Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.8 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹11.1 L+₹3.9 L (54.8%)Rejected-AOC 06 KHASRA NUMBER 56 KIRAN NAGAR BASNI JODHPUR JODHPUR RAJASTHAN 342001 UDYAM RJ 22 0002214 | JODHPUR | RAJASTHAN | 342001 | L2 | Rejected-AOC Not lowest |
Tender Value
₹8 L
EMD Value
₹16,000
Closing Date
4 Jan 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) Jodhpur
GE (AF) Jodhpur
COMPREHENSIVE MAINTENANCE OF MISCELLANEOUS E/M ASSETS IN DOMESTIC AREA AND SU AT AF STN JODHPUR
2021_MES_488975_2
8495/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
GE (AF) Jodhpur
As per NIT
6 documents required · 6 mandatory
₹500
GE (AF) Jodhpur
₹16,000
Yes
19 Jan 2022
16 Dec 2021
6 Jan 2022
16 Dec 2021
4 Jan 2022
23 Dec 2021
60 days
Amount
Supply & fixing in replacement LED decorative post top lantern 40Watt IP65 protection resistant to impact and corrosion, glare free with all necessary acessories required complete all as specified and directed by the Engineer in Charge.
Material and labour for submain wiring with two single core PVC insulated multi stranded copper conductor cable FRLS of size 6 sqmm 1100 volt grade (ISI marked ) drawn through PVC casing & caping with necessary fittings, with one 4 Sqmm single core multi stranded copper conductor cable FRLS as earth continuity to common earth doly as earth wire, including dismantling and taking down old unserviceable submain wiring complete all as specified and directed by the Engineer in Charge. Note : Two runs of main wire and one run of earth wire & one run of casing caping shall be measured and paid as one length.
Material and labour for submain wiring with two single core PVC insulated multi stranded copper conductor cable FRLS of size 10 Sqmm 1100 volt grade (ISI marked ) drawn through PVC casing & caping with necessary fittings, with one 6 Sqmm single core multi stranded copper conductor cable FRLS as earth continuity to common earth doly as earth wire , including dismantling and taking down old unserviceable submain wiring complete all as specified and directed by the Engineer in Charge. Note : Two runs of main wire and one run of earth wire & one run of casing caping shall be measured and paid as one length.
Material & labour in replacement for DB SPN 8 way IP-43 protection, double door fixed on wall with incoming MCB SPN 63 Amps 16KA - 01 No and outgoing MCB SP- 6 TO 32 amps ‘C’ curve type 6 No including necessary connection etc complete all as specified and directed by the Engineer-in-Charge.
Material & labour in repairs for earthing complete with galvanised steel earth plate electrode 60 cm x 60cm x 6 mm buried directly in ground vertically to depth not less than 2.25 m below normal ground level with top edge of the earth plate at a depth not less than 1.5m below ground level connected to and including GI earth strip of size 25mm x 4mm by means of nuts, bolts, check nuts and washer etc, made of GI and connected to test point and earth dully all as shown in electrical plate No. 3 SSR Part-I 2009 and specified or indicated including excavation and earthwork in any type of Soil, PCC (1:3:6) Type C1 in chamber, precast RCC 50 mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric or XPM (Weight not less than 4.00 Kg/Square metre) with PCC frame, funnel with wire mesh, 20mm bore medium grade GI watering pipe, lugs, 40mm bore medium grade GI protection pipe, test point etc. including dismantling old unserviceable earhing complete all as specified and directed by the Engineer in Charge. Note: - Item includes the cost of 7.5 metre GI pipe for protection of earth lead & also the cost of 7.5 metre GI earth lead.
Material & Labour for dismantling LT panel and removing all the connections including copper/aluminium busbar & removing the carbon from the contacts by cleaning through CTC SOLUTION and, after disconnecting cable. Replacment of the unserviceable or defective parts , rusted nuts and bolts ,old damaged/ corroded door hinges /door lock/bus bar, front or back door etc and re-assemble the panel with all the connections properly tight and checked. Control wiring and CT/PT connections of the panel shall be proper to be made serviceable to the entire satisfaction of the Engineer in Charge. Foundation of the panel shall be repaired with existing specifications if deteriorated and coloured with base frame properly mounted, and testing on completion of job complete all as specified and directed by the Engineer- in-Charge. Note :- Defective MS work, copper bus bar shall be measued & paid as supply only item no. 7 & 8 given here in after.
Supply only in repairs LT panel /AMF panel/HT bus panel front /back door made of GI 3.15 mm thick sheets with hinges and lock system, panel should be well welded complete all as specified and directed by the Engineer-in-Charge.
Supply only in replacement copper bus bar of existing size for LT panel including pvc Insulation, with reconnection of LT cable and seperator complete all as specified and directed by the Engineer-in-Charge.
Material and labour for complete removal of existing treatment from iron surfaces of the LT panels of size 10 Sqm to 25 Sqm by cleaning/ rubbing/ scrapping & prepration of surfaces and material and labour for applying two coats of synthetic enamelled paint over a coat of red oxide primer, paint shall be as per the existing colour of panel complete all as specified and directed by the Engineer in Charge. Note:- Painting to Panels Shall be carried out with spray gun equipments.
Material and labour for complete removal of existing treatment from iron surfaces of the LT panels of size 25 Sqm to 50 Sqm by cleaning/ rubbing/ scrapping & prepration of surfaces and material and labour for applying two coats of synthetic enamelled paint over a coat of red oxide primer, paint shall be as per the existing colour of panel complete all as specified and directed by the Engineer in Charge. Note:- Painting to Panels Shall be carried out with spray gun equipments.
Material & labour in repairs of Angle iron frame of required size with a coat of black paint over one coat of red oxide primer complete all as specified and directed by Engr-in-Charge.
Supply and fix in repairs phase indicating lamp R-Y-B. LED type , fixed in existing LT panel board etc complete all as specified and directed by the Engineer-in-Charge.
Material & labour in replacement of LT Feeder Pillar (Kiosk) of size not less than L= 60 cm x 45 cm x 45 cm (H) made out 3.15 mm thick GI sheet, outdoor type (CPRI approved) with openable front door including locking arrangement, with Copper Busbar 200 amps rating with MCCB 125 Amps, 25 KA and fixed on and including angle iron frame and PCC plinth as required complete all as specified and directed by the Engineer-in-Charge.
Supply, install, testing and commissioning in repairs on load change over switch 630 Amps , four pole 415V AC , 50HZ etc in sheet metal enclosure complete all as specified and directed by the Engineer-in-Charge.
Supply install, testing and commisioning in replacement of LT panel board floor mounted cubical type, indoor double door type, dust proof aesthetically designed. manufactured by CPRI approved, fabricated of minimum 3.15 mm thick outer CRCA sheet and minimum 2 mm thick inner CRCA sheet, depth of panel not less than 45 cm, with front and rear opening confirming to IS-8623 and including bus bar chamber continuous GI strip earth bus bar din rail channels cable alley danger notice board also including MS angle iron base frame of required size , 0.30 m above ground level and 0.30m grouted in ground/floor all including necessary excavation in PCC/any type of soil, required foundation in cement concrete 1:4;8 type D2, complete with locking arrangement powder coated rust proof paint connecting incoming and outgoing cable connections with suitable lugs nut bolts washers and cable glands prewired complete with suitable size PVC insulated fire retardant copper conductor complete all as specified and directed and shall consists of the following items:- (a) Copper bus bar of suitable size mounted on PVC insulators - 4 strips (b) Phase indicating lamps ( RYB) - 3 Nos (c ) Multifunction meter for measuring Amp, voltage, frequency etc complete - 1 No (d) MCCB 400 Amps, 36 KA, 04 pole, 415 V, with thermal and magnetic release with manual drawout type- 01 No for incoming. (e ) MCCB 160 Amps 36 KA, 4 pole with thermal and magnatic release ICU=ICS 100% - 3 Nos for Outgoing.
Supply, Laying, Testing and Commissioning in replacement LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables 25 Sqmm 4 core (heavy duty) 1100 Volts grade with stranded Aluminium conductor laid in trenches/ fixed on walls/ floor/ road / culverts/ poles or encased in GI pipe with root marking complete all as specified & directed by the Engineer-in-Charge.
Supply, Laying, Testing and Commissioning in replacement LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables 16 Sqmm 4 core (heavy duty) 1100 Volts grade with stranded Aluminium conductor laid in trenches/ fixed on walls/ floor/ road / culverts/ poles or encased in GI pipe with root markingcomplete all as specified & directed by the Engineer-in-Charge. Note for Ser Item no 16-17:- (i) Sand cushionig, cable protection, GI protection pipe, clamps, testing kits, excavation and earthwork shall be measured and paid seperately. (ii) The rate quoted shall deemed to be included of taking out cable with cable protection cover and stacking neatly for re-use in the work.
Excavation in trenches in soft/loose soil, not exceeding 1.5 metres wide and not exceeding 1.5 metres in depth for foundation/cable trench/laying of pipe line/taking out pipe etc complete all as specified and directed by Engineer-in-charge.
Returning, filling in, including spreading leveling, watering and well ramming the excavated soil in layers not exceeding 25 cm thick complete all as specified and directed by Engineer-in-Charge.
Removal of surplus excavated soil to a distance not exceeding 50 metre distance and depositing as directed at a level not exceeding 1.5 metre above starting point complete all as specified and directed by Engineer-in-Charge.
Material & labour for sand cushioning for PVC cable with tibba sand (one layer of 80 mm thickness before laying of cable and other layer of 150 mm thickness after laying of cable) & punning down to 180 mm to provide a required cover complete all as specified and directed by the Engineer-in-Charge. Note:- Punned thickness only shall be measured and paid.
Laying only 40 to 50 mm thick rough dressed Jodhpur type stone slab cover 25 to 30 cm wide and not less than 50 cm in length retreived from excavation, laid dry abutting each other for protection of cable complete all as specified and directed.
Material & labour for boring of holes under road pavement, hard standing etc manually with 50mm light grade GI pipe complete all as specified and directed by the Engineer-in-Charge.
Supply & fixing in replacement of PVC insulated copper cable of 2.5 Sqmm 2 core for connection of security light to junction box complete all as specified and directed by the Engineer-in-Charge.
Supply & fixing in replacement 100W LED flood light made up of pressure die cast aluminium housing with high efficient LED as lighting source with toughened glass having IP66 protection and impact resistance of IK07, with potted driver 230 Volt with all connected acessories required complete all as specified and directed by the Engineer-in-Charge.
Supply and fixing in replacement of multicolor water proof fountain light of 5 watt with all connected acessories required complete all as specified and directed by the Engineer-in-Charge.
Supply and fixing in replacement of white/warm/any color LED focus light of 9 watt with all connected acessories required complete all as specified and directed by the Engineer-in-Charge.
new india engineers
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .