Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC Gonda
220 KV Sub-station Gonda Campus, Jail Road, Gonda.
Work
2023_UPTCL_797581_1
02/ETC(GD)/2023-24
Open Tender
Electrical Works
Fixed-rate
90 days
BAHRAICH
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,534
EE ETD
₹13,000
Yes
9 May 2023
17 Apr 2023
2 May 2023
17 Apr 2023
2 May 2023
17 Apr 2023
Erection of Main structures required for beam & column for main bus and transfer bus. Erection of Auxiliary structures required for installation of Isolators, CTs, PTs, LAs, and other equipment. The job consists of shifting of all material i.e. structure parts, nuts, bolts, washers etc. from store to site of erection, erection of structure as per relevant drawing and practices using flat and spring washer with each bolt. Matching of holes, cutting, matching of members if required shall also be done by the contractor without any extra cost to complete the work satisfactorily. All material to be erected shall be supplied by UPPTCL free of cost but all men and T&P required for satisfactory completion of work shall be arranged by the contractor at his own cost.
Main Structure
Auxiliary Structure
Opening of following size old and used aluminum power cable 500 mm below ground level including excavation of trench then opening of cable and all other associated works to complete the job satisfactorily.
145 KV Circuit Breaker
145 KV CTs
145 KV CVT/PT
145 KV Line Isolator (Motorized)
145 KV Bus Isolator(Motorized)
145 KV Tandem Isolator(Motorized)
145 KV Post Insulator
132 KV Control & Relay Panel
ABT Energy Meter with cubical
Junction Box for 145 KV CTs/ PTs
Laying of following sizes of control cable in the cable trench from control & relay panels to various equipment, J.B. etc. in switchyard as per cable schedule, its saddling at every 750 mm. distance with M.S. Saddles of size 25x3mm size including carriage of cable drums from store to laying site and shifting back to store and all other associated work to complete the job satisfactorily.
2Cx2.5 Sq. mm. Unarmored
4Cx2.5 Sq. mm. Unarmored
6Cx2.5 Sq. mm. Unarmored
Termination of following sizes of cable as laid above as per cable schedule including making necessary holes in glands plates of box wherever required, supply and fixing of cable glands of appropriate size, supply and providing ferrules and Nos. for each core of cable and its termination with crimping type lugs of Dowell/Tension make and all other associated work to complete the jobs satisfactorily.
2Cx2.5 Sq. mm. Unarmored
4Cx2.5 Sq. mm. Unarmored
6Cx2.5 Sq. mm. Unarmored
Stringing of 132 KV Bus bar all three phases including measuring, cutting, crimping, fixing and all associated works with the help of required tension fittings & suspension fittings, 70 KN/120 KN disc insulator, caring of 10 No. insulators at each both end of bus bar, U bolts complete with PG Clamps, bus post clamps, connectors and all other associated works required to complete the job satisfactorily.
Main bus bar for 132 KV Bay (1 x Moose conductor) 36 mtr. Span.
Transfer bus bar for 132 KV Bay (1 x Panther conductor) 36 mtr. Span.
Interconnection of following equipment and bus bar including cutting, bending of conductor and jumpering clamping along with all other associated work to complete the job satisfactorily as per drawing with Main + Transfer bus system.
132 KV Line bay (1 x Moose/Panther Main + Panther/Panther Transfer bus system)
Earthing of various equipment main & aux. structure at cross ends and trench with MS Flat of following size. The work comprises of making trenches by digging of earth up to the earth mat level, laying of MS Flat of the dug trench as well as above ground on equipment/structure along with its bending to give proper shape excluding the cost of MS Flat. Painting of the MS Flat with one coat of red oxide primer and two coat synthetic enamel paint (1st quality of Burger/Asian make) would have to be done along with filling of earth in trenches.
Special Delta Earthing of LAs consisting of fabrication of 6 Nos. 3 mtr. Long electrodes, its placing inside ground and connection all 6 electrodes with 75 x 10 mm M.S. Flat and connection the same. Excluding the cost of M.S. Bar & Flat. (36/40 mm. dia)
Laying of 36/40 mm dia MS Round bar 900 mm below ground level including cutting, excavation straightening, welding painting and all other associated works to complete the work satisfactorily as per drawing and technical specification excluding the cost of MS Bar.
Cutting & fabrication of 3 Mtr long electrode with 36/40 mm dia MS Rod having 150 mm long conical shape and then its piercing vertically in side the ground with top 900 mm. below ground level and its welding with earthmat, excluding the cost of MS Bar.
Cutting of cleats of size 45x45x6 mm angle iron & thereafter fixing of cleats of angle iron by welding to make joint with the electrode and earthmat at required places including cost of angle iron, electrodes, labour and T&P etc.
Painting of phase sequence by red, yellow & blue colour.
Providing & fixing/concealed laying of following size B-class Jindal/JTC/TATA or other standard make ISI approved GI pipes complete with assembly such as bend, tee, socket, clamps etc. including cost of threading, welding, earth work, cutting bricks, filling the trenches/brick cuttings etc required for completion of work as per site requirement with all material, labour, T&P complete. Laying of 2/4 core 2.5 mm sq. control cable through above pipe including cost of glands, ferrules & termination of 1.25" G.I. Pipe.
Earthing of various equipment main & aux. structure at cross ends and trench with MS Flat of following size. The work comprises of making trenches by digging of earth up to the earth mat level, laying of MS Flat of the dug trench as well as above ground on equipment/structure along with its bending to give proper shape excluding the cost of MS Flat. Painting of the MS Flat with one coat of red oxide primer and two coat synthetic enamel paint (1st quality of Burger/Asian make) would have to be done along with filling of earth in trenches.
Water mist and CAF fire extinguisher back pack capacity 10 ltr. Using spl. AFFF compound with fire rating 55A, 2338, 1000V. (i) One spare compressed air cylinder 2 ltr x 500 bar (Carbon Composite) (ii) 10 Nos O-rings for pressure vessel (iii) One CAN 5 ltr special AFFF compound (iv) Tool Kit - 01 No.
DURGA CONSTRUCTION AND GEN. ORDER SUPPLIERS
M/S Rudra Construction
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .