RequiredExperience with Government
RequiredCertificate (Requested in ATC)
RequiredOEM Authorization Certificate Bid to RA enabled Yes Online UPS ( 1 pieces ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Bid Requirement (Allowed Values) GENERIC Rating in KVA (KVA) 6.0 KVA 6.0 KVA Technology IGBT-PWM without inbuilt isolation IGBT-PWM without inbuilt isolation 1/35 transformer transformer Input Power single phase 160V - 260V sinewave
Required50Hz single phase 160V - 260V sinewave
Required50Hz Output power Single phase 230V +/-1% sinewave 50 Hz Single phase 230V +/-1% sinewave 50 Hz Backup time (Minutes) 60 60 Minimum VAH (VAH) 11000 11000 Warranty for UPS (Years) 5 5 Movable trolly for Batteries Without trollery but with rack Without trollery but with rack Warranty for battery 2 2 Degree of Protection IP20 IP20 Cabling 5 meters for input and out put Without Without Paralleling kit for synchronising Without Without Installation and Commissioning Yes * CONSTRUCTIONAL Minimum thickness of M.S.Sheet Enclosure duly painted (mm) 1.0 * Type of Battery SMF-VRLA conforming to JISC:8702(Pt.I
RequiredII&III) * FUNCTIONAL Maximum overshoot and Under shoot of output rated voltage 4 * Voltage Regulation from no load to full load (%) </= 3% * 20% Overload limit for minimum 10 minutes No
Requiredonly for 5 Minutes No
Requiredonly for 5 Minutes Overall Efficiency (%) >/=92% >/=92% Total Harmonic Distortion(THD) (%) Maximum 3% * 50% Overload limit for minimum 1 minutes No
Requiredonly for 3 seconds No
Requiredonly for 3 seconds PROTECTION Protection for under voltage at battery terminal at 10.5V per 12 V battery. Yes * Protection of Over Yes * 2/35 voltage
RequiredShort Circuit & over load at UPS output terminal METERING AND INDICATIONS Digital Metering in UPS for AC Input Voltage
RequiredOutput AC Volt age
RequiredCurrent
RequiredFrequency
RequiredBattery Voltage and Current Yes * Indicators for mains presence
RequiredBattery charging and discharging
RequiredOutput Over Load
RequiredLow Battery Voltage Yes * REPORTS AND CERTIFICATION Damp Heat : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C
Requiredtwo cycles of (12+12) hours each 2007) Yes * Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs Yes * Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs. Yes * Availability of the Type Test Report from Central Govt. NABL/ILAC Accredited lab covering all technical requirements. Yes * Type Test Certificate No. - * Type Test Certificate date - * Name of Lab - * Address of Lab - * As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as Not applicable presently * 3/35 applicable * Specifications highlighted in bold are the Golden Parameters. * Bidders may note that In respect of non-golden Parameters
Requiredthe specifications 'Values' chosen by Buyer will generally be preferred over 'Bid requirement ( allowed Values) by the Buyer. Additional Specification Documents