Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.6 LAccepted-AOC NO 1A 1 SHALOM VALLUVAR STREET SIVANANDHA COLONY COIMBATORE TAMIL NADU 641 012 | COIMBATORE | TAMIL NADU | 641012 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹29.7 L+₹70,077 (2.42%)Rejected-Finance A S NIVAS CHANKURTHY ADAIKKAKUZHI P O KANYAKUMARI DISTRICT TAMIL NADU 629153 | KANYAKUMARI | KANYAKUMARI | TAMIL NADU | 629153 | L2 | Rejected-Finance Not being L1 | |
| 3 | L3₹34.8 L+₹5.8 L (20.0%)Rejected-Finance 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | L3 | Rejected-Finance Not being L1 | |
| 4 | L4₹36.2 L+₹7.2 L (25.0%)Rejected-Finance 20 2169 PALLURTH PO ERNAKULUM KERALA 682006 | ERNAKULAM | KERALA | 682006 | L4 | Rejected-Finance Not being L1 |
| Sl No | Description | Qty | Unit | Jack Electrolinks Private Limited L4 | SUJAN L2 | shalom constructions L1 | MONA GENERATOR SEVICES PVT. LTD. L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Dismantling of unserviceable / broken electric pole of any size and type by disconnecting all connections, demolition of concerted foundation including excavation, earth work as required and removing the same from site complete all as specified and directed. | 10 | Each | 850 ₹8,500 | 600 ₹6,000 | 500 ₹5,000 Lowest | 804 ₹8,040 |
| 2.00 | Dismantling of unserviceable insulators of any size and type from LT overhead lines complete all as specified and directed. | 10 | Each | 10 ₹100 Lowest | 50 ₹500 | 10 ₹100 Lowest | 15 ₹150 |
| 3.00 | M&L for erection of Prestressed concrete pole, 9.0 metres long, 102mm x 172mm at top and 102mm x 279mm at bottom, class 10 vertical position complete including painting two coats of bituminous paint through out upto the below ground level depth and the remaining portion of the exterior shall be painted with anti-fungal weather coat paint complete all as specified and directed. | 10 | Each | 22,500 ₹2,25,000 | 7,000 ₹70,000 Lowest | 12,000 ₹1,20,000 | 9,572 ₹95,720 |
| 4.00 | Stretching/ restringing only ACSR conductor in position on LT overhead lines of any size, type, span length with permissible span sag and binding with pin/ shackle insulator with new aluminium binding wire not less than 2mm dia complete all as specified and directed. | 1 | Per Quintal | 5,000 ₹5,000 | 500 ₹500 Lowest | 1,800 ₹1,800 | 502 ₹502 |
| 5.00 | M&L for pin type insulator, porcelain vitreous, white, brown or green including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100 mm height and 65 mm dia for 1100 volts grade complete all directed. | 5 | Each | 150 ₹750 | 200 ₹1,000 | 90 ₹450 Lowest | 248 ₹1,240 |
| 6.00 | M&L for shackle type porcelain vitreous white, brown or green insulator of size 75mm height, 90mm dia (maximum) including galvanised steel fittings straps of section 31mmx3mm, washers, 12mm dia insulator bolts and nuts suitable for working pressure 1100 volts grade complete all as specified and directed. | 5 | Each | 200 ₹1,000 | 150 ₹750 | 90 ₹450 Lowest | 303 ₹1,515 |
| 7.00 | M&L for loop type insulator, vitreous porcelain, white, brown or green large size, with overall dimensions 90mm x 140mm and clearance of hole 25.5mm complete all as specified and directed. | 5 | Each | 150 ₹750 | 150 ₹750 | 90 ₹450 Lowest | 345 ₹1,725 |
| 8.00 | M&L for preparation old painted surface of cement concrete poles of any size from pole coping to top of pole including struts, cross arms, clamps, etc and painting with two coats of approved colour of aluminium paint on cross-arms over one coat of aluminium red oxide primer and two coats of anti-fungal weather coat paint (apex ultima) on cement poles and numbering of poles as directed with black synthetic enamelled paint complete all as specified and directed. | 20 | Each | 450 ₹9,000 | 170 ₹3,400 Lowest | 239 ₹4,780 | 598 ₹11,960 |
| 9.00 | M&L for LT UG cable XLPE insulated and screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of cross-sectional area 150 Sq.mm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed. | 300 | Running Metre | 1,200 ₹3,60,000 | 800 ₹2,40,000 Lowest | 1,035 ₹3,10,500 | 992 ₹2,97,600 |
| 10.00 | M&L for LT UG cable XLPE insulated and screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of cross-sectional area 120 Sq.mm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed. | 200 | Running Metre | 1,000 ₹2,00,000 | 648 ₹1,29,600 Lowest | 890 ₹1,78,000 | 837 ₹1,67,400 |
Tender Value
₹36 L
EMD Value
₹72,000
Closing Date
23 Aug 2025, 6:00 pmClosed
GE Army Trivandrum
Office of Garrison Engineer Army, Thirumala Post, Trivandrum- 695006
REPAIR/MAINT OF LT PANEL, MCCBS, CLEANING OF SUBSTATION, PAINTING OF POLE/PANEL INCL ALLIED WORKS, REPAIR/REPLACEMENT OF HIGH MAST/FLOOD/SOLAR/STREET LIGHTING INCL CONNECTED ITEMS AT PMS UNDER GE (ARMY) TRIVANDRUM
2025_MES_723003_1
8281/E8
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
Trivandrum
As per tender documents
8 documents required · 8 mandatory
₹500
GE Army Trivandrum
₹72,000
Yes
15 Oct 2025
28 Jul 2025
26 Aug 2025
28 Jul 2025
23 Aug 2025
11 Aug 2025
28 Jul 2025 - 4 Aug 2025
Amount
Dismantling of unserviceable / broken electric pole of any size and type by disconnecting all connections, demolition of concerted foundation including excavation, earth work as required and removing the same from site complete all as specified and directed.
Dismantling of unserviceable insulators of any size and type from LT overhead lines complete all as specified and directed.
M&L for erection of Prestressed concrete pole, 9.0 metres long, 102mm x 172mm at top and 102mm x 279mm at bottom, class 10 vertical position complete including painting two coats of bituminous paint through out upto the below ground level depth and the remaining portion of the exterior shall be painted with anti-fungal weather coat paint complete all as specified and directed.
Stretching/ restringing only ACSR conductor in position on LT overhead lines of any size, type, span length with permissible span sag and binding with pin/ shackle insulator with new aluminium binding wire not less than 2mm dia complete all as specified and directed.
M&L for pin type insulator, porcelain vitreous, white, brown or green including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100 mm height and 65 mm dia for 1100 volts grade complete all directed.
M&L for shackle type porcelain vitreous white, brown or green insulator of size 75mm height, 90mm dia (maximum) including galvanised steel fittings straps of section 31mmx3mm, washers, 12mm dia insulator bolts and nuts suitable for working pressure 1100 volts grade complete all as specified and directed.
M&L for loop type insulator, vitreous porcelain, white, brown or green large size, with overall dimensions 90mm x 140mm and clearance of hole 25.5mm complete all as specified and directed.
M&L for preparation old painted surface of cement concrete poles of any size from pole coping to top of pole including struts, cross arms, clamps, etc and painting with two coats of approved colour of aluminium paint on cross-arms over one coat of aluminium red oxide primer and two coats of anti-fungal weather coat paint (apex ultima) on cement poles and numbering of poles as directed with black synthetic enamelled paint complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of cross-sectional area 150 Sq.mm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of cross-sectional area 120 Sq.mm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of cross-sectional area 95 Sq.mm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of cross-sectional area 70 Sqmm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 50 Sqmm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 35 Sqmm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 25 Sqmm, 3.5 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 10 Sqmm, 2 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
M&L for LT UG cable XLPE insulated and screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade of Size 16 Sqmm, 2 core as per IS 7098 (Part 1) 1988, including taking down old unserviceable LT UG cable complete all as specified and directed.
Supplying, installing, testing and commissioning, factory made and tested (incl CPRI type test certified), LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 HZ AC supply system, having bus bar chamber with insulated aluminium bus bars 250 Amps. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm thick CRCA MS sheet and 40x40x6mm thick angle iron frame work, powder coated finish, front opening type, with aprons for cable entry, with double door shutter and locking arrangements including provision of 65mm Godrej (Freedom) lock with 2 keys , internal wiring with PVC insulated, copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. Panel should be above ground level including dismantling existing old unserviceable feeder pillar complete all as specified and as directed (Loc - MM Range). The scope of work includes the following:-
(b) Outgoing: (i) MCCB 4 pole 415 volts AC grade 125 Amp and 16 KA rupturing capacity -02 Nos (ii) MCCB 4 pole 415 volts AC grade 63 Amp and 16 KA rupturing capacity -01 No (iii) MCB SPN 63 Amp rating -02 No (iv) MCB SPN 40 Amp rating -01 No (v) Single phase street light timer of 40 Amps rating -01 No
(c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15mm in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road level. Note : All out going feeders shall be connected by cable through suitable size gland plate / glands.
Supplying, installing, testing and commissioning, factory made and tested (incl CPRI type test certified), LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 HZ AC supply system, having bus bar chamber with insulated aluminium bus bars 400 Amps. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm thick CRCA MS sheet and 40x40x6mm thick angle iron frame work, powder coated finish, front opening type, with aprons for cable entry, with double door shutter and locking arrangements including provision of 65mm Godrej (Freedom) lock with 2 keys , internal wiring with PVC insulated, copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. Panel should be above ground level including dismantling existing old unserviceable feeder pillar complete all as specified and as directed (Loc - Near NCC House). The scope of work includes the following:-
(b) Outgoing: (i) MCCB 4 pole 415 volts AC grade 200 Amp and 25 KA rupturing capacity -02 No (ii) MCCB 4 pole 415 volts AC grade 160 Amp and 16 KA rupturing capacity -02 Nos (iii) MCCB 4 pole 415 volts AC grade 100 Amp and 16 KA rupturing capacity -02 No (iv) Single phase street light timer of 40 Amps rating -01 No
(c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15mm in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road level. Note : All out going feeders shall be connected by cable through suitable size gland plate / glands.
Supplying, installing, testing and commissioning, factory made and tested (incl CPRI type test certified), LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 HZ AC supply system, having bus bar chamber with insulated aluminium bus bars 400 Amps. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm thick CRCA MS sheet and 40x40x6mm thick angle iron frame work, powder coated finish, front opening type, with aprons for cable entry, with double door shutter and locking arrangements including provision of 65mm Godrej (Freedom) lock with 2 keys , internal wiring with PVC insulated, copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. Panel should be above ground level including dismantling existing old unserviceable feeder pillar complete all as specified and as directed (Loc - Near Pangode sainik Institute). The scope of work includes the following:-
(b) Outgoing: (i) MCCB 4 pole 415 volts AC grade 160 Amp and 25 KA rupturing capacity -02 No (ii) MCCB 4 pole 415 volts AC grade 100 Amp and 16 KA rupturing capacity -02 Nos (iii) MCCB 4 pole 415 volts AC grade 63 Amp and 16 KA rupturing capacity -01 No (iv) MCB SPN 63Amps rating - 04 No. (v) Single phase street light timer of 40 Amps rating -01 No
(c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15mm in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road level. Note : All out going feeders shall be connected by cable through suitable size gland plate / glands.
Supplying, installing, testing and commissioning, factory made and tested (incl CPRI type test certified), LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 HZ AC supply system, having bus bar chamber with insulated aluminium bus bars 250 Amps. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm thick CRCA MS sheet and 40x40x6mm thick angle iron frame work, powder coated finish, front opening type, with aprons for cable entry, with double door shutter and locking arrangements including provision of 65mm Godrej (Freedom) lock with 2 keys , internal wiring with PVC insulated, copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. Panel should be above ground level including dismantling existing old unserviceable feeder pillar complete all as specified and as directed (Loc - Main Power House). The scope of work includes the following:-
(b) Outgoing: (i) MCCB 4 pole 415 volts AC grade 125 Amp and 25 KA rupturing capacity -02 Nos (ii) MCCB 4 pole 415 volts AC grade 100 Amp and 16 KA rupturing capacity -02 No (iii) MCB SPN 63 Amp rating -03 No
(c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15mm in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road level. Note : All out going feeders shall be connected by cable through suitable size gland plate / glands.
Supplying, installing, testing and commissioning, factory made and tested (incl CPRI type test certified), LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 HZ AC supply system, having bus bar chamber with insulated aluminium bus bars 250 Amps. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm thick CRCA MS sheet and 40x40x6mm thick angle iron frame work, powder coated finish, front opening type, with aprons for cable entry, with double door shutter and locking arrangements including provision of 65mm Godrej (Freedom) lock with 2 keys , internal wiring with PVC insulated, copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. Panel should be above ground level including dismantling existing old unserviceable feeder pillar complete all as specified and as directed (Loc - MM range Pump House). The scope of work includes the following:-
(b) Outgoing: (i) MCCB 4 pole 415 volts AC grade 63 Amp and 16 KA rupturing capacity -02 Nos (ii) Star Delta Starter upto 10HP monoblock pump-02 Nos (iii) MCB TPN 63 Amp rating -01 No (iv) MCB SPN 40 Amp rating -01 No
(c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15mm in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road level. Note : All out going feeders shall be connected by cable through suitable size gland plate / glands.
M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.3mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below normal ground level, connected to galvanised earth lead of GI wire of size 4mm dia by means of GI Bolts, Nuts, check nuts and washers of the earth and thimbles and other end of the earth wire connected to earthing test point and protected by galvanised iron pipe light grade 15mm bore from earth plate to Panel/DBs and water pipe 20mm bore GI medium grade raised up to a level of 50cm above ground level with plug at top, earthing pit in PCC (1:3:6) type C-1 RCC pre-cast (1:2:4 type B-1) cover slab of 50 mm thick using 8.00mm dia CTD bars reinforcement both ways at 140 mm centre to centre with handle, 20 mm bore GI pipe medium grade for watering pipe, wire mesh, funnel and providing charcoal or coke and salt in alternative layers of 15 cm including necessary earth work in soft/ loose soil, returning, refilling and removing of surplus soil to a distance not exceeding 50 mtr testing complete all as shown in electrical plate No-3 of MES Schedule Part-I of SSR-2009 complete all as specified and directed, including taking down existing unserviceable earthing complete all as specified and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.3mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below normal ground level, connected to galvanised earth lead of GI strip of size 32x6mm by means of GI Bolts, Nuts, check nuts and washers of the earth and thimbles and other end of the earth strip connected to earthing test point and protected by galvanised iron pipe light grade 50mm bore from earth plate to Panel/DBs and water pipe 20mm bore GI medium grade raised up to a level of 50cm above ground level with plug at top, earthing pit in PCC (1:3:6) type C-1 RCC pre-cast (1:2:4 type B-1) cover slab of 50 mm thick using 8.00mm dia CTD bars reinforcement both ways at 140 mm centre to centre with handle, 20 mm bore GI pipe medium grade for watering pipe, wire mesh, funnel and providing charcoal or coke and salt in alternative layers of 15 cm including necessary earth work in soft/ loose soil, returning, refilling and removing of surplus soil to a distance not exceeding 50 mtr testing complete all as shown in electrical plate No-3 of MES Schedule Part-I of SSR-2009 complete all as specified and directed, including taking down existing unserviceable earthing complete all as specified and directed.
S&F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc as required 32 x 6 mm galvanised iron strip complete all as specified and directed.
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 sq m on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and directed.
Excavating in trenches, not exceeding 1.5 m wide and exceeding 1.5 meter but not exceeding 3.00 metre depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 sq m on plan and getting out in soft/ loose soil complete all as specified and directed.
Returning, filling in, riddled soil including spreading levelling, watering and well ramming in layers not exceeding 25cm using soil obtained from excavation after the pipes/ fittings are laid/ fixed jointed and tested complete all as specified and directed.
Removing excavated soil material from site to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr from the starting point complete all as specified and directed.
M&L for PCC (1:3:6) type C-2 with using 40mm graded stone aggregate as in foundation of steel tubular poles and stay with necessary form work as required complete all as specified and directed.
M&L for PCC (1:2:4) type B-1 with using 20mm graded stone aggregate as in coping of steel tubular poles with necessary form work as required complete all as specified and directed.
M&L for high density polyethylene pipes (HDPE) of 50 mm bore of pressure rating 6 kgf/cm2 for cable protection laid in trenches complete all as specified and as directed.
M&L for high density polyethylene pipes (HDPE) of 40 mm bore of pressure rating 6 kgf/cm2 for cable protection laid in trenches complete all as specified and as directed.
M&L for high density polyethylene pipes (HDPE) of 90 mm bore of pressure rating 6 kgf/cm2 for cable protection laid in trenches complete all as specified and as directed.
M&L for high density polyethylene pipes (HDPE) of 25 mm bore of pressure rating 6 kgf/cm2 for cable protection laid in trenches complete all as specified and as directed.
Taking down existing unserviceable street lights/ flood lights fittings, including necessary disconnection of electric connection and removing from site and deposited to MES store complete all as specified and directed.
Taking down existing unserviceable street light bracket from pole along with clamps, nut & bolt and removing from site and deposited to MES store complete all as specified and directed.
S&F street light bracket of length 1.20 metre made of GI pipe medium grade 25 mm bore dia., bend to shape to fix on LT poles including MS clamps, nuts, bolts, painting with synthetic enamel paint etc including taking down old unserviceable street light bracket from pole, complete all as specified and directed.
Supply and fixing LED street light fitting 50 Watt 230 Volt, AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including connecting with 2 core PVC insulated copper cable of suitable size complete all as specified and directed. Make : Goldmedal (GL90803) or equivalent in Jaquar / Philips / Bajaj / Wipro / Osram / GE / Havells / HPL/ Halonix/ Surya/CG/Luker/Surya/CS
Supply and fixing LED street light fitting 70 Watt 230 Volt, AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including connecting with 2 core PVC insulated copper cable of suitable size complete all as specified and directed. Make : Goldmedal (GL90804) or equivalent in Jaquar / Philips / Bajaj / Wipro / Osram / GE / Havells / HPL/ Halonix/ Surya/CG/Luker/Surya/CS
Taking down existing unserviceable flood lights from high mast light including necessary disconnection of electric connection and removing from site and deposited to MES store complete all as specified and directed.
Supply and fixing LED flood light 100 watt 230 Volt, AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. Make : Goldmedal (GL90862) or equivalent in Jaquar / Philips / Bajaj / Wipro / Osram / GE / Havells / HPL/ Halonix/ Surya/CG/Luker/Surya/CS
Supply and fixing (High mast light) Phantom LED flood light 100 watt 240 Volt, AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. Make : Goldmedal (GPOFAAS100L01CD) or equivalent in Jaquar / Philips / Bajaj / Wipro / Osram / GE / Havells / HPL/ Halonix/ Surya/CG/Luker/Surya/CS
Supply and fixing (High mast light) Phantom LED flood light 150 watt 240 Volt, AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. Make : Goldmedal (GPOFAAS150L01CD) or equivalent in Jaquar / Philips / Bajaj / Wipro / Osram / GE / Havells / HPL/ Halonix/ Surya/CG/Luker/Surya/CS
Supply and fixing (high mast light) Phantom LED flood light 200 watt 240 Volt, AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. Make : Goldmedal (GPOFAAS200L01CD) or equivalent in Jaquar / Philips / Bajaj / Wipro / Osram / GE / Havells / HPL/ Halonix/ Surya/CG/Luker/Surya/CS
Taking down existing unserviceable post top/ gate light fittings/ decorative light fittings, including necessary disconnection of electric connection and removing from site and deposited to MES store complete all as specified and directed.
Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed.
S&F in repairs 3 core, 1.5 Sqmm, PVC copper cable, multistranded, drawn through inside pole from the bottom connector to fittings by providing necessary lugs including taking down the existing wire, complete all as specified and directed.
S&F sheet metal enclosure for DB, SPN, 2 way single door, 240Volt when MCB to be used for on/off post top lights including taking down old DBs complete all as specified and directed.
S&F in repairs SMC terminal box of size 273 x 136 x 113 mm (internal dimensions) made of impact resistance plastic & heat resistant materials including MCB SP 6A with DIN bar and 4 way terminal block, and fixing the box to street light pole with 25x3mm flat iron clamps, nuts and bolts complete all as specified and directed.
S&F in repairs LED driver for LED street light fitting with surge protection upto 10kV of make suitable for LED fitting of make BAJAJ / WIPRO / PHILIPS / CROMPTON of capacity upto 80 Watts complete all as specified and directed.
S&F in repairs digital electronic analogue time switch (with battery backup), 01 module, 40 Amp, 3 Pole, 230 Volt including taking down old/unsv items complete all as specified and directed. Make: INDOASIAN cat No. TL040080 or equivalent make in ABB / Havells / L&T / C&S
S&F smart integrated solar LED street light fittings with in built in mono crystalline panel, lithium Ferro phosphate battery, MPPT charge controller and PIR sensor with colour temp 6000-6500K, 2 days autonomy including connecting, testing with drimming profile complete ass as specified and directed. Make : Bajaj (BSEZSL 30W, all in std) or equivalent in Jaquar / Philips / Goldmedal / Wipro / Osram / GE / Havells / HPL/ Halonix/ Surya/CG/Luker/Surya/CS
Fixing only LED street light of any wattage complete all as specified and directed . Note : The item shall be issued under Schedule B Store, The contractor should collect the LED street light from E/M store yard and re-fix the same and old light should be deposited to MES yard
Laying of service wire/cable of any size from pole to pole for street light complete all as specified and directed . Note : The item shall be issued under Schedule B Store, The contractor should collect the wire/cable from E/M store yard and re-fix the same and old cable should be deposited to MES yard
SUJAN (BID ID -3395986)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3403591)
Jack Electrolinks Private Limited (BID ID -3395949)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .