RequiredOEM Authorization Certificate Online UPS ( 4 ) ( Under PAC ) Make numeric Model numerichpmaxonlineups-5.0kva-1p1p-30min-62 40vah-5y-withparallelingkit Technical Specifications * As per GeM Category Specification Specification Specification Name Values Bid Requirement (Allowed Values) GENERIC Rating in KVA (KVA) 5.0 KVA 5.0 KVA Technology IGBT-PWM with inbuilt isolation transformer IGBT-PWM with inbuilt isolation transformer 1/4 Input Power single phase 160V - 260V sinewave
Required50Hz single phase 160V - 260V sinewave
Required50Hz
RequiredThree phase 300 V - 450V sinewave
Required50Hz Output power Single phase 230V +/-1% sinewave 50 Hz Single phase 230V +/-1% sinewave 50 Hz
Required3 Phase 400V +/-1% with alternative user setable setting of 380V +/-1% 50 Hz Backup time (Minutes) 30 15
Required30
Required60
Required90
Required120
Required180
Required240 Minimum VAH (VAH) 6240 400 - 640000 Warranty for UPS (Years) 5 1
Required2
Required3
Required4
Required5 Movable trolly for Batteries Without trollery but with rack With
RequiredWithout
RequiredWithout trollery but with rack Warranty for battery 2 1
Required2 Degree of Protection IP21 IP21
RequiredIP20 Cabling 5 meters for input and out put Without With
RequiredWithout Paralleling kit for synchronising With With Installation and Commissioning Yes * CONSTRUCTIONAL Minimum thickness of M.S.Sheet Enclosure duly painted (mm) 1.2 * Type of Battery SMF-VRLA conforming to JISC:8702(Pt.I
RequiredII&III) * FUNCTIONAL Maximum overshoot and Under shoot of output rated voltage 4 * Voltage Regulation from no load to full load (%) </= 3% * 20% Overload limit for minimum 10 minutes Yes Yes
RequiredNo
Requiredonly for 5 Minutes Overall Efficiency (%) >/=90% >/=90%
Required>/=92%
Required>/=94%
Required>/=96% Total Harmonic Distortion(THD) (%) Maximum 3% * 50% Overload limit for minimum 1 minutes Yes Yes
RequiredNo
Requiredonly for 3 seconds PROTECTION Protection for under Yes * 2/4 voltage at battery terminal at 10.5V per 12 V battery. Protection of Over voltage
RequiredShort Circuit & over load at UPS output terminal Yes * METERING AND INDICATIONS Digital Metering in UPS for AC Input Voltage
RequiredOutput AC Volt age
RequiredCurrent
RequiredFrequency
RequiredBattery Voltage and Current Yes * Indicators for mains presence
RequiredBattery charging and discharging
RequiredOutput Over Load
RequiredLow Battery Voltage Yes * REPORTS AND CERTIFICATION Damp Heat : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C
Requiredtwo cycles of (12+12) hours each 2007) Yes * Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs Yes * Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs. Yes * Availability of the Type Test Report from Central Govt. NABL/ILAC Accredited lab covering all technical requirements. Yes * Type Test Certificate No. NTS/PPTL/UPS-303/15 * Type Test Certificate date 10.09.2015 * Name of Lab NISAKI TECHNOLOGY * Address of Lab Bangalore-560027 * 3/4 As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Not applicable presently * * Bold specifications are the golden parameters.