVA including disassembling of operating mechanism parts, well cleaning with petrol & CRC-226 and replacing wornout parts reassembling of parts including disconnection,connection, well cleaning the complete stablizer, oil tank, connection plate,de-carbonizing all joints, metal parts and making servo stablizer operating in manual and electric mode including all routine testing ,calibration and replacement of unserviceable parts complete all as spd and directed. Note: (a) Any rewiring/changing of cable required for functioning of stablizer is included in the quoted rate. (b) Major Spares to be paid separately as given below.
Supply only in replacement Electronic cards including replacement of all worn - out parts like IC's , regulators, condensers, Triac, Transistors, transformers suitable for 200 KVA servo voltage stabilizer complete all as specified and directed.
Supply only in replacement Micro switch complete all as specified and directed.
Supply only in replacement R.C. Network card for motor complete all as specified and directed.
Supply only in replacement AC synchronous motor 240 volt 1 PH, 50 Hz 250 ma , 60 RMP , torque 10 Kg-cm suitable for 160 to 200 KVA complete all as specified and directed.
Supply only in replacement Voltmeter Digital type complete all as specified and directed.
Supply only in replacement Carbon Brushes complete all as specified and directed.
Supply only in replacement New Transformer Oil of 50 KV Die electric Strength complete all as specified and directed.
Maintenance servicing and complete overhauling of servo stablizer of capacity 25 KVA to 60 KVA including disassembling of operating mechanism parts, well cleaning with petrol & CRC-226 and replacing wornout parts reassembling of parts including disconnection,connection, well cleaning the complete stablizer, oil tank, connection plate,de-carbonizing all joints, metal parts and making servo stablizer operating in manual and electric mode including all routine testing ,calibration and replacement of unserviceable parts complete all as spd and directed. Note: (a) Any rewiring/changing of cable required for funtioning of stablizer is included in the quoted rate. (b) Major Spares to be paid separately as given Below.
Supply only in replacement Electronic cards including parts like IC's , regulators, condensers, Triac, Transistors, transformers Etc. complete with digital display of Voltage and load and touch pad card suitable for 25 KVA to 60 KVA servo voltage stabilizers complete all as specified and as directed.
Supply only in replacement Micro switch complete all as specified and directed.
Supply only in replacement R.C. Network card for motor complete all as specified and directed.
Supply only in replacement AC synchronous motor 240 volt 1 PH, 50 Hz 250 ma , 60 RMP , torque 10 Kg-cm suitable for 25 to 60 KVA complete all as specified and directed.
Supply only in replacement Carbon Brushes complete all as specified and directed.
Supply only in replacement New Transformer Oil of 50 KV Die electric Strength complete all as specified and directed.
Supply only in replacement Dimmer as per existing capacity complete all as specified and directed.
Supply only in replacement Gears as per existing capacity complete all as specified and directed.
M&L for Repairs & overhauling to AMF Panel of 320 KVA DG set by testing the Panel on DG sets supply and mains supply and checking out thoroughly for the defects & rectifing them,overhauling of the AMF panel, replacement of wornout minor spares like wiring circuits,nuts & bolts etc reassembling , re-installation , and replacement of unserviceable parts testing & commissioning of AMF panel complete all as directed Note :(i) Cost of cleaning agents, testing tools and minor spares shall be deemed to be including in quoted rates. (ii) Other major parts & accessories will be paid separately under following relevant items.
Supply only in replacement of microcontroller based AMF relay complete all as specified and directed.
Supply only in replacement of electronic Timer for AMF Panel of 320 KVA DG as per existing make & mode complete all as specified and directed.
Taking out old unserviceable Old LT cable any type and size from trenches or fixed on poles or through pipes/walls/laid under roads/paths/ drains/culverts complete all as specified and directed.
Supply laying and Testing cable in replacement of XLPE Insulated, screened, PVC bedded, galvanised steel strip or wire armored, electric power cables(heavy duty) with stranded aluminium conductor, 1100 volts grade, of size 16 Sqmm 4 core complete all as specified and directed.
All as per ser item No. 70 here-in-before but 25 Sqmm 4 core complete all as specified and directed.
All as per ser item No. 70 here-in-before but 35 Sqmm 3½ core complete all as specified and directed.
All as per ser item No. 70 here-in-before but 50 Sqmm 3½ core complete all as specified and directed.
All as per ser item No. 70 here-in-before but 70 Sqmm 3½ core complete all as specified and directed.
All as per ser item No. 70 here-in-before but 95 Sqmm 3½ core complete all as specified and directed.
All as per set item No. 70 here-in-before but 120 Sqmm 3½ core complete all as specified and directed.
All as per ser item No. 70 here-in-before but 150 sqmm 3½ core complete all as specified and directed.
Excavation in trenches in any type of soil n.exc. 1.5 mtr wide and n.exc 1.5 mtr in depth for laying of under ground cable and erection of steel poles and getting out in any type of soil complete all as specified and directed.
Returning, filling in, any type of soil and spreading in layers n. exc 25cm thick each layer including watering & well ramming complete all as specified & directed.
Removal of surplus soil to a distance n.exc 50 mtr & depositing where directed at a level n. exc. 1.5mtr above the starting point complete all as specified & directed.
M&L for providing of new sub class 'B' bricks old sizes, well burnt laid flat dry for protection of under ground cable.
M&L for sand cushioning from local sand dry, filling in trenches around LT under ground cable complete all as specified and directed.
Supply and fixing / laying in replacement of galvanized iron pipe of 80 mm nominal dia light grade fixed to poles with clamps nuts, bolts and washers or laid under road crossing or fixed to wall complete all as specified and directed. Note : The cost of MS clamp, nut, bolt, washer and GI fittings etc shall be inclusive in the item rate.
All as above item 83 here in before but for 40 mm nominal dia complete all as specified and directed.
Cutting of floor/wall/road/footpath for removal of LT U/G cable of any size/description and making good the same as per existing specification after relaying the same or new cable and all as specified & directed.
Material and labour for PCC 1:3:6 type C-2, using stone aggregate 40mm graded as in foundation of stays and coping of poles including necessary form work where required and fair finish to the exposed surfaces including broken of existing PCC all as specified & directed.
Material and labour for PCC 1:4:8 type D-2, using stone aggregate 40mm graded as in foundation for electric poles and making of cable duct including necessary form work where required and fair finish to the exposed surfaces all as specified & directed.
S&F heat shrink LT end joints of size 120 sqmm to 150 sqmm complete all as specified and directed.
S&F heat shrink LT end joints of size 185 sqmm to 240 sqmm complete all as specified and directed.
S&F heat shrink LT end joints of size 300 sqmm to 400 sqmm complete all as specified and directed.
S&F heat shrink LT straight through joints of size 70 sqmm to 95 sqmm complete all as specified and directed.
S&F heat shrink LT straight through joints of size 120 sqmm to 150 sqmm complete all as specified and directed.
S&F heat shrink LT straight through joints of size 185 sqmm to 240 sqmm complete all as specified and directed.
S&F heat shrink LT straight through joints of size 300 sqmm to 400 sqmm complete all as specified and directed.
M&L in repair/replacement for earthing complete with using galvanized mild steel earth plate (electrode) 600 mmx 600 mmx 6.0 mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all round the plate using 32X6 mm GI earth strip as earth lead moulded and riveted to earth plate at one end and connected to main equipment at switch/control board at another end, GI earth lead incased in and including 50 mm dia GI ‘light grade’ pipe from upper end of earth plate upto equipment with & including 20 mm dia bore GI pipe ‘light grade’ as water pipe from earth chamber to upper edge of the earth plate, GI funnel with wire mesh fixed on water pipe and provision of PCC 1:2:4 type B1(using 20 mm graded stone agg) as in pits chamber and RCC pit cover 50 mm thick of precast RCC 1:2:4 type B-1 (using 20 mm graded stone agg) complete all specified and directed.
M& L in replacement for fixing of air termination, single pointed aluminum rod 12 mm dia and 300 mm long complete all as specified and directed. Note: All accessories for fixing of termination is included in the quoted rates.
S&F in repair/replacement of aluminum strip 25x3.15mm with saddles and fixing screws etc for roof conductor and down conductors above ground all as specified & directed by Engg-in-charge.
S&F in replacement for galvanized iron strip 32x6mm buried into ground all as specified & directed.
S&F in replacement of test point terminal block made of gun metal or phosphorus bronze of size 75x75x25mm, drilled and screwed including 3 Nos 8 mm dia, 25mm long, hex head screw complete all as specified and directed.
M&L in replacement for GI tube light grade galvanized with all fittings fixed complete in walls and ceiling of 25 mm dia. complete all as specified and directed.
S & F in replacement of PVC DMC blocks with nut bolts in PCC blocks complete all as specified and directed. Note: All additional items required for fixing and connecting to strip is included in the quoted rate.
Clearing away all grass vegetation ,saplings, shrubs, brush wood undergrowth roots and trees not exceeding 30 CM girth (measured one metre above ground level) and removing rubbish upto a distance of 50 metres outside the periphery of the area under clearance soft/loose soil and getting out including spreading of anti vegitation chemical on complete Area all as directed and specified.
Supply and erection (in truly vertical position) in replacement of LT Steel tubular swaged pole complete with cast iron base plate finial taper plug, bolt , nut and screwed type 410 SP 31 09 mtrs long Class -10 including painting of poles with two coats of synthetic enamel paint in red and white strips upto 1.5 mtr height from coping over a coat of red oxide primer including numbering of poles all as directed. Note : PCC, Earth work and MS work as cross arms clamps etc will be measured and paid separately.
S&F MCB DB sheet metal enclosure 230 volt facility to fix MCB in incomer and MCBs outgoing , SPN vetical type 4 ways double door type complete fitted with busbar neutral links, S&F MCB isolator SPN 40 Amp capacity & blanking plates making good the disturbed surfaces so as to match with the existing surfaces complete and taking down old one from existing site.
Supply and fix in repairs loop-in loop-out box of size 20X20x15 cm made of 1.6mm thick PVC sheet weather proof, dust and vermin proof with hinged door of locking arrangements and slanting cover on top with provision of aluminium busbar of size 25 x 2mm - 2 No fixed on insulator complete fixed on pole with and including suitable size MS flat iron clamps, nuts, bolts and washers, etc complete all as specified & directed.
Supply and fixing in repair MCB single pole 6 amps to 32 amps 230 volts complete all as specified.
Supply and fixing in repair PVC Conduit size 20 mm dia heavy duty including clamp for fixing of service mains and twin core PVC cable fixed on wall/bldg complete all as specified and as directed.
Supply and fixing in repair PVC flexible conduit size 20 mm dia heavy duty including clamp for fixing of service mains and twin core PVC cable fixed on wall/bldg complete all as specified and as directed.
Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and as directed.
S&F in replacement Supply and fixing post top lantern LED type 20 Watt 230 volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed.
_ditto- as above item No 110 but for capacity 40 Watt complete all as specified and directed.
S&F in replacement LED Bollard light fittings of 1 Mtr height energy saving eco friendly robust body of capacity 8 watt with PCC works and fixing arrangement complete all as directed.
S&F in repair driver of post top energy saving LED gate light of capacity 20 watt-70 Watt complete all as specified and directed.
S&F in repair driver of Bollard LED light of capacity 8 watt-10 watt complete all as specified and directed.
S&F in repair contactor rating 63 Amp of existing make/model suitable for street light timer including dismantling existing un serviceable from the timer assembly and making reconnection connection all as specified and directed.
S&F in repair sensor of nature timer switch as per existing capacity and ranges complete all as specified & directed
S& F in replacement integral type solar street light 20 W with all accessories all in one type with 2 days back up complete all as specified and directed.
Supply and fixing in replacement LED flood light powder coated pressure die cast aluminium compact ,with surface mounting diode and heat resistance toughened glass suitable for 50 Watt complete all as specified and directed.
Supply and fixing in replacement LED flood light powder coated pressure die cast aluminium compact ,with surface mounting diode and heat resistance toughened glass suitable for 70 Watt complete all as specified and directed.
Supply and fixing in replacement LED flood light powder coated pressure die cast aluminium compact ,with surface mounting diode and heat resistance toughened glass suitable for 120 Watt complete all as specified and directed.
S&F in replacement for LED Highbay light Fitting 80 Watt with PDC aluminium housing with aim & adjustable bracket, Mat finished reflector for glare elimination, SMD LED with secondary lens & Integral SMD LED with pressure die cast aluminium housing, anodised aluminium reflector, complete with accesories IP-65 protection with necessary electrical connections alongwith iron chain suitable for bearing the load of fitting upto 1 mtr for extension upto ceiling of any height complete all as specified and directed.
Supply and fixing in replacement LED street light fitting, powder coated pressure die cast aluminium compact and heat resistance toughened glass with lens suitable for 45 Watt IP 66 protection complete all as specfied and as directed.
S&F in replacement of 1100 Volts grade heavy duty cable twin core Aluminum solid conductor with inner seathed with PVC tapes of size 6 Sqmm complete all as as specfied & directed
All as per sr item No 123 here in before but 10 Sqmm twin core Aluminum solid conductor complete all as specified and directed.
All as per sr item No 123 here in before but 16 Sqmm twin core Aluminum solid conductor complete all as specified and directed.
M& L for Cleaning and preparation of LT overhead line pole complete and painting with one coat of aluminium paint including channels/ brackets , cross arms and making red & white strips with synthetic enameled paint of 30 cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enameled paint after making circular base with black synthetic enameled paint and applying two coats of white wash on PCC coping complete all as specified & directed.
Supply Fixing in replacement of rechargeable sealed Lead Acid Battery maintenance free of capacity 2 Volt 150 AH model C10 for breaker Panel Charger complete all as specified and directed.
Supply Fixing in replacement of rechargeable sealed Lead Acid Battery of capacity 12 Volt 180 AH complete all as specified and directed.
Supply Fixing in replacement of rechargeable sealed Lead Acid Battery of capacity 12 Volt 100 AH complete all as specified and directed.
Supply Fixing in replacement of rechargeable sealed Lead Acid Battery of capacity 12 Volt 80 AH complete all as specified and directed.
M/S LADPURIA ENTERPRISES
shivam builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .