Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹51.2 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹67.9 L+₹15.6 L (29.9%)Rejected-Finance 70 VARDHMAN NAGAR A P O SHYAM NAGAR AJMER ROAD JAIPUR PIN 342019 | JAIPUR | 342019 | L2 | Rejected-Finance OTHER THAN LOWEST |
| Sl No | Description | Qty | Unit | M/s Prem Associates L1 | Pioneer Enterprises L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing & commissioning of Outdoor (IP54) 11kV 630Amps 21KA/3 sec. One side Extensible Ring Main Unit Compact switchgear (outer enclouser made of powder coated 2mm thickness CRCA sheet) consisting of 2 nos. fixed morotized Load break switch module and 5 nos. fixed motorized Vacuum Circuit Breaker Module with additional BUS PT metering module and Copper Busbar in SF6 insulated stainless steel enclosure (IP67, 2.5mm thick, SS304 grade). THe complete RMU must be type tested for Internal arc 21KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber. HT RMU shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. The Vaccum Interrupter must be of RMU manufacturer's own make. Complete RMU shall be in compliance with standard IEC 62271-200 & VCB as per IEC 62271-100.
Make of RMU shall : ABB/ SIEMENS/ SCHNEIDER INFRASTRUCTURE [ Channel partner / System Integrator / Authourized Partner/ License partner make RMU shall not be accepted. Note: Cost of grouting RMUs with suitable PCC as per OEM's requirement is deemed to be included in the quoted rate.
The complete RMU shall be consisting of followings: | 2 | Set | 23,90,000 ₹47,80,000 Lowest | 31,25,000 ₹62,50,000 |
| 1.01Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along with series trip coil (Modbus RS485 complaint) for each VCB Module. | |||||
| 1.02Capacitative voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. | |||||
| 1.03SF6 Gas pressure indicator on the gas tank. | |||||
| 1.04Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO amd suitable for 10000 mechanical operation. | |||||
| 1.05CT shall be minimum 100/1A ,2.5VA , 5P20 - 3 nos. for protection in each VCB module. | |||||
| 1.06CT shall be minimum 100/1A ,2.5VA , Class 0.5 - 3 nos. for metering in each VCB Module. | |||||
| 1.07MFM for measurement of Current, Voltage, Frequency, PF, KWH etc. for each VCB Module. | |||||
| 1.08Master Trip relay for each VCB Module - 1 No. | |||||
| 1.09Right angle boot to be provided in each module. | |||||
Tender Value
₹69.4 L
EMD Value
₹1.3 L
Closing Date
30 Jan 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE JAIPUR
Military Engineer Services, HQ Commander Works Engineer, KalyanMarg, Banipark, Jaipur-06
CONVERSION OF 2 POLE / 4 POLE STRUCTURES INTO RMUS IN SOUTHERN SECTOR AT KOTA MIL STN
2026_MES_747010_1
82513/KOTA/E8
Open Tender
Civil Works
Item Rate
180 days
GE KOTA
AS PER NIT
6 documents required · 6 mandatory
₹1,000
GE KOTA
₹1.3 L
Yes
HQ CWE JAIPUR
26 Mar 2026
2 Jan 2026
2 Feb 2026
2 Jan 2026
30 Jan 2026
24 Jan 2026
9 Jan 2026
Each Job
Each Job
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
tender82513.pdf
Tender Documents • 0.77 MB
BOQ_836504.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .