Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 701 SKYWALK TOWERS TANK LANE ORLEM MALAD WEST MUMBAI MAHARASHTRA 400064 | MUMBAI SUBURBAN | MAHARASHTRA | 400064 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance 9TH FLOOR 920 WAVE SILVER TOWER SECTOR 18 NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201301 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | Admitted-Finance |
| 4 | Admitted-Finance GROUND FLOOR ROOM NO 3 Y R TAWDE ROAD DAHISAR WEST MUMBAI 400068 | MUMBAI | MUMBAI | MAHARASHTRA | 400068 | Admitted-Finance |
| 5 | Rejected-Technical 7TH FLOOR DGK 712 DLF GALLERIA ACTION AREA 1 BG 8 NEWTOWN KOLKATA WEST BENGAL 700156 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700156 | Rejected-Technical Not submitted completion certificate of ISO 6/Class 1000 clearoom work in India. |
Tender Value
₹86.8 L
EMD Value
₹1.7 L
Closing Date
19 Jul 2022, 11:30 amClosed
DIRECTOR, NISER
DIRECTORATE, NISER
SITC OF 450 Sqft. OF CLASS 1000 / ISO Class 6 CLEAN ROOM IN CENTRE FOR MEDICAL AND RADIOLOGICAL PHYSICS (CMRP), NISER, JATNI
2022_NISER_698655_1
NISER/MECH/CMRP/2022-23/03
Open Tender
Machineries/ Mechanical Engg Items
Works
105 days
NISER, JATNI
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹1.7 L
IWD OFFICE, NISER
2 Aug 2022
4 Jul 2022
20 Jul 2022
4 Jul 2022
19 Jul 2022
4 Jul 2022
13 Jul 2022
WALL PARTITION: Supply, installation, testing and commissioning of Standard wall partitions, with a composite construction of two skins of PCGI/PPGI over an GI frame work with a sealed and insulated interior. Standard panel dimensions of 1185x3000mm or equivalent. Standard panels must have an overall thickness of 80 mm, optimum for walls of clean rooms of class 1000. Additional wall heights can be achieved using a stacking technique. The self-supporting internal walls are constructed with an interior GI frame work. Partition to Partition connections are maintained with precision with aluminium profiles that create uniform seams. The Partition seams are sealed by silicone with a perfectly flush finishing. PUF insulation material is sandwiched between the two skin layers and sealed from the exterior by the GI frame work. Self-supporting wall provided in modular units consisting of external skin in PCGI/ PCGI which will be 0.8mm thick ,with protective film to prevent surface damage during shipping and installation. The panel joints shall be made completely leak proof to prevent any kind of contamination in the conditioned air using silicon sealant properly as required for ISO 6/Class 1000 Clean Room. The scope also includes making of openings for cables, pipes, fire detections equipments, etc. and finishing after the work is completed. completly leak proof, complete in all respects and as per the instructions of Engineer In-Charge Movable Wall Includes: a) Puff Instulation of density: 40kg/m³ b) GI frame work c) Silicon Sealant (Clear/White/Winsil Gray) Wall Panel Thickness: 80 MM with inbuilt riser. Preffered Make: Nicomac/Synergy-Thrislington/iClean/ Beardshell/Qtech or equivalent
CEILING PANELS : SITC of Ceiling panels designed to fit within each other and suspended by threaded tension bars with adjustable turnbuckles fastened to the overhead support at fixed intervals and have a composite construction of two skins of PCGI / PPGI over an GI frame work with a sealed and insulated interior. A proper Ceiling includes: a) Puff insulation. b) Sheet Thickness 0.8 mm. c) GI frame frame work. d) Silicon sealant from both inside and ouside. Ceiling Panel Thickness: 80 MM : Walkable. Preffered make: Nicomac/Synergy-Thrislington/iClean/ or equivalent
COVINGS AND WALL CONNECTIONS: SITC of Vertical & Horizontal Coving for wall and ceiling. Extruded Aluminium Power coated/Anodised R42 Clip-On type coving. Vertical & Horizontal Coving for wall and ceiling. Preffered make: Nicomac/Synergy-Thrislington/iClean/ or equivalent
COVINGS AND WALL CONNECTIONS: SITC of Vertical & Horizontal Coving for wall and ceiling. Extruded Aluminium Power coated/Anodised R42 Clip-On type coving. 3D Corner Piece (2D Coving /3D Coving). Preffered make:Nicomac/Synergy-Thrislington/iClean/ or equivalent
CLEAN ROOM DOORS: SITC of Clean room doors. Doors are designed to fit flush into the wall panel system on both sides and are supplied in given dimension. Doors are fabricated from galvanized iron sheets duly powder coated. Shutter has sheet thickness of 0.8 mm and the frame of 1.2mm. Standard 50 mm panel has frame width of 50 mm and shutter width of 46 mm. Doors to be made such a way to provide proper Class 1000 clean room environment as per the requirement of the client and instructions of Engineer - In - Charge. The following accessories are a part of the door: a) Shutter Thickness: 46 mm thick b) Stainless steel hinges c) Stainless Steel 'D' type of handles on pull side d) Stainless steel push plates on push side. e) Standard arm door closure. f) View panel along with self-adhesive tape and silicon sealant g) Both side key operated locking arrangement h) Automatic door bottom seal at the bottom i) Stainless Steel kick plates j) Filler material: Puff Insulation, Single Shutter Door Size 900(W) X 2100 (H)
CLEAN ROOM DOORS: SITC of Clean room doors. Doors are designed to fit flush into the wall panel system on both sides and are supplied in given dimension. Doors are fabricated from galvanized iron sheets duly powder coated. Shutter has sheet thickness of 0.8 mm and the frame of 1.2mm. Standard 50 mm panel has frame width of 50 mm and shutter width of 46 mm. Doors to be made such a way to provide proper Class 1000 clean room environment as per the requirement of the client and instructions of Engineer - In - Charge. The following accessories are a part of the door: a) Shutter Thickness: 46 mm thick b) Stainless steel hinges c) Stainless Steel 'D' type of handles on pull side d) Stainless steel push plates on push side. e) Standard arm door closure. f) View panel along with self-adhesive tape and silicon sealant g) Both side key operated locking arrangement h) Automatic door bottom seal at the bottom i) Stainless Steel kick plates j) Filler material: Puff Insulation, Double Shutter Door (Emergency door) Size 1200 (W) X 2100 (H)
VIEW PANEL: Double Glaze Vision Panel with 2 Nos. of 6 mm thick clear toughened glass with 20mm black/white border with all accessories like double adhesive tape, silicon sealant and silica gel with 0.8 mm GI powder coated inner channel with installation as per Standards size : 1200 mm x 1500 mm. View Panel for Clean Room: 1200 mm x 1500 mm
DX TYPE CONDENSING UNIT: Supply installation, Testing & Commissioning of modular type Variable Refrigerant Flow / Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll/Rotary Compressor(s), minimum two compressors for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable civil foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V+/-10%, 3Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 . Note: All the electrical joints and connections shall be properly sealed to prevent short circuit due water seepage. DX Type Outdoor Unit VRF Units Capacity: 20 HP, Preferred Make: Bluestar/ Daikin /Carrier-Toshiba
Supply, Installation, testing and commissioning of air Cooled type Outdoor unit with scroll compressor, Copper condenser, condenser fan with motor, controller etc. The system will be suitable for 415V+/- 10%, 3 Ph operation. Eco friendly Refrigerant R410A/ R407C. Note: All the electrical joints and connections shall be properly sealed to prevent short circuit due water seepage. Outdoor Unit for Precooling coil of Dehumidifier, Capacity: 11 TR. BlueStar/Daikin/Carrier-Toshiba
REFRIGERANT PIPING: Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of suitable sizes of soft/hard drawn seamless copper refrigerant piping (IS: 10773/ASTM B280/B88) for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, cutting, jointing/brazing including accessories, expansion valves, dryer, supports and fixtures insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 13mm thickness for Suction and Liquid lines, with protective layer of aluminium/PVC/plastic tape with all accessories etc. between condensing unit and AHUs including as required and as per the instructions of Engineer In-Charge. Refrigerant Copper Piping for 20 HP VRF unit
DRAIN PIPING: Supply & fixing of PVC 40 mm pipeline for condensate drainage water piping from the AHU to the nearest drain point. complete as required and as per the instructions of Engineer In-Charge. Drain Piping 40 mm
DESICCANT DEHUMIDIFIER: Supply, Installation, testing and commissioning of Desiccant dehumidifier comprising of a high efficiency desiccant honeycomb rotor / bed mounted on a horizontal fixed shaft arrangement, Inlet Fresh Air-filter EU-3 / 20 micron Synthetic Non-Woven media filter, Plug type process air fan with motor, DX type copper Pre-Cooling Coil, insulated drain pan made of 18 G SS 304 construction, Reactivation fan, Motor, Electric heater, Electrical control panel with necessary accessories. All the electrical joints and connections shall be properly sealed to prevent short circuit due water seepage. Desiccant Dehumidifier, Capacity: 1500 CMH. Make: Bry Air/ Dessica/ Munters/Drytech/Hygrotech
HEPA FILTER with housing: Supply, Installation ,Testing and Balancing of following sizes terminal hepa filters complete with 1.6 mm powder coated aluminium frame and gaskets as per the approved shop drawings and specifications. Efficiency of hepa filters shall not be less than 99.95% down to 0.05 microns. The hepa filters shall be housed within air tight factory fabricated housing constructed out of 1.6mm aluminium sheet without any mechanical arrangements easy to remove and refix. 1.2 mm thick stainless steel perforated sheet and volume control damper including filter housing. Inclusive of provision for DOP/PAO testing port. All necessary fixtures and arrangements to secure the modules in false ceiling shall be part of the scope.Complete as required and as per the instructions of Engineer In-Charge. Hepa filters shall be of following sizes: 600 mm x 600 mm HEPA filter. Camfil/Freudenberg/ AFI
HEPA FILTER with housing: Supply, Installation ,Testing and Balancing of following sizes terminal hepa filters complete with 1.6 mm powder coated aluminium frame and gaskets as per the approved shop drawings and specifications. Efficiency of hepa filters shall not be less than 99.95% down to 0.05 microns. The hepa filters shall be housed within air tight factory fabricated housing constructed out of 1.6mm aluminium sheet without any mechanical arrangements easy to remove and refix. 1.2 mm thick stainless steel perforated sheet and volume control damper including filter housing. Inclusive of provision for DOP/PAO testing port. All necessary fixtures and arrangements to secure the modules in false ceiling shall be part of the scope.Complete as required and as per the instructions of Engineer In-Charge. Hepa filters shall be of following sizes: 300 mm x 300 mm HEPA filter. Make: Camfil/Freudenberg/ AFI
GSS DUCTING: Supply, Installation, Testing Balancing & Commissioning of G.S.S square/ round/ rectangular factory/site fabricated ducting with MS ceiling and ground supports as per site requirements, neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, ceiling stud supports, fastners, adjustable dampers, etc. as per drawings and as required for dehumidified air distribution of following thickness as per approved working drawings, specifications and requirement at site. The duct joints shall be made completely leak proof to prevent any kind of contamination in the conditioned air using silicon sealant or other similar Room Temperature Vulcanizing (RTV) sealant as required for ISO 6/Class 1000 Clean Room. The work to be carried out following the IS standards completeas required as per specifications and as per the instructions of Engineer In-Charge. 24G
GSS DUCTING: Supply, Installation, Testing Balancing & Commissioning of G.S.S square/ round/ rectangular factory/site fabricated ducting with MS ceiling and ground supports as per site requirements, neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, ceiling stud supports, fastners, adjustable dampers, etc. as per drawings and as required for dehumidified air distribution of following thickness as per approved working drawings, specifications and requirement at site. The duct joints shall be made completely leak proof to prevent any kind of contamination in the conditioned air using silicon sealant or other similar Room Temperature Vulcanizing (RTV) sealant as required for ISO 6/Class 1000 Clean Room. The work to be carried out following the IS standards completeas required as per specifications and as per the instructions of Engineer In-Charge. 22G
GSS DUCTING: Supply, Installation, Testing Balancing & Commissioning of G.S.S square/ round/ rectangular factory/site fabricated ducting with MS ceiling and ground supports as per site requirements, neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, ceiling stud supports, fastners, adjustable dampers, etc. as per drawings and as required for dehumidified air distribution of following thickness as per approved working drawings, specifications and requirement at site. The duct joints shall be made completely leak proof to prevent any kind of contamination in the conditioned air using silicon sealant or other similar Room Temperature Vulcanizing (RTV) sealant as required for ISO 6/Class 1000 Clean Room. The work to be carried out following the IS standards completeas required as per specifications and as per the instructions of Engineer In-Charge. 20G
GSS DUCTING: Supply, Installation, Testing Balancing & Commissioning of G.S.S square/ round/ rectangular factory/site fabricated ducting with MS ceiling and ground supports as per site requirements, neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, ceiling stud supports, fastners, adjustable dampers, etc. as per drawings and as required for dehumidified air distribution of following thickness as per approved working drawings, specifications and requirement at site. The duct joints shall be made completely leak proof to prevent any kind of contamination in the conditioned air using silicon sealant or other similar Room Temperature Vulcanizing (RTV) sealant as required for ISO 6/Class 1000 Clean Room. The work to be carried out following the IS standards completeas required as per specifications and as per the instructions of Engineer In-Charge. 18G
THERMAL INSULATION: Supplying and fixing of following thickness duly laminated aluminum foil of matt finish closed cell XLPE / Nitrile rubber (Class “O”) insulation. Insulation density should not less than 30 kg per cubic meter in single layer with factory lamination of 30 micron aluminium foil on existing duct after applying suitable adhesive for XLPE / Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive XLPE / nitrile rubber tape insulation complete as per specifications and as required. 19 mm Nitrile Rubber/XLPE Insulation (for inside building use). Armacell/Aerolam/Kflex
THERMAL INSULATION: Supplying and fixing of following thickness closed cell XLPE / Nitrile rubber (Class “O”) insulation. Insulation density should not less than 30 kg per cubic meter in single layer duly pasted with Glass cloth on on face on existing duct after applying suitable adhesive for XLPE / Nitrile rubber. The joints shall be sealed with similar 50 mm wide and 3 mm thick self adhesive XLPE / nitrile rubber tape insulation complete as per specifications as required and as per the instructions of Engineer In-Charge. 19 mm Nitrile Rubber/XLPE Insulation faced with glass cloth (for exterior of building use). Armacell/Aerolam/Kflex
EXPOSED RETURN AIR RISER: Supplying, fixing, testing, commissioning of exposed Return air Risers of powder coated G.I return air duct with volume control damper, anti smudge ring & removable core, etc. mounted with 1.2 mm perforated SS-304 Grill of suitable size to maintain air balancing with flanged connection to GI The duct shall connect to main duct by a flanged connections as per specifications complete as required and as per the instructions of Engineer In-Charge. Return Risers with grills and dampers
MOTORIZED DUCT DAMPERS: Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sqmm) for integration within AHU. Motorized (ON-OFF Type) duct mounted GI volume control damper
FIRE CONTROL DAMPERS: Supply, installation, testing and commissioning of fusible link type fire control damper in 16SWG GI construction. Rated for 90 minutes with Fusible link for fire damper with Limit Switch. Fusible Link Fire Damper. Make: Carryair/Greeheck/ or equivalent
CANVAS : Double layered Flexible canvass for connection between AHU's dampers and supply air duct made of fibreglass weave having silver grey silicon rubber coating, Flexible connection shall be air tight & water proof and withstand high temperature application, non flammable and does not support combustion. Flexible connection shall be complete with MS flanges made out of 22G G.S.S sheet on both sides for connection to unit and duct complete with nuts, bolts etc. properly sealed for air tight connection to prevent any infiltration of untreated air, complete as required and as per the instructions of EIC.
EPOXY FLOORING WITH COVING: Supplying, providing and laying self-levelling epoxy floor topping 4mm thick at all floor, level and location of approved colour/shade for re-topping worn out floor consisting of 2 mm thick (or more as per site requirement for making the existing concrete floor in level) moisture barrier screen made with Sika floor 81 Epocem of M/s. Sika Qualcrete or equivalent over a coat of suitable primer as per manufacturer recommendation followed by 2 mm thick self-levelling, self - smoothing, epoxy floor topping prepared with MASTERTOP 1215 PLUS of M/s. BASF or equivalent along with suitable primer etc. as recommended by manufacture preparing surface by removing old coating, with concrete, cement laitance, loose particles, oil, grease, other stains etc.by scarifying or grinding, shot blasting followed by vacuum cleaning including anchor cutting of feather joints for terminations, curing etc. complete as directed by the Engineer in Charge.Epoxy Flooring. Make: BASF/Sika Qualcrete/Imperial or equivalent
EPOXY FLOORING WITH COVING: Supplying, providing and laying self-levelling epoxy floor topping 4mm thick at all floor, level and location of approved colour/shade for re-topping worn out floor consisting of 2 mm thick (or more as per site requirement for making the existing concrete floor in level) moisture barrier screen made with Sika floor 81 Epocem of M/s. Sika Qualcrete or equivalent over a coat of suitable primer as per manufacturer recommendation followed by 2 mm thick self-levelling, self - smoothing, epoxy floor topping prepared with MASTERTOP 1215 PLUS of M/s. BASF or equivalent along with suitable primer etc. as recommended by manufacture preparing surface by removing old coating, with concrete, cement laitance, loose particles, oil, grease, other stains etc.by scarifying or grinding, shot blasting followed by vacuum cleaning including anchor cutting of feather joints for terminations, curing etc. complete as directed by the Engineer in Charge.Epoxy Floor Coving and Corner. Make: BASF/Sika Qualcrete/Imperial or equivalent
Copper Strip fixing below the PVC flooring of Epoxy Flooring: Providing and fixing 24 mm X 0.3 mm tinned copper strip on surface, below epoxy floor etc. as required.
Copper Strip fixing below the PVC flooring of Epoxy Flooring: Providing and fixing earth bus of 50 mm X 5 mm tinned copper strip on surface with suitable insulator support fixing etc. as required for the earth bus connection.
VALIDATION OF THE CLEAN ROOM: Third party Validation as per ISO 14644 with HVAC qualification documents DQ / IQ / OQ / PQ as per norms. Complete in all respects and as per the instructions of EIC. a) Air velocity test b) Filter Integrity Test c) PAO Leak Test d) CFM Test e) Air Balancing f) Smoke Visualization g) Particle Count Test h) Recovery Test i) Air Flow Pattern Test j) Light Intensity Test k) Sound Level Measurement l) Temperature and RH mapping m) Differential Pressure checking/Balancing. Validation of Clean Room
MONITORING & CONTROL SYSTEMS: SITC of Temperature, Humidity and Pressure monitoring systems, Magnehelic Gauges, Voltage & Ampere Meter, ABB Drive for Motor Blower, RH Control Inbuilt thyristor Control System, Hooter / Data Back Up & Customized Programable as per design PLC with PLC panel for AHU Motor, Condensing Unit and Control Only inclusive of wiring, cabling, 7 Inch display, MCBs all power, communication, integration and signal cables, etc. all cables in MS conduits, panels with provision to prevent damages by dust, vermin and rodent. Capacity : 24 Port Input and 18 Port Output portMonitoring & Control Systems Make: Siemens/Honeywell
ELECTRICAL PANELS: Supply, Installation, testing and commissioning of Dust and vermin proof indoor type factory built sheet steel enclosed modular construction floor/ wall mounted control panel for 2 nos. AHUs, 2 nos. Dehumidifier and 6 Nos. Outdoor unit, suitable for operation on 415±10% volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized square tubular section and covered with CRCA sheet steel of 2mm thick for frame work and covers etc. The panel comprising of Incomer MCCB/MCB, Outgoing MCB, overload protection, Analog/ Digital type timer, manual operational facility, internal wiring, On Off Indication Lamp, as required. Incomer Details : 200A, 4 pole MCCB 36Ka - 1 No. Outgoing Deatils : 40A, 3P, MCB - 2 Nos. 100A, 4P MCB - 2 Nos. 63A, 4P MCB - 2 Nos. 50 A, 4P MCB - 2 Nos. Make: Legrand/ Schiender/ Hagger
DISTRIBUTION BOARD: Supplying and fixing following way prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required with following MCB/ RCCB/ Isolator. 6 way (4 + 18), Double door – 1 No. 63 Amp 4 pole Isolator- 1 No. 63 Amp Double pole RCCB(Sensivity 30 mA)- 3 Nos. 25/32 Amp SP MCB- 12 Nos. Make:- Legrand / Hager / Schneder / Siemens
Power Cabling : Supply and laying and commissioning of copper flexible power cabling (1.1 kV gr.) with Lux, gland for connection4 C X 16 sqmm - Outdoor Units Make: Polycab/ Anchor/ Rrkabel/Finolex
Power Cabling : Supply and laying and commissioning of copper flexible power cabling (1.1 kV gr.) with Lux, gland for connection 4 C X 10 sqmm - Dehumidifier Polycab/ Anchor/ Rrkabel/Finolex
Power Cabling : Supply and laying and commissioning of copper flexible power cabling (1.1 kV gr.) with Lux, gland for connection4 C X 6 sqmm - Outdoor units & AHUs Polycab/ Anchor/ Rrkabel/Finolex
Power Cabling : Supply and laying and commissioning of copper flexible power cabling (1.1 kV gr.) with Lux, gland for connection4 C X 4 sqmm Polycab/ Anchor/ Rrkabel/Finolex
CONTROL CABLE: Supply, laying and commissioning of Copper control cabling (1.1kV gr.) including MS/GI conduit with accessories. 2 C X 1.5 sqmm - Control for VRF outdoor units and control panel Polycab/ Anchor/ Rrkabel
CONTROL CABLE: Supply, laying and commissioning of Copper control cabling (1.1kV gr.) including MS/GI conduit with accessories. 4 C X 1.5 sqmm - for Control panel Polycab/ Anchor/ Rrkabel
CONTROL CABLE: Supply, laying and commissioning of Copper control cabling (1.1kV gr.) including MS/GI conduit with accessories. 6 C X 1.5 sqmm - for Control panel Polycab/ Anchor/ Rrkabel
CABLE TRAY Supplying and installing following size of perforated GI/painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including horizontalbolts & nuts, painting suspenders etc as required as per the location of following specifications. Cable Tray: 200 mm width X 50 mm depth X 1.6 mm thickness
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC1 x 3 Ph industrial socket + 1 x 1 Ph industrial socket Legrand/Myrius
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC 3 x 5/16 A Switch socket Legrand/Myrius
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC 3 x 5/16 A Switch socket + 1 LAN Legrand/Myrius
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC 2 x 5/16 A Switch socket + 1 LAN Legrand/Myrius
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC 2 x 5/15A + 1 LAN Legrand/Myrius
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC 4 x 5/15A Legrand/Myrius
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC 4 x 5/15A + 1 LAN Legrand/Myrius
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC 4 x 5/15A Legrand/Myrius
Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections GI box along with modular base & cover plate for modular switches in recess, etc. as required and as per instructions of EIC 2 x 5/ 15 A + 1 LAN Legrand/Myrius
LIGHT FITTINGS & FIXTURES Supply, Installation, Testing & Commissioning of the following fixtures complete with all HF electronic ballast with THD less than 10%, , fixing arrangements, earthing complete with all hardware, clamps, etc as per specification. Ceiling mounting flush type square LED lighting fixture suitable for clean room operation. Efficiency will be min 95% or above. LED Light Fixtures Capacity : 32 Watt, 3600 Lumen,Size : 600 mm x 600 mm, 6500 k Philips/ Wipro/ Bajaj/ Crompton
Supplying and fixing of Ceiling mounting flush type square LED lighting fixture suitable for clean room operation. Efficiency will be min 95% or above LED Light Fixtures Capacity : 32 Watt, Size : 600 mm x 600 mm Philips/Bajaj/Wipro
Supply and laying and commissioning of Wiring for light point/ fan point/ exhaust fan point/ call bell point with following sizes of FRLS PVC insulated copper conductor single core cable in existing steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc complete as required and as per the instructions of Engineer Incharge. Wiring for electrical items and fixtures of clean room 2 x 1.5 Sq.mm + 1 x 1.5 sq.mm earth wire Finolex/Polycab
Supply and laying and commissioning of Wiring for light point/ fan point/ exhaust fan point/ call bell point with following sizes of FRLS PVC insulated copper conductor single core cable in existing steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc complete as required and as per the instructions of Engineer Incharge. Wiring for electrical items and fixtures of clean room 2 x 2.5 Sq.mm + 1 x 2.5 sq.mm earth wire Finolex/Polycab
Supply and laying and commissioning of Wiring for light point/ fan point/ exhaust fan point/ call bell point with following sizes of FRLS PVC insulated copper conductor single core cable in existing steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc complete as required and as per the instructions of Engineer Incharge. Wiring for electrical items and fixtures of clean room 2 x 4 Sq.mm + 1 x 4 sq.mm earth wire Finolex/Polycab
Supply and laying and commissioning of Wiring for light point/ fan point/ exhaust fan point/ call bell point with following sizes of FRLS PVC insulated copper conductor single core cable in existing steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc complete as required and as per the instructions of Engineer Incharge. Wiring for electrical items and fixtures of clean room 4 x 4 Sq.mm + 12 x 4 sq.mm earth wire Finolex/Polycab
Supplying and drawing of UTP LHZS 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. Single run of cable
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25 mm
Information Outlet with face plate with Back box CAT 6 Information outlet with faceplate (Single/Dual/Quad) conforming to ANSI/TIA/EIA-568 C.2 latest or ISO/IEC:11801 latest Make: D-Link or equivalent
Punching work
Providing and fixing of galvanised iron strips size of 25 mm x 6 mm n surface or in recess for loop earthing with , suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required.
Providing and fixing two runs of 6 SWG dia G.I. wire on surface or in recess for loop earthing with , suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required.
Cleanroom Door Interlocking to prevent the pressure loss during the opening of two doors simultaneously. Provision to me made that at the time of fire, the doors can be open all at once for evacuation Door Interlocking
Supply, Installation, Testing and Commissioning of Air Shower Inner size : 900 x 900 x 1950mm (WxDxH) Cabinet: CRCA Powder Coated Platform: PVC Matt Flooring View Panel door Pre-filter: 10 microns HEPA Filters:0.3 micron Adjustable SS nozzles Motor blower Power supply- 3phase, 415volts RPM- 2440 Exit door & entry door Audio visual alarm as a safety measure in case motor blower trips. Fault acknowledgement for motor blower tripper Blower/filter.: Side-mounted Flow: Vertical down and two sides Lighting Fluorescent tubes Shower duration 0-120 seconds (Adjustable) Sound level: 90dbA±5% Motor Air - Velocity: 4000-4500FPM Controls: Motor by DOL starter, doors by electromagnetic interlocking, Overload Protection: By thermal relay, Shower duration: By Electronic timer, Emergency off: By push Button. Air Shower : 900 x 900 x 1950mm (WxDxH) Make: Klenzaids/Thermodyne/Ramnath/Kashyp/Qtech
Sterile Garment storage cabinet suitable for 6 persons cloths & shoes rack including UV Lights, Fan module, HEPA Filter etc. for clean room application complete in all respect Make: Hitech/ESCO/ Kleanzone/Kashyp/Qtech SS Sterile Garment cabinet
SITC of Dynamic Pass Box made out of SS304 comprising of H13 type Hepa Filter of Efficiency of 99.99%, UV Lamp, Magnehelic guages. Inner Dimension : 1200 mm x 1200 mm x 1200mm Make : Thermodyne/ Kleanzoid/ Hitech/ESCO/Kashyp/Qtech Dynamic Pass Box : Inner Dimension : 1200 mm x 1200 mm x 1200mm
CGMP Projects Pvt. Ltd
Cadillac Filter Pvt. Ltd.
Kashyp Technoengicon India Pvt. Ltd.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .