Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.0 LAccepted-AOC CHATHANATTU HOUSE XXIII 362B 1 AYYANKALI ROAD EDAKOCHI KOCHI 682 010 | KOCHI | ERNAKULAM | KERALA | 682010 | ₹33.0 L Quoted ₹34.8 L | L1 | Accepted-AOC L1 |
| 2 | L2₹35.8 LRejected-Finance MATTILIPARAMBIL HOUSE SAHODHARAN AYYAPPAN ROAD EROOR WEST PO THIRUPUNITHURA 682306 | THIRUPUNITHURA | ERNAKULAM | KERALA | 682306 | ₹35.8 L | L2 | Rejected-Finance NOT DUE TO BEING L1 AND REASONABLE |
| 3 | L3₹42.9 LRejected-Finance KATTUPADATH H AZHEEKAL P O VYPEEN KOCHI ERNAKULAM DIST KERALA 682 508 | KOCHI | ERNAKULAM | KERALA | 682508 | ₹42.9 L | L3 | Rejected-Finance NOT DUE TO BEING L1 AND REASONABLE |
| 4 | L4₹43.4 LRejected-Finance | ₹43.4 L | L4 | Rejected-Finance NOT DUE TO BEING L1 AND REASONABLE |
| Sl No | Description | Qty | Unit | Oriental Constructions L2 | ANIE JOHN CONTRACTORS L1 | MS BUILDERS L3 | JESWIN BUILDERS L4 |
|---|---|---|---|---|---|---|---|
| 1.00 | Attending complaint including transportion of tools for rectification of urgent nature of electrical complaints like checking of existing electrical items for continuous electric supply including carrying out such as minor repairs to ceiling fans / exhaust fans like replacement of capacitors, cleaning and oiling etc. as required to make the electrical items/ appliances fully functional at Kataribagh and Naval Base area at Naval Base during off hours (1700 hrs evening to 0900 Hrs morning ) on all working days all as specified and directed.
NOTE:-
(i) The contractor should display contact number at complaint cell to register users complaint.
(ii) The recovery of rupees 1000 per complaint will be charged if contractor failed to attend that in stipulated time period .
(iii) Number of complaints may vary day to day and shall be on required basis. Contractor shall quote their rates accordingly including in all aspects like labours,tool,transportation etc. | 200 | Per complaint | 180 ₹36,000 | 25 ₹5,000 | 150 ₹30,000 | 125 ₹25,000 |
| 2.00 | M&L for checking of ceiling fans stability (like fan hooks,nuts, bolts ,hanging rod ,canopy ,washer etc ) and exhaust fan stability at Naval base all as specified and directed.
Note: - 1. The contractor should prepare seperate registers at AGE E/M (NW) Kochi and enter office name with signature of offce incharge and submitted to Engineer in Charge. | 3,000 | Each job | 50 ₹1.5 L | 15 ₹45,000 | 25 ₹75,000 | 55 ₹1.6 L |
| 3.00 | Taking down fan, sealing cable end, dismantling blades, removing fan, painting of ceiling fans complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc and refixing ceiling fan (M.D.supply) and connecting up including provision of cable from ceiling rose or connector to fan complete all as specified and as directed. | 540 | Each Job | 110 ₹59,400 | 80 ₹43,200 | 125 ₹67,500 | 95 ₹51,300 |
| 4.00 | Taking down unserviceable ceiling fan of 1200mm/1400mm sweep, cutting out the existing burnt out fan motor winding, cleaning the motor slots, rewinding the motor with insulated copper winding wire of existing gauge, baking / heating up the motor to achieve the proper insulation resistance and refixing testing complete including marking MES No complete all as specified. | 540 | Each job | 300 ₹1.6 L | 400 ₹2.2 L | 400 ₹2.2 L | 475 ₹2.6 L |
| 5.00 | Ditto all as per item Ser No. 4 above but exhaust fan of 450/300/250 mm sweep complete all as specified. | 100 | Each job | 350 ₹35,000 | 500 ₹50,000 | 400 ₹40,000 | 375 ₹37,500 |
| 6.00 | Ditto all as per item Ser No. 4 above but wall mounted fan of 400 /450 mm sweep complete all as specified. | 100 | Each job | 350 ₹35,000 | 200 ₹20,000 | 400 ₹40,000 | 375 ₹37,500 |
| 7.00 | Ditto all as per item Ser No. 4 above but pedestal fans 600 /400 mm sweep complete all as specified. | 100 | Each job | 350 ₹35,000 | 200 ₹20,000 | 400 ₹40,000 | 395 ₹39,500 |
| 8.00 | Ditto all as per item Ser No. 4 above but industrial air circulator fans of any sizes complete all as specified and directed | 150 | Each job | 380 ₹57,000 | 100 ₹15,000 | 400 ₹60,000 | 425 ₹63,750 |
| 9.00 | S&F in replacement PVC body exhaust fan motor suitable for 250/300 mm of size of any make as per site requirement all as specified and directed. | 200 | Each | 500 ₹1 L | 500 ₹1 L | 400 ₹80,000 | 1,425 ₹2.9 L |
| 10.00 | S&F in replacement exhaust fan motor suitable for metallic body exhaust fan for 250/300 mm of size of any make as per site requirement all as specified and directed. | 100 | Each | 550 ₹55,000 | 400 ₹40,000 | 350 ₹35,000 | 2,150 ₹2.1 L |
Updated dates
Tender Value
₹49.9 L
EMD Value
₹99,800
Closing Date
2 Feb 2026, 6:00 pmClosed
GE(NW)KOCHI
GARRISON ENGINEER (NW) MILITARY ENGINEER SERVICES NAVAL BASE POST -682 004
AS PER BOQ AND TENDER DOCUMENT
2026_MES_747090_1
8567_GE_NW
Open Tender
Electrical and Maintenance Works
270 days
KOCHI
AS PER TENDER DOCUMENT
7 documents required · 7 mandatory
₹500
GE(NW)KOCHI
₹99,800
4 Apr 2026
3 Jan 2026
5 Feb 2026
3 Jan 2026
2 Feb 2026
19 Jan 2026
3 Jan 2026 - 19 Jan 2026
Attending complaint including transportion of tools for rectification of urgent nature of electrical complaints like checking of existing electrical items for continuous electric supply including carrying out such as minor repairs to ceiling fans / exhaust fans like replacement of capacitors, cleaning and oiling etc. as required to make the electrical items/ appliances fully functional at Kataribagh and Naval Base area at Naval Base during off hours (1700 hrs evening to 0900 Hrs morning ) on all working days all as specified and directed. NOTE:- (i) The contractor should display contact number at complaint cell to register users complaint. (ii) The recovery of rupees 1000 per complaint will be charged if contractor failed to attend that in stipulated time period . (iii) Number of complaints may vary day to day and shall be on required basis. Contractor shall quote their rates accordingly including in all aspects like labours,tool,transportation etc.
M&L for checking of ceiling fans stability (like fan hooks,nuts, bolts ,hanging rod ,canopy ,washer etc ) and exhaust fan stability at Naval base all as specified and directed. Note: - 1. The contractor should prepare seperate registers at AGE E/M (NW) Kochi and enter office name with signature of offce incharge and submitted to Engineer in Charge.
Taking down fan, sealing cable end, dismantling blades, removing fan, painting of ceiling fans complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc and refixing ceiling fan (M.D.supply) and connecting up including provision of cable from ceiling rose or connector to fan complete all as specified and as directed.
Taking down unserviceable ceiling fan of 1200mm/1400mm sweep, cutting out the existing burnt out fan motor winding, cleaning the motor slots, rewinding the motor with insulated copper winding wire of existing gauge, baking / heating up the motor to achieve the proper insulation resistance and refixing testing complete including marking MES No complete all as specified.
Ditto all as per item Ser No. 4 above but exhaust fan of 450/300/250 mm sweep complete all as specified.
Ditto all as per item Ser No. 4 above but wall mounted fan of 400 /450 mm sweep complete all as specified.
Ditto all as per item Ser No. 4 above but pedestal fans 600 /400 mm sweep complete all as specified.
Ditto all as per item Ser No. 4 above but industrial air circulator fans of any sizes complete all as specified and directed
S&F in replacement PVC body exhaust fan motor suitable for 250/300 mm of size of any make as per site requirement all as specified and directed.
S&F in replacement exhaust fan motor suitable for metallic body exhaust fan for 250/300 mm of size of any make as per site requirement all as specified and directed.
S&F ball bearing 6201 suitable for ceiling fans complete all as specified and directed.
S&F ball bearing 6202 suitable for ceiling fans complete all as specified and directed.
S&F in replacement, capacitor for ceiling fans, 230 volts, 2.5 MFD including necessary soldering complete all as specified and as directed. Make Havells Cat Part No. QHPCWC5002X5 or its equivalent make as approved by GE
S&F in replacement, capacitor for any type of exhaust fan/ pedestal fan/ air circulator fan 230 volts AC including necessary soldering of capacity 4 MFD complete all as specified and directed. Make Havells Cat Part No. QHPCWC5004X0 or its equivalent make as approved by GE
S&F in replacement Nickel plated mild steel clamps, Nuts, Bolts, Washers and split pin suitable for ceiling fans any type, any make, any size all as directed.
S&F in replacement down rod made out of , suitably threaded and holed, made out of 15 mm dia GI tubes heavy grade, duly painted, 2' long, suitable for ceiling fans any type, any make, any size all as directed.
Ditto all as per item Ser No 16 above but 3' long
Ditto all as per item Ser No 16 above but 5' long
S& F in replacement copper conductor multistranded cable flexible 03 core PVC insulated of size 1.5 Sqmm at site/MES store yard complete all as specified and directed.
S&F in replacement Fan canopy with tightening screw/check nut, made out of PVC, suitable for ceiling fans any type, any make, any size all as directed.
S&F in replacement Rubber reel insulator, suitable for ceiling fans any type, any make, any size all as directed.
M&L in replacement for hanging hook for ceiling fan with nuts, bolts and washer min thickness 15 mm all as specified and directed
Supply and fixing in replacement of ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and as directed. Make : Havells Cat Part No.Epic/ Orient Model Ecotech Neu BLDC 5 star or its equivalent makes from the list of approved makes Note : Old ceiling fan will be deposited in MES store yard.
Supply and fixing in replacement of 450mm sweep, metallic body exhaust fan heavy duty, single phase 230 volts, all as specified & directed. Make : Havells Cat Part No. Turbo Force SP or its equivalent make from the list of approved makes Note : Old exhaust fan will be deposited in MES store yard.
Supply and fixing in replacement of 300mm sweep, metallic body exhaust fan heavy duty, single phase 230 volts, all as specified & directed. Make : Havells Cat Part No. Turbo Force SP or its equivalent make from the list of approved makes Note : Old exhaust fan will be deposited in MES store yard.
Supply and fixing in replacement of 250mm sweep, PVC body exhaust fan heavy duty, single phase 230 volts, all as specified & directed. Make : Havells Cat Part No. Ventil Air-DX white or its equivalent make from the list of approved makes Note : Old exhaust fan will be deposited in MES store yard.
Supply and fixing in replacement of Pedestal Fans, metallic body 400 mm sweep Five star rated with brushless direct current motor (BLDC) complete all as specified and as directed. Make Orient Cat Part No. Tornado-II or its equivalent makes from the list of approved makes Note : Old Pedestal fan will be deposited in MES store yard.
Supply and fixing in replacement of metallic body wall fans 230 volts single phase oscillating 400 mm sweep Five star rated with brushless direct current motor (BLDC) suitable for wall mounting complete all as specified and directed. Make : Orient Cat Part No. Wall 47 or its equivalent makes from the list of approved makes Note : Old wall fan will be deposited in MES store yard.
Supply and fixing in replacement of metallic body wall fans, heavy duty, 230 volts single phase oscillating 450 mm sweep Five star rated suitable for wall mounting complete all as specified and directed. Make : Orient Cat Part No. Tornado Wall-II or its equivalent makes from the list of approved makes Note : Old wall fan will be deposited in MES store yard.
M & L in replacement Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanized iron wire 4 mm dia as earth up to 7.5 m distance and connected by means of bolts, nuts, checknuts and washers of galvanised iron or steel all shown in electric plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including provision of necessary excavation and earth work in any type of soil, PCC pit , RCC cover 50 mm thick, reinforced with 8 mm dia TMT bars both ways @ 10mm c/c ,20 mm bore medium grade watering pipe, water funnel, 15 mm bore GI light grade protection pipe, common salt, charcoal dust, returning, filling in of soil, removal of spoil to a distance not exceeding 50 mtr etc including testing on completion complete all as specified. Note :- (i) The unit rate includes for protection pipe and earth lead upto 7.50 Mtr. (ii) Earth lead beyond 7.50 Mtr length shall be measured and paid separately.
M&L in replacement of earthing complete with galvanised steel earth plate electrode 60 cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth strip 25 x 4 mm as earthing lead by means of bolts nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. point 3 connected to earthing test point all as specified or indicated including testing on completion including provision of necessary excavation and earth work in any type of soil, PCC pit , RCC cover 50 mm thick, reinforced with 8 mm dia TMT bars both ways @ 10mm c/c , 20 mm bore medium grade watering pipe, water funnel, 40 mm bore GI light grade protection pipe, common salt, charcoal dust, returning, filling in of soil, removal of spoil to a distance not exceeding 50 mtr etc including testing on completion complete all as specified. Note :- (i)The unit rate includes for protection pipe and earth lead upto 7.50 Mtr. (ii) Earth lead beyond 7.50 Mtr length shall be measured and paid separately.
M&L in repair/replacment of earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, burried directly in ground ( earth pit not less than 2.25 mtrs below ground level) with top edge of the plate not less than 1.5 mtr normal ground level, connected to GI strip 32x6 mm as earth lead by means of bolts, nuts, check nuts and washers of GI or steel as shown in electrical plate No 3 connected to earthing test point all as specified and directed inclusing testing complete all as specified and directed by Eng-in-charge Note:- Earthing should be interconnected
M&L for maintenance free chemical earthing with 01 No of copper cladded 17mm dia nickel cadmium steel with high tensile strength electrode of each of 1.8m each jointed with suitable compressive coupler planted at depth not less that 1.80m depth and duly covered with low resistant superior conductive powdered non corrosive, concrete brand earth enhancing material all as directed including connecting up to the common bus bar for a length upto 7.5 m with copper strip of size 25 x 4mm to achieve an earth resistance of below 2.0 Ohms including suitable PCC earth chamber. The copper strip shall be jointed to electrode with exothermic welding and all other joints shall be properly brazed complete all as directed after dismantling the existing unserviceable earthing. Make: M/S McML Protection Technologies Pvt Ltd. / M/S JMV Earthing Equipment Pvt Ltd / M/S JEF Techno Solutions (P) Ltd.
Taking down old unservicable earthing with GI wire/ GI strip any size complete all as specided and directed by Engineer-in- Charge
M & L Earth continuity conductor or main earthing lead fixed to wall on batten ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and directed
M & L for Earth continuity conductor or main earthing lead fixed to wall on batten ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25x 4 mm dia galvanised iron strip complete all as specified and directed
Supply and fix aluminium strip 25x3 mm complete with saddles and fixing screws for fitting the strip for lightening protection complete all as specified and directed
Supply and fix GI Strip 32x6 mm with saddle and fixing screws etc from test terminal block to earth pit or lightening protection complete all as specified and directed
Supply and fix Copper strip 20 x 3.15mm with saddles and fixing screws etc. for roof conductors / down conductors / connecting to earth pit to equipement including removing the old unserviceable strip and brazing all the joints complete all as directed..
S&F in repair/replacement on wall/ concealed on wall, 40mm dia light grade GI pipes including all necessary fittings, solvents, complete all as specified and directed
M&L in repair of pointed air termination aluminium rod 12 mm dia, 300 mm long complete all as specified and directed
M&L in repair of Air termination, single pointed, copper rod 12mm dia and 300mm long complete all as specified and directed
Supply and fix in repair/replacement of Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed
M&L for PCC 1:3:6 Type C-I using 20 mm gradaed agregate for PCC chamber of size 0.15m x 0.15m x 0.15m cube with and including FRP dunnage block, MS ferrule of suitable size and shape for mounting GI pipe 40 mm dia complete all as specified and directed by Eng-in-charge.
M&L for Checking of earthing resistance and E-N voltage with calibrated earth tester meter and multimeter including recharging of conventional earthing of lightening arrestor of building /workshop/hanger /OTM/Md Accn etc at Naval Base Kochi complete with Supply of saline water filling to earth pit in adequate quantity, chemical and, maintaining the earth testing record, rectification of earthing related fault including marking the earth resistance value using on the earth display board complete all as specified and as directed. Note: The earthing shall be tested in presence of user/user representative .
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
Tender8567.pdf
Tender Documents • 0.64 MB
BOQ_836596.xls
BOQ • 0.31 MB
PS8567.pdf
Additional Documents • 0.26 MB
Download all tender documents and submit your bid