| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹4.4 CrAccepted-AOC WEST BENGAL INDIA | DARJEELING | WEST BENGAL | 734001 | ₹4.4 Cr Quoted ₹8.7 Cr | 1 | Accepted-AOC L1 |
| 2 | 1₹4.4 CrAccepted-AOC | ₹4.4 Cr Quoted ₹8.7 Cr | 1 | Accepted-AOC L1 |
| 3 | 2₹9.0 CrRejected-Finance | ₹9.0 Cr | 2 | Rejected-Finance NOT L1 |
| Sl No | Description | Qty | Unit | NIMISHA CONSTRUCTION L1 | AMAL DUTTA ROY L1 | MS G C CONSTRUCTION L2 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation, testing and commissioning of remote type internal battery operated electromagnetic bulk flowmeter ( full bore or optimised full bore or reduced full bore) with inbuilt data logger& pulse outputs and can be upgraded to internal integrated 4G/5G based telemetry data transmission system in flow transmitter itself along with pressure transducer. Both the flow sensor and Flow transmitter shall be IP68 & shall have OIML R49 approved for Class 1 & class 2.Meter shall have in situ verification capability. Flow tube material shall be Stainless steel.Flow sensor housing shall be SS316/ fully welded carbon steel & shall be buriable design in nature. Liner material EPDM/Hard rubber/Elastomer/polypropylene with WRAS approval. Battery life shall be 8-10 years. All the connections between flow sensor & transmitter shall be " MIL" grade IP68 plug & socket type.The flow transmitter electronics shall be completely tamper proof. (For detailed specification of the flowmeter, please refer Section-C and other clauses of this NIT) including Excavation of soil/bituminous road/ concrete road and supply, laying of suitable length of HDPE/GI pipe (Materials gradePE-100,PN6/TATA) of different sizes compatible to the flowmeters of different sizes having minimum 12 mtr length for each battery operated electromagnetic flowmeter crossing the user premise boundary and interfacing with existing distribution pipeline of MOC HDPE/DI/OPVC with all necessary fittings maintaining the depth (av.) 1.10m.earth cushion from top of the pipe upto G.L. including loading ,unloading, carrying, lowering laying fitting fixing carefully pipes with the battery operated flowmeter & backfilling of the trench with the excavated soil and ramming upto ground level and repair the excavated portion as per the BOQ mentioned in Section-D and abiding by the clauses of Scope of Work as mentioned in Section-A and in other relevant clauses of this NIT and as per the instruction and satisfaction of the E.I.C. and submission of meter reading data for one year. | ||||||
| 1.01 | Bulk water meter size - 25 mm; Ferrule size - 10 mm | 1 | Nos | 1,88,000 ₹1.9 L | 1,88,000 ₹1.9 L | 2,00,000 ₹2 L |
| 1.02 | Bulk water meter size - 25 mm; Ferrule size - 15 mm | 3 | Nos | 1,88,000 ₹5.6 L | 1,88,000 ₹5.6 L | 2,00,000 ₹6 L |
| 1.03 | Bulk water meter size - 25 mm; Ferrule size - 20 mm | 198 | mm | 1,86,500 ₹3.7 Cr | 1,86,500 ₹3.7 Cr | 1,95,000 ₹3.9 Cr |
| 1.04 | Bulk water meter size - 40 mm; Ferrule size - 25 mm | 110 | km | 1,98,000 ₹2.2 Cr | 1,98,000 ₹2.2 Cr | 2,05,000 ₹2.3 Cr |
| 1.05 | Bulk water meter size - 40 mm; Ferrule size - 32 mm | 76 | KK | 2,00,000 ₹1.5 Cr | 2,00,000 ₹1.5 Cr | 2,05,000 ₹1.6 Cr |
| 1.06 | Bulk water meter size - 40 mm; Ferrule size - 40 mm | 62 | Nos | 2,00,000 ₹1.2 Cr | 2,00,000 ₹1.2 Cr | 2,05,000 ₹1.3 Cr |
Tender Value
Refer Docs
EMD Value
₹10 L
Closing Date
15 Oct 2025, 5:30 pmClosed
SECTOR-VI INDUSTRIAL TOWNSHIP AUTHORITY
Nabadiganta Bhawan, Sector-V, 3rd Floor, Kolkata - 700091
Supplying, installation, testing and commissioning of 25 mm and 40 mm diameter bulk water meters........jurisdiction under AMRUT 2.0 scheme.
2025_UDMA_901990_1
SEC-VI_ITA_10 Of 2025-2026
Open Tender
CIVIL WORKS
180 days
KOLKATA
Please refer Tender documents.
3 documents required · 3 mandatory
₹10 L
12 Dec 2025
18 Sept 2025
17 Oct 2025
18 Sept 2025
15 Oct 2025
18 Sept 2025
Amount
Supply, Installation, testing and commissioning of remote type internal battery operated electromagnetic bulk flowmeter ( full bore or optimised full bore or reduced full bore) with inbuilt data logger& pulse outputs and can be upgraded to internal integrated 4G/5G based telemetry data transmission system in flow transmitter itself along with pressure transducer. Both the flow sensor and Flow transmitter shall be IP68 & shall have OIML R49 approved for Class 1 & class 2.Meter shall have in situ verification capability. Flow tube material shall be Stainless steel.Flow sensor housing shall be SS316/ fully welded carbon steel & shall be buriable design in nature. Liner material EPDM/Hard rubber/Elastomer/polypropylene with WRAS approval. Battery life shall be 8-10 years. All the connections between flow sensor & transmitter shall be " MIL" grade IP68 plug & socket type.The flow transmitter electronics shall be completely tamper proof. (For detailed specification of the flowmeter, please refer Section-C and other clauses of this NIT) including Excavation of soil/bituminous road/ concrete road and supply, laying of suitable length of HDPE/GI pipe (Materials gradePE-100,PN6/TATA) of different sizes compatible to the flowmeters of different sizes having minimum 12 mtr length for each battery operated electromagnetic flowmeter crossing the user premise boundary and interfacing with existing distribution pipeline of MOC HDPE/DI/OPVC with all necessary fittings maintaining the depth (av.) 1.10m.earth cushion from top of the pipe upto G.L. including loading ,unloading, carrying, lowering laying fitting fixing carefully pipes with the battery operated flowmeter & backfilling of the trench with the excavated soil and ramming upto ground level and repair the excavated portion as per the BOQ mentioned in Section-D and abiding by the clauses of Scope of Work as mentioned in Section-A and in other relevant clauses of this NIT and as per the instruction and satisfaction of the E.I.C. and submission of meter reading data for one year.
Bulk water meter size - 25 mm; Ferrule size - 10 mm
Bulk water meter size - 25 mm; Ferrule size - 15 mm
Bulk water meter size - 25 mm; Ferrule size - 20 mm
Bulk water meter size - 40 mm; Ferrule size - 25 mm
Bulk water meter size - 40 mm; Ferrule size - 32 mm
Bulk water meter size - 40 mm; Ferrule size - 40 mm
AMAL DUTTA ROY (BID ID -7088224)
MS G C CONSTRUCTION (BID ID -7088192)