Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.8 CrAdmitted-Finance | ₹2.8 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.9 Cr+₹14.7 L (5.29%)Admitted-Finance | ₹2.9 Cr+₹14.7 L (5.29%) | L2 | Admitted-Finance |
| 3 | L3₹2.9 Cr+₹16.5 L (5.93%)Admitted-Finance 6 573D BHASKARA BUILDING NADAKKAVU P O UDAYAMPEROOR ERNAKULAM KERALA 682307 | ERNAKULAM | KERALA | 682307 | ₹2.9 Cr+₹16.5 L (5.93%) | L3 | Admitted-Finance |
| 4 | L4₹3.1 Cr+₹32.2 L (11.6%)Admitted-Finance | ₹3.1 Cr+₹32.2 L (11.6%) | L4 | Admitted-Finance |
| Sl No | Description | Qty | Unit | YOOSAF K A L1 | Delstar a Grade Electrical contractors L4 | BPE BHARATH POWER ENGINEERS PVT LTD L3 | POWERRADIANCE L2 |
|---|---|---|---|---|---|---|---|
| 1.00SUB POWER PANEL | |||||||
| 2.00 | Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-250A Microproceesor based MCCB 1 Nos, Outgoings-160A Microproceesor based MCCB 3 Nos,125A Microproceesor based MCCB 3 Nos, Provision for cable duct- Incomer & Outgoing, Including RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs ,Multi Function Meter | 1 | nos | 5,12,000 ₹5,12,000 Lowest | 5,75,784 ₹5,75,784 | 5,43,966.78 ₹5,43,966.78 | 5,38,801.66 ₹5,38,801.66 |
| 3.00SEYPA PANEL | |||||||
| 4.00 | Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-400A FP MCCB1 Nos, Outgoing- 250A TPN MCCB 7 Nos, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc | 1 | nos | 5,20,000 ₹5,20,000 Lowest | 5,84,781 ₹5,84,781 | 5,52,466.2 ₹5,52,466.2 | 5,47,221 ₹5,47,221 |
| 5.00UTILITY PANEL | |||||||
| 6.00 | Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-630A FP MCCB1 Nos, Outgoing- 400A TPN MCCB 1 Nos,250A TPN MCCB 6 Nos,200A TPN MCCB 2 Nos Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc | 1 | nos | 5,47,800 ₹5,47,800 Lowest | 6,16,044 ₹6,16,044 | 5,82,001.9 ₹5,82,001.9 | 5,76,476 ₹5,76,476 |
| 7.00OFFICE PANEL | |||||||
| 8.00 | Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-400A FP MCCB1 Nos, Outgoing- 160A TPN MCCB 5 Nos,125A TPN MCCB 2 Nos, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc | 1 | nos | 4,56,000 ₹4,56,000 Lowest | 5,12,808 ₹5,12,808 | 4,84,470.4 ₹4,84,470.4 | 4,79,871 ₹4,79,871 |
| 9.00SUB PANEL | |||||||
| 10.00 | Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-250A FP MCCB1 Nos, Outgoing- 125A TPN MCCB 2 Nos,100A TPN MCCB 4 Nos, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc | 4 | nos | 4,02,000 ₹16,08,000 Lowest | 4,52,081 ₹18,08,324 | 4,27,098.95 ₹17,08,395.8 | 4,23,044 ₹16,92,176 |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
30 Oct 2025, 4:00 pmClosed
Manager (Electrical Projects)
KEL MAMALA KOCHI
RENOVATION OF OUTDATED ELCTRICAL WIRING SYSTEM, HT, LT PANEL AND OTHER ELECTRICAL INSTALLATION IN KBPS (PHASE 2-GENERAL ELECTRICAL WORK)
2025_KEL_813345_1
KEL/KMEP/EPROC/040/2025-26
Open Tender
Electrical Works
Item Rate
KEL MAMALA
Please refer Tender documents.
6 documents required · 6 mandatory
₹7,500
₹1 L
Yes
1 Nov 2025
23 Oct 2025
31 Oct 2025
23 Oct 2025
30 Oct 2025
23 Oct 2025
23 Oct 2025 - 30 Oct 2025
Amount
SUB POWER PANEL
Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-250A Microproceesor based MCCB 1 Nos, Outgoings-160A Microproceesor based MCCB 3 Nos,125A Microproceesor based MCCB 3 Nos, Provision for cable duct- Incomer & Outgoing, Including RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs ,Multi Function Meter
SEYPA PANEL
Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-400A FP MCCB1 Nos, Outgoing- 250A TPN MCCB 7 Nos, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc
UTILITY PANEL
Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-630A FP MCCB1 Nos, Outgoing- 400A TPN MCCB 1 Nos,250A TPN MCCB 6 Nos,200A TPN MCCB 2 Nos Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc
OFFICE PANEL
Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-400A FP MCCB1 Nos, Outgoing- 160A TPN MCCB 5 Nos,125A TPN MCCB 2 Nos, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc
SUB PANEL
Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-250A FP MCCB1 Nos, Outgoing- 125A TPN MCCB 2 Nos,100A TPN MCCB 4 Nos, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc
BINDING HALL PANEL
Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-630A FP MCCB1 Nos, Outgoing- 200A TP MCCB 5 Nos,160A TP MCCB 3 Nos, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc
LOTTERY POWER PANEL
Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-200A FP MCCB1 Nos, Outgoing- 125A TPN MCCB 3 Nos,100A TPN MCCB 3 Nos, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc
LSB PANEL
Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. All incomers and outgoings shall be labelled. Incomer-200A TPN MCCB1 Nos, Outgoing- 125A TP MCCB 8 Nos,, Provision for cable duct- Incomer & Outgoing, Including EFR, MFM, REF, RYB Indications, V, A , F, KWH,KVA, PF with Control MCBs etc
LT CABLES
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 3.5C x 400 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works.3.5C x 300 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works.3.5C x 185 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 3.5C x 150 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 3.5C x 120 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works.3.5C x 95 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works.3.5C x 70 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 3.5C x 50 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 3.5C x 35 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 3.5C x 25 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 4C x 16 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 4C x 10 Sq.mm Al. cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works. 6C x 1.5 Control Cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works.4C x 1.5 Control Cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works.2C x 2.5 Control Cable
Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium / Copper cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 50cm and pulling through pipes including all minor civil works.3C x 1.5 Cu Cable
GLANDING AND TERMINATION
3.5C x 400 Sq.mm Al. cable
3.5C x 300 Sq.mm Al. cable
3.5C x 185 Sq.mm Al. cable
3.5C x 150 Sq.mm Al. cable
3.5C x 120 Sq.mm Al. cable
3.5C x 95 Sq.mm Al. cable
3.5C x 70 Sq.mm Al. cable
3.5C x 50 Sq.mm Al. cable
3.5C x 35 Sq.mm Al. cable
3.5C x 25 Sq.mm Al. cable
4C x 16 Sq.mm Al. cable
4C x 10 Sq.mm Al. cable
6C x 1.5 Control Cable
4C x 1.5 Control Cable
2C x 2.5 Control Cable
3C x 1.5 Cu Cable
DB, ENCLOSURE AND ITS ACCESSORIES
OD21069/2025-2026 Supply and installation of Termination box with Terminal connector and complete the work as required
OD21070/2025-2026 Supply and installation of 250A SFU with Enclosure and complete the work as required
OD21071/2025-2026 Supply installation testing and commissioning of 63A Isolator with SS Enclosure and complete the work as required
OD21072/2025-2026 Supply installation testing and commissioning of 100A Isolator with SS Enclosure and complete the work as required
OD21073/2025-2026 Supply installation testing and commissioning of 125A Isolator with SS Enclosure and complete the work as required
90.11.1.16 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.20 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.3.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
OD21078/2025-2026 Supply and fixing following rating, four pole, (three phase and neutral), 415V, Residual Current Circuit Breaker (RCCB), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A 100mA
OD21079/2025-2026 Supply and fixing following rating, four pole, (three phase and neutral), 415V, Residual Current Circuit Breaker (RCCB), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A 100mA
OD21089/2025-2026 Supply and fixing following rating, four pole, (three phase and neutral), 415V, Residual Current Circuit Breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A 30mA
OD21090/2025-2026 Supply and fixing following rating, four pole, (three phase and neutral), 415V, Residual Current Circuit Breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A 30mA
OD21091/2025-2026 Supply and fixing following rating, four pole, (three phase and neutral), 415V, Residual Current Circuit Breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A 30mA
2.13.2 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.13.1 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.12.2 Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.12.1 Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.1 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
OD21104/2025-2026 Supplying and fixing following rating, two pole, 230 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 32A
GENERAL ELECTRIFICATION
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.. (Note:The total distance from the DB/switch box to the point will not exceed 5mtr, incase if length increases above 5 metres, the wiring shall be measured under item Circuit wiring) (office area)
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
1.33 Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.24.3 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.21.1 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 nos 3 pin 5/6 A modular socket outlet and ons nos 5/6 A modular switch, connections etc. as required.
1.32: Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,IP 66 enclosed plug top alongwith 20 amps "C" curve, SP, MCB, in the IP66 enclosure, on surface or in recess,complete with connections, testing and commissioning etc. as required
EARTHING CONDUCTORS
25mm*6 mm GI Strip
25mm*3 mm GI Strip
EARTHING BENCH
Supply and clamping 30cm tinned Cu. Earth bench of the following sizes on the surface of wall for connecting earth continuity leads at required locations. 25 x 6 mm
Supply and clamping 30cm tinned Cu. Earth bench of the following sizes on the surface of wall for connecting earth continuity leads at required locations.25 x 3 mm
CABLE TRAY
Supplying and installing following size of perforated Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Iron cable tray “bends” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Iron cable tray “bends” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Iron cable tray “bends” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Iron cable tray “Tee” (galvanisation not less than 50microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required 100 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Iron cable tray “Tee” (galvanisation not less than 50microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required 150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Iron cable tray “Tee” (galvanisation not less than 50microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required 300 mm width X 50 mm depth X 1.6 mm thickness
Light, Fan and Exhaust
Supply,Installation, testing and commissioning of High bay type fittings wattage of 80W on wall/Column/truss/false ceiling using suitable MS clamps, nuts, bolts/ 20mm heavy duty GI chain/ pipe (upto 50cm)etc including connections with 3C 1.5 Sq.mm PVC insulated flexible copper conductor cable as required.Make-CIP-323-80-57-60D-HL2-LM-NGG or Equivalent approved make
Supply,Installation, testing and commissioning of High bay type fittings wattage of 120W on wall/Column/truss/false ceiling using suitable MS clamps, nuts, bolts/ 20mm heavy duty GI chain/ pipe (upto 50cm)etc including connections with 3C 1.5 Sq.mm PVC insulated flexible copper conductor cable as required.Make-CIP-328-120-57-60D-HL2-LM-NGG or Equivalent approved make
Supply, Installation, testing and commissioning of industrial surface mounted LED batten and lamp with Poly Carbonate Body and PolyCarbonate Diffuser, IP-65 rated fixture along with driver ,system wattage of 40+/-4 Watts,lumen output of lamp greater than 3600 lumen, power factor >= 0.9 including all necessary accessories as required complete.Make:-CIS-301-40-57-HL3-DP-NGR or equivalent approved make
Supply,Installation, testing and commissioning of of 2x2 LED recess mounted fixture with Aluminium body with a high efficiency diffuser along with driver,system wattage 36+/-4 Watts,lumen output of lamp greater than 3500 lumens, power factor >= 0.9, including all necessary accessories as required complete. Make LCTLRNE-36-FO-CDL or equivalent approved make
Supply and fixing of LED outdoor floodlight luminaire. The fixture shall be of IP66 protected, pressure die cast aluminium housing body with optimal heat sink, with system wattage less than 50 (+/-5)W with rated life of L70 @ 50,000 hours, CRI greater than or equal to 70 & with system lumens greater than 10000 lumen and system efficacy greater than or equal to 95%.
Supply and fixing of LED outdoor floodlight luminaire. The fixture shall be of IP66 protected, pressure die cast aluminium housing body with optimal heat sink, with system wattage less than 100 (+/-5)W with rated life of L70 @ 50,000 hours, CRI greater than or equal to 70 & with system lumens greater than 10000 lumen and system efficacy greater than or equal to 95%.
Supply and fixing of 450 mm size wall mounting oscillating type fan having three speed control, oscillation control at bottom and suitable for operation on single phase 230 volt, 50Hz AC supply complete with continuous duty motor, chrome plated front and rear gaurds and all accessories as required
Supply of 450 mm sweep,900 rpm heavy duty exhaust fan in metal body with louvers working on 230 V AC supply complete with all accessories as required.
Supply of 250 mm sweep,900 rpm light duty exhaust fan in plastic body with self opening louvers working on 230 V AC supply complete with all accessories as required.
90.4.5.4 Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
MS STRUCTURALS
Supply, fabrication and installation of cable tray and supports using M.S angles and plates of adequate size painted with one coat of epoxy primer and two coats of epoxy grey paint.
DOCUMENTATION
OD21174/2025-2026 Preparation of scheme drawings and getting approval from Electrical Inspectorate. Submission of completion report, arranging inspection and obtaining Sanction Order from Electrical Inspectorate . (*All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission of supporting documents).
OD21177/2025-2026 LIAISONING WORKS INCLUDING SUPERVISION CHARGES @10%/Shop drawing/as-built drawing/O&M manual
EXCLUSIVE OF GST
POWERRADIANCE (BID ID -2415005)
BPE BHARATH POWER ENGINEERS PVT LTD (BID ID -2414859)
Delstar a Grade Electrical contractors (BID ID -2414698)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
BOQ_1359704.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .