PROVN OF 250 KVA TRANSFORMER ALONGWITH ALL CONNECTED WORKS AT SFF ACADEMY EST-22, THROUGH MES DEHRADUN
2026_MES_754386_3
0223/CHK/E8
Open Tender
Electrical and Maintenance Works
180 days
Chakrata
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
AGE (I) Chakrata
₹1.1 L
Yes
5 Jun 2026
5 Jun 2026
22 Jun 2026
5 Jun 2026
19 Jun 2026
13 Jun 2026
Supply, installation testing and commissioning of factory made 11 KV Compact Sub Station (CSS) with non extendable RMU consisting of 1 No manually operated 11 KV/400 Amps VCB in SF6 insulated stainless enclosure, HT Cable/Bus bar 630A,1 No, Transformer 250 KVA, 11/0.433 KV CRT dry type air cooled and LT switchgear complete in accordance with IEC: 62271-2021 & associated LT devices, Fault making capacity 52.5 KA/ Sec,Power frequency 1 min : 28 kV, Input range +5% to -5%, HV Current 13.12 Amps and LV Current 333 Amps, Star / Delta connection, 3 phase, and off load tap changeover, 5 Steps , Losses at No Load- ECBC Losses at 100% Efficiency at full load 98.3%, Average Amb Temp 50 degree C, HV & LV Winding - Copper Wound,Winding temp – 95 degree C above ambient comprising of and including the following :- (Applicable standards and testing for the above specifications and Hence, will be as per IS-11171;2021, IS-2026 (part I-11), IEC-6007-11, ECBC losses- Latest).
Enclosure (i) Outdoor type 2 mm thick galvanised iron (GI) enclosure with 4 mm thick GI base, powder coated. Roof shall be designed to support load upto 250kg/ sqm with suitable slanting (approx 10 degree) to prevent accumulation of water. Partition between compartments with 2 mm thick GI sheet (ii) Door with locking arrangement at suitable positions for easy operation and maintenance of all the components (iii) Suitable provision for HT and LT cable entry and S&F at site double compression cable glands for each cable entry (iv) Suitable LED illumination lamp with door operated switch for each compartment Integral lifting arrangement. Appropriate Danger notice plates at all sides and on each compartment (v) Protection grade IP 54 for HT & LT switchgear compartment and IP 34 for transformer compartment (vi) Type tested against Internal Arc at 21 kA for 01 second duration (vii) Suitable louvers designed for natural ventilation and thermal class K10
HT Section (i) 01 No VCB SF6 insulated consisting of 11 KV 630 Amps 50 Hz Vacuum Circuit Breaker (motorised) - 01 VCB and cable box with direct Raiser as per IEC 62271 and other relevant IS/ IEC standards (ii) Copper Busbar of suitable size-01 set (iii) Vacuum Circuit Breaker shall be suitably rated to withstand max 28 KV (RMS) at rated power frequency and lightning impulse withstand voltage 75 KV peak. It should have short circuit withstand capacity 21 KA for 3 seconds and internal arc withstand capacity 21 kA for 0.1 second. (iii) Self powered microprocessor electronic based numerical relay (with LCD display.and manual reset type) for protection against over current, earth fault, short circuit and transformer winding temperature increase. (iv) Current Transformers for 03 phases (03 Nos) with ratio : 200/5A,Class 1.0/10P10, Burden 15-15 VA. (v) Three position (Open, Close & Earth) independent operation Disconnector Switch (vi) Fault passage indicator (vii) Mechanical operation interlock (viii) Operation counter
(ix) Emergency Push button (x) Shunt Trip Coil suitably rated (xi) Manual Operating Handle (xii) Automatic motorised Spring Charging mechanism alongwith facility for manual spring charging handle / motor (xiii) Thermostatically controlled space heater of suitable rating connected through MCB and mounted by suitable spacers so that heater does not come in contact with panel wall or panel accessories. (xiv) Cable Boots suitable for 3C x 95 Sqmm for incoming and 3 x 1C x 95 sqmm for outgoing
(xiv) HT Metering Module comprising of (A) Potential Transformers for 03 phases with ratio: 11 KV/√3/110V/√3/110V/√3, class 0.5-3, Burden 50-50 VA earthed (B) Three phase LED multi-function meter for indication of Current, Voltage, Frequency, Power Factor, KW, KVA, KVAR, KWH, KVAH, KVARH, MD, fault data memory etc (C) Suitable Battery with battery charging unit alongwith suitable circuit for standby connection/ operation of control/ protection circuits (D) Suitable size and numbers of MCBs, Limit Switches and control wiring as per OEM (E) Suitable Alarm for trip indication (F) LED indicator lamps fot indicating "ON", "OFF", "TRIP", "EARTH", "TRIP CKT HEALTHY"
Transformer (i) 11 KV/ 433 V, 250 KVA, 3 phase, 50 Hz epoxy cast resin CRT dry type copper wound transformer with vector group DYN11 as per IS:11171 : 2026 (Pt-I) - 2021 or as recommended by OEM of CSS and subsequently approved by dept (ii) Off load tap changer with +5% to -10% in steps of 2.5% (iii) Winding temperature indicator with alarm and trip arrangement (iv) Losses as per latest relevant IS / ECBC.
LT Section (i) Incoming Air Circuit Breaker 415 volt grade 630 Amps, 4 pole, 50 kA, manual fixed (MF) type microprocessor release with overload, short circuit, earth fault, over and under voltage protection, High short time withstand capacity Icu = Ics = Icw for 1 sec, 100% rated neutral pole, Test button for on-load testing complete (ii) Copper busbar 500 Amp rated for main bus and suitable copper busbar for main bus to incoming side of MCCBs and internal control wiring with copper cables (iii) Three phase multi-function with LED display meter for indication of Current, Voltage, Frequency, Power Factor, KW, KVA, KVAR, KWH, KVAH, KVARH, fault data memory etc (iv) Current Transformers for 03 phases (03 Nos) with ratio : 630/5 A, 5 VA, class 1.0 (v)) Phase indicator LED lamps R, Y, B
Interconnection (i) RMU to transformer with 3 run of single core 95 sqmm copper conductor duly PVC 11KV insulation sleeve and other necessary accessories (ii) Transformer to LT Panel incomer with copper busbar 1000 amp duly PVC insulation sleeve (iii) Earth continuity conductor between integral components with 50 x 6 mm GI strip (iv) Suitable termination points for connecting external earth strips to the CSS
Excavation in trenches in hard / dense soil n exc 1.5 metre wide and not exc 1.5 metre deep and getting out including forming bottom surface for laying HT cable, foundations etc complete all as specified and directed.
Excavation in trenches in hard / dense soil n exc 1.5 metre wide but exceeding 1.5 metre and not exc 3.0m deep and getting out including forming bottom surface for laying underground cable, foundation for poles etc complete all as specified and directed.
Returning filling in including spreading levelling watering and well ramming in layer not exceeding 25 cm thick complete all as specified and directed.
Removing excavated material n.exc 50 m and depositing where directed at a level n exc 1.5 metre above the starting point complete all as specified and directed.
Supply, laying of DWC (double Wall corrugated) HDPE polyethiline pipe of size outer dia 120 mm and inner dia 103.5 ISI marked including couplers, bends, cap etc. with smooth internal and profiled external surface for non pressure under ground cable complete all as secified and directed.
M & L for making horizontal bore by suitable means for insertion of GI pipe 80 mm bore for passing cable across the road without cutting the road complete all as specified & directed.
M & L for 80mm bore galvanised tubing light grade laid in trenches or fixed to pole and / or laid under road in any position with necessary clamp nut and bolt etc for cable protection complete all as specified & directed.
Supply, laying, connecting and testing XLPE HT underground insulated (Earthed) screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavyduty) with stranded aluminium conductor, 11000 volts grade, cross sectional area 95 sqmm, 3 core conforming to IS-7908(Part-I)1988, laid in trenches/down through pipe fixed to walls/poles or laid under roads/drains/path/culverts complete all as specified and directed. (Note : Excavation & earth work, sand, cable protection shall be measured and paid seperately).
M & L for cable jointing kit for 11 KV grade (Earthed) HT cable for outdoor end termination heat shrinkable type complete with jointing material and accessories suitable for 95 sqmm 3 core XLPE armoured aluminium conductor cable of following sizes complete all as specified and directed.
Supply, laying, connecting and testing XLPE insulated armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 185 Sqmm, 3.5 core complete all as specified and directed.
Supply, install, test and commissioning of LT Panel, TPN 415 Volts, 50 Hz, outdoor cubical type floor mounted CPRI approved factory made, double door dust and vermin proof IP-54, fabricated out of CRCA sheet not less than 3.15 mm thick with 2 mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50 x 50 x 6 mm with cable chamber for individual feeders for incoming and outgoing connections, one set of LED indicator lamp RYB with switch and fuse and the panel board shall be provided with proper ventillation including suitable size of cable alley copper bus bar suitable for carrying of Aluminium suitable bus bar suitable Amps rating, 3 Nos for phases and one No for neutra with suitable connections from MCCB outgoing to main bus bar shall be carried out with TPN copper bus bars of suitable rating and connections from main bus bar to outgoing MCCB's (intake point) will be carried out with TPN copper bus bar as per MCCB rating duly insulated all MCCB with ICS=100% ICU, adjustable thermal - 0.8-1 In, adjustable magnetic-5 mounted on suitable size o bridge insulator including necessary PCC foundation of minimum 0.35 m height positioned and ixed with suitable nut, bolts, washers etc to the MC pedestal complete all as specified and directed.
In coming (a) MCCB 4 pole 415 V 40 Amps 50KA - 01 No
Out going (a) MCCB 4 pole 415 V 250A (36 KA) - 01 Nos (b) MCCB 4 pole 415 V 125 A (16 KA) - 01 Nos (c) MCCB 4 pole 415 V 100 A (16 KA) - 01 Nos (d) MCCB 4 pole 415 V 63 A (16 KA) - 01 Nos (e) Astronomical timer switch 415 V three phase of rating 20 A with contactor fitted inside steel enclosure & digital multifunction meter with auto ON/OFF -01 Nos (f) Three phase LED multifunction meter for indication of current, Voltage, Frequency, Power factor, KW, KVA, KSAR, KWH, KVARH etc -01 set (g) Phase indicator (RYB), LED type -01 set of three (h) Aluminium suitable bus bar suitable Amps rating , 3 Nos for phases and one Nos for neutral of half capacity.- 01 set
M&L for provn of transformer Platform of size 3.0x3.0x1m high from ground level including excavation and earth work in trenches in any type of soil, PCC 1:5:10 type E-2 for foundation, brick work in CM 1:6, PCC 1:2:4 type B-1 as in coping, plaster of 10mm thick in CM 1:6 on brick surface , complete with 75mm thick PCC 1:4:8 type D-2 as in sub base of floor with topping of PCC 1:2:4 type B-1, 100mm thick in floor and finished even and fair (without using extra cement) including returning, filling in and removal of surplus spoil to a distance n.exc 50m including chain link fencing 1.8 m height made out of 4mm dia GI wire 150 x 100 mm mesh with mild steel angle iron 50 x 50 x 6mm as in fencing post and embedded in PCC 1:2:4 type B-1, 30 x 23 x 30cm block at 1.5 mtr interval each side as approved with 1 No steel gate (3.5 m clear) span with locking arrangement made out of 15mm dia mild steel rod 50x50x6mm angle iron frame and painting the steel surface with 2 coats of aluminium paint over a coat of red oxide primer and 3 coats of white washing on cement work including ISMB 100mm channel 02 Nos for fixing transformer, complete all as specified and as directed.
Supply, erecting and fixing steel tubular swaged pole 11 m long Type -410 SP-55 conforming to IS-2713 part I to III 1980 with and including cast iron base plate, finial taper plug,nuts, bolts and washers etc. and fixed into plain cement concrete foundation duely painted with two coats of aluminium paint over one coat of red oxide primer including preparetion of surfaces and making strip 150mm wide upto 1.50m( above PCC coping) by black , yellow paint in alternate layers and pole nos. complete all as specified and directed. Note : Earth work, PCC will be measured and paid seperately.
M & L for vertical isolation air break gang operated switch HT 11 KV triple pole mechanically operated out door type and rated capacity 200 Amp with 9 insulator and steel frames mechanically operated mechanism consisting of three male contacts & three female contacts of tinned copper, three arching horns, three MS jumper carrier equipped with braided copper belt , operating rod of heavy grade 32/25mm bore GI pipe of suitable length worked from ground level with locking arrangement with clamp of flat iron 50X6 mm and testing after installation complete all as specified and directed.
M & L for Cross arms bracing supports clamps and back plate fabricated from structural steel section including nuts bolts washers welding bending cold or hot drilling holes for bolts in any shape & size as indicated or directed and including of one primer coat one under coat one finishing coat with aluminium paint complete all as per specified and directed.
M & L for anti climbing device on HT/LT poles comprising of 2.24 mm dia galvanised steel 2 strand barbed wire with 2 mm dia wire wrapped spirally around poles to a length of 0.5 to1.0 metre clamped and properly secured all as directed.
M&L for Lightening arrestor single pole zinc oxide (gap less) surge type heavy duty complete with all fittings, station class, discharge capacity 10 KA for 11 KV, 50 Hz conforming to IEC 99-4/1991 standard complete all as specified and directed.
S&F Aluminium conductors, reinforced (ACSR) conductor of any size for as per site requirement including stretching, binding with aluminium binding wire, jumpers, line taps etc complete all as specified and directed.
S&F expulsion fuse assembly single pole vertically mounted on MS channel 11000 volts grade above 25A & upto 50 Amps capacity including making connections with HT cables/GOD with provision of jumper suitable crimped/fixed with appropriate size of lugs/connectors complete all as specified and directed.
S&F pin type, procelain, vitreous white,brown or green insulator including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, 150mm height, 150 mm dia, 11000 Volts grade, complete all as specified and as directed.
S&F 'Two in series' disc assembly with disc type insulator, procelain, vitreous, 145 mm high and 255 mm dia ball and socket type, white, brown or green with tension clamps for conductors with working presure 11000 Volts, complete all as specified and as directed.
M & L for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled/ painted white with letters figures and conventional skull and bones in signal red colour and fixed with M.S. clmps , bolts and nuts of approved size, for HT of size 25 X20 cm complete all as specified and directed.
S&F RCC cable route indicator (75x75x600mm) with base foundation 300 x 300 x 400 mm depth below ground level, embossed with letters " MES 11 KV HT" complete all as specified and directed.
M & L for PCC (1:3:6) type C-2 (using 40 mm graded crushed stone aggregate) as in foundation for pole and stay, filling in and mass concrete complete all as specified and directed.
M & L for PCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) as in coping of pole etc including form work complete all as specified and directed.
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SSR Part I all as specified and testing on completion including provision of earth lead protected by 50 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc complete. Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 20mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 50x50 cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade and charcoal & salt around earth plate in alternate layers of 15 cm [v]. GI protection pipe of size 50 mm bore light grade upto 7.5 m complete all as per specified and directed.
M & L for earthing complete with copper earth plate 600 x 600 x 3mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to copper strip of size 20X3 mm by means of bolts, nuts, check nuts and washers as per SSR Part I all as specified and testing on completion including provision of earth lead protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc complete. Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 40mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 50x50 cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade and charcoal & salt around earth plate in alternate layers of 15 cm [v]. GI protection pipe of size 40 mm bore light grade upto 7.5 m complete all as per specified and directed.
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth wire of 4mm dia by means of bolts, nuts, check nuts and washers as per SSR Part I all as specified and testing on completion including provision of earth lead protected by 15 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc complete. Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 40mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 50x50 cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade and charcoal & salt around earth plate in alternate layers of 15 cm [v]. GI protection pipe of size 15 mm bore light grade upto 7.5 m complete all as per specified and directed.
Please Enable Macros to View BoQ information
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.56 MB
0223_Tender.pdf
Tender Documents • 1.40 MB
BOQ_862324.xls
BOQ • 19.16 MB
SecurityForm.pdf
Additional Documents • 0.40 MB
Download all tender documents and submit your bid